1. Overview

Thank you for purchasing the GL10-PS2 power module, which is independently developed and produced by 

Inovance. Please read this manual carefully before using this product.
The GL10-PS2 module can work with modules including AM600CPU, AM600-RTU-ECT, AM600-RTU-COP and AM600-

RTU-DP. It can provide power of 24 VDC and 2 A.

This manual mainly describes the product's specifications, characteristics and how-to-use. Read this manual 

carefully before use for your safety. See the Medium-Sized PLC Programming Manual to understand the use of 

the user program development environment and design method of the user program of the product. You can 

download the latest materials from 

www.inovance.com

.

2. Safety Precautions

The safety precautions are divided into two classes: "WARNING" and "NOTICE". Please pay attention to the safety 

precautions before using the product.

WARNING

Wrong operations can cause death or serious injury;

CAUTION

Wrong operations can cause moderate or minor injury and equipment damage.

Accidents described in the "NOTICE" class may cause serious subsequent in some cases. Follow the safety 

instructions. Otherwise, death or heavy injury, damage to the product, machines and system can be caused. 

Please keep this manual properly for reference when needed and deliver it to end users.

Control System Design

WARNING

 

The safety circuit must be designed to ensure that the control system can continue working safely when the 

external power is off or the PLC is faulty;

 

In case of long-time over-current on the output circuit caused by a current exceeding the rated value or 

short-circuit of the load equipment, the module may smoke or get on fire. Therefore, external safety devices 

should be used, such as fuses or breakers. 

CAUTION

 

The emergent braking circuit, protection circuit, interlock circuit for forward/reversal rotation, and top and 

bottom position interlock switches that can prevent damage to equipment should be configured in the 

external circuit of the PLC;

 

◆ Please configure the external protection circuit and safety mechanisms for output signals related to material 

accidents to ensure that the equipment can work safely;

 

◆ When the CPU of the PLC detects any system exceptions, all outputs may be closed; when the circuit of the 

controller is faulty, its outputs may become out of control. Therefore, an appropriate external control circuit 

should be designed to ensure that the equipment can work properly;

 

◆ When the PLC is used in an outdoor electric environment or level-II over-voltage environment, the power 

system should be equipped with anti-lighting devices to ensure that the over-voltage caused by the lightning 

does not affect ports of the PLC, including the power input, or signal inputs and control outputs of the PLC..

1

Installation

WARNING

 

Only professional service engineers who have received related electrical training and knowledge can install 

the product;

 

Before disassembling the module, the external power supply must be disconnected from the system. If the 

power supply is connected, it may lead to an electric shock or fault and false tripping;

 

Do not use a PLC under following conditions: Environment with dust, oil smoke, conductive dust, erosive 

gas and flammable gases; environment exposure to high temperature, condensation, rain and wind; 

environment under vibration and shock. Electric shock, fire and misoperations can cause damage to the 

product;

 

◆ The PLC is an open-type device. To protect operators without adequate knowledge about electric devices 

from an electric shock, the PLC must be mounted in a control cabinet with a door lock. The casing of the 

cabinet must meet IP20 or above safety requirements. Only operators who have received related training 

about electric devices with adequate electric knowledge can open the cabinet.

CAUTION

 

◆ While handling bolt holes and connecting wires, do not let cuttings and wire crumbs fall into the PLC through 

ventilation holes. This may cause fire, faults and false tripping;

 

After a new PLC is installed, the ventilation surface of the PLC must not be covered. Otherwise, the ventilation 

efficiency will be lowered, causing fire, faults and false tripping;

 

◆ When modules are being mounted, the modules must be firmly connected to their connectors and fixed on 

the hooks. If a module is not mounted correctly, it may cause false tripping, faults and the module to fall. 

Wiring

WARNING

 

Only professional service engineers who have received related electrical training and knowledge can wire the 

product;

 

All external power supplies must be disconnected from the system during the wiring process. If a power 

supply is connected, it may lead to an electric shock or fault and false tripping;

 

The PLC can be powered on after installation and wiring. The terminal cover must be mounted before starting 

operations. If not, it may cause an electric shock;

 

Cable terminals must be insulated to ensure that the insulation distance between cables does not decrease 

after the cables are connected.Otherwise, it may cause an electric shock or equipment damage;

 

◆ The input power distribution circuit should be equipped with suitable protective devices, generally including 

disconnectors with fusing and detection functions or external fuses. Factors including the rated current, 

overload capability and the short-circuit capability of the its preceding power distribution when choosing 

protective devices. 

