Appendix A Parameter Table
- 107 -
Para.
No.
Para. Name
Setting Range
Default
Property
F4-33
AI curve selection
Ones: AI1 curve selection
1: Curve 1 (2 points, see F4-13 to F4-
16)
2: Curve 2 (2 points, see F4-18 to F4-
21)
3: Curve 3 (2 points, see F4-23 to F4-
26)
4: Curve 4 (4 points, see A6-00 to A6-
07)
5: Curve 5 (4 points, see A6-08 to A6-
15)
Tens: AI2 curve selection (same as
the ones position)
Hundreds: Reserved
321
☆
F4-34
Setting for AI less than
minimum input
Ones: Setting selection when AI1 less
than min. input
0: Corresponding percentage of min.
input
1: 0.0%
Tens: Setting selection when AI2 less
than min. input (same as the ones
position)
Hundreds: Reserved
0
☆
F4-35
DI1 delay
0.0s to 3600.0s
0.0s
☆
F4-36
DI2 delay
0.0s to 3600.0s
0.0s
☆
F4-37
Reserved
-
-
-
F4-38
DI active mode
selection 1
0: High level active
1: Low level active
Ones: DI1
Tens: DI2
Hundreds: Reserved
Thousands: DIO1
Ten thousands: DIO2
0
★
F4-40 AI2 input type
0: Voltage input
1: Current input (input impedance
500 Ω)
0
★
F4-41
DIO terminal type
Ones: DIO1 type
0: DI/PulseIn
1: DO
Tens: DIO2 type
0: DI
1: DO/FMP
00
★
Group F5: Output Terminals
F5-00
DIO2 terminal output
mode
0: Pulse output (FMP)
1: Digital output (FMR)
0
☆