background image

(Models: AI 7442 / 7842 / 7742 / 7942 / 7642)

1. DISPLAY TYPE

: 4- Digit 7 segment LED (RED)

STATUS LED’S

: OP1 : Main Control Output

OP2 : Alarm Status

2.

Sensor input

: J/K/Pt-100

Range

: Refer below Table.

Sampling Time

: 200 msec.

Resolution

: 1°C

CJC for TC

: Built in automatic

LWC for Pt-100

: Built in upto 18E max.

Digital Filter

: 1 to 10 Sec.

3.

Contact type

: N/O, CM, N/C

Contact Rating

: 5A @ 250VAC or 30 VDC

Life expectancy

: > 5,00,000 operations

Isolation

: Inherent

4.

Drive Capacity

: 12V @ 30mA.

Isolation

: Non-Isolated.

5.

1

:

INPUT

RELAY OUTPUT

SSR DRIVE OUTPUT

FUNCTION
Output

Main Control output

Output 2

: Programmable

1) Auxiliary control
2) Alarm

Control Action

: ON-OFF/T.P (Select)

Control Mode

: Heat/Cool (Select)

Compliance

: ----

6.

Operating Range

: 0 ~50°C, 5~90% Rh

Storage Humidity

: 85% Rh (Non-condensing)

7.

Supply Voltage

: 90~270VAC, 50/60Hz.

Consumption

: 4W Maximum.

8.

Housing

: ABS Plastic

ENVIRONMENTAL

POWER SUPPLY

PHYSICAL

SPECIFICATIONS : -

(48 X 48)

(72 X 72)

(96 X 96)

(48 X 96)

(96 X 48)

This controller is meant for temperature control
applications. It is important to read the manual prior to
installing or commissioning of controller. All safety related
instruction appearing in this manual must be followed to
ensure safety of the operating personnel as well as the
instrument.

The controller must be configured correctly for intended
operation. Incorrect configuration could result in damage
to the equipment or the process under control or it may
lead personnel injury.
The controller is generally part of control panel and in such
a case the terminals should not remain accessible to the
user after installation.

The Controller in its installed state must not come in close
proximity to any corrosive/combustible gases, caustic
vapors, oils, steam or any other process by-products.
The Controller in its installed state should not be exposed
to carbon dust, salt air, direct sunlight or radiant heat.
Ambient temperature and relative humidity surrounding
the controller must not exceed the maximum specified limit
for proper operation of the controller.
The controller in its installed state must be protected
against excessive electrostatic or electromagnetic
interferences. Ventilation holes provided on the chassis of
the instrument are meant for thermal dissipation hence
should not be obstructed in the panel.

The controller must be wired as per wiring diagram & it
must comply with local electrical regulation.
Care must be taken not to connect AC supplies to low
voltage sensor input.
Circuit breaker or mains s/w with fuse (275V/1A) must be
installed between power supply and supply terminals to
protect the controller from any possible damage due to
high voltage surges of extended duration.
Circuit breaker and appropriate fuses must be used for
driving high voltage loads to protect the controller from
any possible damage due to short circuit on loads.
To minimize pickup of electrical noise, the wiring for low
voltage DC and sensor input must be routed away from
high current power cables. Where it is impractical to do
this, use shielded ground at both ends.
The controller should not be wired to a 3-Phase supply with
unearthed star connection. Under fault condition such
supply could rise above 264 VAC which will damage the
controller.
The Electrical noise generated by switching inductive
loads might create momentary Fluctuation in display, alarm
latch up, data loss or permanent damage to the instrument.
To reduce this use snubber circuit across the load.

It is essential to install a over Temp. Protection device to

avoid any failure of heating system. Apart from spoiling the
product, this could damage the process being controlled.

SAFETY INSTRUCTION :

GENERAL

MECHANICAL

ELECTRICAL

v

v

v

v

v

v

v

v

v

v

v

v

v

v

Model no.

Display height

AI-7442 AI-7842 AI-7742 AI-7942 AI-7642

0.39”

0.39”

0.56”

0.56”

0.56”

USER’S OPERATING MANUAL FOR PID DIGITAL TEMPERATURE CONTROLLER

Model no.

Weight (gms.)

AI-7442 AI-7842 AI-7742 AI-7942 AI-7642

130

200

200

240

200

1

Document Name : OIM AI-7X42 (Ver 1.2) Page 1 of 6

Fe-K(J) T/C

Cr-AL(K) T/C

Pt-100 (RTD)

Pt-100 (RTD 0.1)

Sensor Type

Accuracy

± 1 C

o

± 0.3 C

o

0

760 C

~

o

-99 ~ 1300 C

o

-100

450 C

~

o

-100.0

450.0 C

~

o

Resolution

Range

1 C

o

1 C

o

1 C

o

0.1 C

o

}

Reviews: