Version 1.0 09/08/2017
http://www.inorea.com
32
No.
Code
Parameter name
Setting range
Factory default Change
Reference page
56.
F2.01
Reserved
2: Motor reverse running
3: Fault output
4: Frequency level
detection FDT output
5: Frequency arrival
6: Zero speed running
7: Upper limit frequency
arrival
8: Lower limit frequency
arrival
9 to 10: Reserved
57.
F2.02
Reserved
58.
F2.03
Relay output selection
1
☆
58
59.
F2.04
AO1 output selection
0: Running frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: Analog input AI1 value
7: Analog input AI2 value
8: Run speed
9 to 10: Reserved
0
☆
59
60.
F2.05
AO1 output lower limit
0.0% to F2.07
0.0%
☆
59
61.
F2.06
Lower limit corresponds to
AO1 output
0.00V to 10.00V
0.00V
☆
59
62.
F2.07
AO1 output upper limit
F2.05 to 100.0%
100.0%
☆
59
63.
F2.08
Upper limit corresponds to
AO1 output
0.00V to 10.00V
10.00V
☆
59
64.
F2.09
MO1 Turn-on delay time
0.0~3600s
0.0s
☆
60
65.
F2.10
MO1 Turn-off delay time
0.0~3600s
0.0 s
☆
60
66.
F2.11
Turn-on delay time of relay
0.0~3600s
0.0 s
☆
60
67.
F2.12
Turn-off delay time of relay
0.0~3600s
0.0 s
☆
60
68.
F2.13
Reserved
69.
F2.14
D0 terminal active status
selection
0x00 to 0x1F
00
☆
60
70.
F2.15
MO1 output type selection
0: pulse output
1: digital output
☆
60