6. Description of Parameters
- 185 -
6
Function Code
Parameter Name
Setting Range
Default
F5-17
FMR output delay
0.0s to 3600.0s
0.0s
F5-18
Relay 1 output delay
0.0s to 3600.0s
0.0s
F5-19
Relay 2 output delay
0.0s to 3600.0s
0.0s
F5-20
DO1 output delay
0.0s to 3600.0s
0.0s
F5-21
DO2 output delay
0.0s to 3600.0s
0.0s
These parameters set output delay of terminals FMR, relay1, relay2, DO1 and DO2 from state
change.
Function Code
Parameter Name
Setting Range
Default
F5-22
DO active mode
selection 1
Relay1 active mode:
0: Positive logic active
1: Negative logic active
FMR active mode:
0: Positive logic active
1: Negative logic active
Relay2 active mode:
0: Positive logic active
1: Negative logic active
DO2 active mode:
0: Positive logic active
1: Negative logic active
DO1 active mode:
0: Positive logic active
1: Negative logic active
00000
This function parameter sets active mode of terminals FMR, relay1, relay2, DO1 and DO2.
Ɣ
0: Positive logic active
Digital output terminal becomes active when being connected with COM, and inactive when
being disconnected from COM.
Ɣ
1: Negative logic active
Digital output terminal becomes active when being disconnected from COM, and inactive
when being connected with COM.
Summary of Contents for MD290 Series
Page 1: ......
Page 79: ...3 Electrical Installation 78 3 ...
Page 80: ...4 Operating Panel Keypad Display 4 1 Introduction 80 4 2 Inbuilt LED Operating Panel 80 ...
Page 92: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 92 5 2 Setup Flowchart 93 ...
Page 227: ...7 Interfaces and Communication 226 7 ...
Page 285: ...10 Troubleshooting 284 11 ...
Page 349: ......
Page 350: ......