Code
Parameter name
Setting range
Factory default
Change
Combine ENABLE and direction. This mode is the most commonly used two-wire mode. The forward and reverse running of
motor is determined by the defined FWD, REV terminal commands.
1: Two-wire type control 2
Separate ENABLE and direction. FWD defined by this mode is the enable terminals. The direction is determined by the
defined REV state.
Two-wire type control 1 (Combine ENABLE and direction) Two-wire type control 2 (Separate ENABLE and direction)
2: Three-wire type control 1
In this mode, DIn is as the enable terminal, SB1 as level control is active; the running command is controlled by the pulse
rising edge of SB2 or SB3 so as to control forward or reverse of the motor; the stop command is controlled by the switch
SB1.
3: Three-wire type control 2
In this mode, DIn is as the enable terminal, SB1 as level control is active; the running command is produced by FWD, SB2 as
pulse edge control is active, the running direction of motor is determined by REV, K1 as level control is active.
FWD
REV
COM
SB2
DIn
K1
SB1
Inverter
FWD
REV
COM
SB2
DIn
SB1
SB3
SB2
SB3
Stop button
Forward
Three-wire control mode 1
button
Reverse
button
SB2
SB3
Running
Forward
Reverse
direction
Three-wire control mode 2
Inverter
SB1
SB1
F1.07
Change rate of terminal UP/DOWN
frequency increment
0.01 to 50.00Hz/s
0.50Hz/
s
☆
When the terminal UP/DOWN is used to adjust the set frequency, the rate of frequency change, i.e. frequency change
amount per second.
F1.08
AI1 lower limit
0.00V to F1.10
0.00V
☆
F1.09
AI1 lower limit setting
-100.0% to 100.0%
0.0%
☆
F1.10
AI1 upper limit
F1.08 to 10.00V
10.00V
☆
F1.11
AI1 upper limit setting
-100.0% to 100.0%
100.0%
☆
F1.12
Filter time of AI1 input
0.00s to 10.00s
0.10s
☆
The above function code defines the relationship between analog input voltage and the analog input, when the analog
input voltage exceeds the maximum input or minimum input, the maximum input or the minimum input will be used for
calculation.
When the analog input is the current input, 0mA to 20mA current corresponds to 0V to 10V voltage.
In the different applications, the 100.0% of analog setting vary from the meaning of its corresponding nominal value, please
refer to the description of each application for details.
对应频率
100%
10V
AI
20mA
0
-100%
Relationship diagram between analog reference and set amount
AI1 Input filter time: Adjust analog input sensitivity. if this value is increased appropriately, the anti-interference of analog
will be enhanced, but the analog input sensitivity will be weakened.
K1 K2
Running
command
OFF
ON
OFF
OFF
OFF ON
ON ON
Stop
Forward run
Reverse run
Stop
K1
K2
FWD
REV
COM
In
v
er
te
r
K1 K2
Running
command
OFF
ON
OFF
OFF
OFF ON
ON ON
Stop
Forward run
Reverse run
Stop
K1
K2
FWD
REV
COM
In
v
er
te
r
Inv
er
te
r
Corresponding
frequency