6. Description of Parameters
- 170 -
6
6.8.4 Motor 2 Parameters
The drive supports driving two motors at different time. For the two motors, you can:
Ɣ
Set motor nameplate parameters respectively
Ɣ
Perform motor auto-tuning respectively
Ɣ
Select V/F control or vector control respectively
Ɣ
Set encoder-related parameters respectively
Ɣ
Set parameters related to V/F control or vector control independently
Motor 2 parameters are defined the same as motor 1 parameters. For details on motor 1
parameters, see descriptions of these parameters in
6.4 Motor Auto-tuning
.
You can select the desired motor parameter group in F0-24 or via a DI terminal
1. Select the desired motor parameter group in F0-24.
Function Code
Parameter Name
Setting Range
Default
F0-24
Motor parameter group
selection
0: Motor parameter group 1
1: Motor parameter group 2
0
2. Select the desired motor parameter group via a DI terminal.
Set any DI (F4-00 to F4-09) for function 41 "Motor selection". If the DI is inactive, motor
parameter group 1 is selected. If the DI is active, motor parameter group 2 is selected.
Function Code
Parameter Name
Setting
Description
Any of F4-00 to F4-09
DIx function selection
41
Motor selection
Note
Ɣ
If any of F4-00 to F4-09 is set for function 41 “Motor selection”, DI terminal
overrides F0-24. If none of F4-00 to F4-09 is set for function 41 “Motor
selection”, motor selection is determined by F0-24.
Ɣ
Switchover of two groups of motor parameters is prohibited during drive
running. Otherwise, the drive detects Err41.
Function
Code
Parameter Name
Setting Range
Default
A2-00
Motor type selection
0 to 1
0
A2-01
Rated motor power
0.1 to 1000.0 kW
Model
dependent
A2-02
Rated motor voltage
1 to 2000 V
Model
dependent
A2-03
Rated motor current
WR$&GULYHSRZHUN:
0.1 to 6553.5 (AC drive power > 55 kW)
Model
dependent
A2-04
Rated motor frequency 0.01 to max. frequency
Model
dependent
A2-05
Rated motor speed
1 to 65535
Model
dependent
A2-06
Stator resistance
WR$&GULYHSRZHUN:
0.0001 to 6.5535 (AC drive power > 55 kW)
Auto-tuning
parameter
A2-07
Rotor resistance
WR$&GULYHSRZHUN:
0.0001 to 6.5535 (AC drive power > 55 kW)
Auto-tuning
parameter
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......