CAUTION

 

◆ Prevent dropping metal filings and wire ends drop into ventilation holes of the PLC at wiring. Failure to comply 

may result in fire, fault and malfunction.

 

◆ The external wiring specification and installation method must comply with local regulations. For details, see 

the wiring section in this guide.

 

◆ To ensure safety of equipment and operator, use cables with sufficient diameter and connect the cables to 

ground reliably.

 

◆ When connecting the cable, ensure that you have recognized the connector type correctly. Failure to comply 

may result in module and external equipment fault.

 

◆ Tighten bolts on the terminal block in the specified torque range. If the terminal is not tight, short-circuit, fire 

or malfunction may be caused. If the terminal is too tight, fall-off, short-circuit, fire or malfunction may be 

caused.

 

◆ If the connector is used to connect with external equipment, perform correct crimping or welding with the tool 

specified by manufacturer. If connection is in poor contact, short-circuit, fire or malfunction may be caused.

 

A label on the top of the module is to prevent foreign matters entering the module. Do not remove the label 

during wiring. Remember to remove it before system operation, facilitating ventilation.

 

Do not bundle control wires, communication wires and power cables together. They must be run with distance 

of more than 100 mm. Otherwise, noise may result in malfunction.

 

◆ Select shielded cables for high-frequency signal input/output in applications with serious interference so as to 

enhance system anti-interference ability.

Operation and Maintenance

WARNING

 

◆ and maintain the product;

 

◆ Touching terminals when the PLC is power-on may cause an electric shock or false tripping;

 

All external power supplies must be disconnected from the system before cleaning modules or re-fastening 

bolts on the terminal block and mounting bolts on connectors. Otherwise, it may cause an electric shock;

 

All external power supplies must be disconnected from the system before modules can be disassembled or 

communication cables can be connected or disconnected. Otherwise, it may cause an electric shock or false 

tripping.

Retirement

CAUTION

 

◆ The product should be disposed of as industrial waste;

 

The retirement of batteries should comply with the local regulations.

3. Product Information

 

Model and Nameplate

(-14

.BSL

%FTDSJQUJPO

-

-PDBMNPEVMF

.BSL

4FSJFT

TFSJFT

.BSL

%FTDSJQUJPO

(

.BSL

.PEVMF

5ZQF

1PXFSTVQQMZ

14

.BSL

0VUQVU$VSSFOU

"

(FOFSBM.PEVMF

"

"

.PEFM
*OQVU
0VUQVU

4FSJBM/P

/BNFQMBUF

.0%&-盘(-14

108&3*/165盘7"$")[

065165盘7%$"

9999999999999999

7FSTJPO/P

7&399999

9999999999999999

Figure 1 

Model and nameplate

Model

Type

Description

Applicable for 

GL10-PS2

Power module

220 V input; 24 V/2 A output

AM600

 

External Ports

   

圧圦圃坒坘块坓坘块

L
N

100-240 VAC

INPUT

OUTPUT

24VDC-2A

POWER

圤圦圃坌坑坓坘块

圳在

圩在

Figure 2 

Ports of the power module

The power module has two terminals. One is the input port, the other one is the output port. The AC input port 

should meet the following requirements:

Port

Definitions of functions

AC input port

100-240 VAC input
Protective ground (connecting to the AC input power ground cable)

Functional ground (connecting to the PLC casing)

The DC output port should meet the following requirements:

Network

Type

Function

Remarks

24 V

Output

24 VDC output

-

5 V

Output

5 VDC output

For modules without 5 V terminal, the internal terminal is empty.

GND

Output

DC output ground -

GND

Output

DC output ground -

 

General Specifications

Item

Specifications

Input power

100~240 VAC(-15%~+10%)

Input frequency

50/60 Hz(-5%~+5%)

Output voltage

24 VDC±5%

Rated Output Current

2 A

Efficiency

Above 70%

Over-current protection

Yes

Fuse

Built-in

2

3

User Guide
GL10-PS2 Power Module