Function Parameter Table MD320/MD320N User Manual
Function
code
Name
LED display
Set range
Minim-
um unit
Factory
default
value
Modi
¿
cation
description
F9-20
Input terminal
upon fault
Input terminal
upon fault
ˉ
ˉ
ˉ
ƽ
F9-21
Output
terminal upon
fault
Output
terminal upon
fault
ˉ
ˉ
ˉ
ƽ
Group FA PID Function
FA-00
PID setup
source
PID setup
source
0: FA-01
1: AI1
2: AI2
3: AI3
38/6(VHWXS',
&RPPXQLFDWLRQVHWXS
1
0
ƿ
FA-01
PID keyboard
setup
PID setup
0.0%
̚
100.0%
0.1
ƿ
FA-02
PID feedback
source
PID feedback
source
0: AI1
1: AI2
2: AI3
3: AI1-AI2
38/6(VHWXS',
&RPPXQLFDWLRQVHWXS
1
0
ƿ
FA-03
PID action
direction
PID action
direction
0: Positive action
1: Reverse action
1
0
ƿ
FA-04
PID setup
feedback
range
PID range
0
̚
1
1000
ƿ
)$
Proportional
gain P
Proportional
gain P
0
ˊ
0
̚
100
ˊ
0
0
ˊ
1
20
ˊ
0
ƿ
FA-06
Integration
time l
Integration
time l
0.01s
̚
10.00s
0.01s
2.00s
ƿ
FA-07
Differential
time D
Differential
time D
0.000s
̚
10.000s
0.01s
0.00s
ƿ
FA-08
Cutoff
frequency of
PID reverse
rotation
Cutoff
frequency
of reverse
rotation
aPD[LPXPIUHTXHQF\
0.01Hz
2
ˊ
00Hz
ƿ
FA-09
Deviation limit
Deviation limit
0.0%
̚
100.0%
0.1%
0.0%
ƿ
FA-10
Differential
amplitude
Differential
amplitude
0%
̚
100%
1%
ƿ
Group FB Swing Frequency, Fixed Length and Count
FB-00
Swing setup
mode
Swing setup
mode
0: Relative to the central
frequency
1: Relative to maximum frequency
0
ˊ
01
0
ˊ
00
ƿ
efesotomasyon.com
Summary of Contents for MD320 Series
Page 9: ...z G Gw efesotomasyon com...
Page 16: ...Safety and Precautions MD320 MD320N User Manual efesotomasyon com...
Page 17: ...w Gp efesotomasyon com...
Page 40: ...Product Information MD320 MD320N User Manual efesotomasyon com...
Page 41: ...t G Gl Gp efesotomasyon com...
Page 59: ...v G Gk efesotomasyon com...
Page 67: ...m Gw G efesotomasyon com...
Page 93: ...w Gk efesotomasyon com...
Page 154: ...Parameter Description MD320 MD320N User Manual efesotomasyon com...
Page 155: ...ltjGn efesotomasyon com...
Page 159: ...m Gk G Gz efesotomasyon com...
Page 175: ...h efesotomasyon com...