Appendix A Parameter Table
- 128 -
Para.
No.
Para. Name
Setting Range
Default
Property
Fd-14
Number of CAN frames
received in a period
-
-
●
Fd-15 Maximum value of node
receiving error counter
-
-
●
Fd-16 Maximum value of node
sending error counter
-
-
●
Fd-17
CANopen/CANlink bus
disconnection times in
a period
-
-
●
Fd-18
Power supply unit No.
1 to 99
1
★
Fd-20 DP communication
address
0: broadcast address, 1 to 125
0
★
Fd-21 DP communication
dropping coefficient
0 to 65535
350
☆
Fd-22
DP-CANopen
conversion network
bridge
0: Reporting communication error
reported if the number of slaves in
PLC is inconsistent with the actual
1: Not reporting communication
error reported if the number of
slaves in PLC is inconsistent with the
actual
0
☆
Fd-23 Number of online slates 0 to 65535
0
●
Fd-24
DP-CANopen
conversion power-on
delay
0s to 65535s
8s
☆
Fd-25
Status of stations 1
to 15 at DP-CANopen
conversion
0: Offline
1: Online
Bit1: Station 1
Bit2: Station 2
…
Bit15: Station 15
0
●
Fd-26
Status of stations 16
to 30 at DP-CANopen
conversion
0: Offline
1: Online
Bit0: Station 16
Bit1: Station 17
…
Bit14: Station 30
0
●
Fd-33 CANopen
communication period -
-
●
Fd-94 Modbus software
version
0.00 to 655.35
0.00
●
Fd-95
CANlink software
version
0.00 to 655.35
0.00
●