5 Quick Commissioning
- 68 -
Operation
Para.
No.
Parameter Name
Default
Commission
Setting range same as FMR
F5-06 FMP function selection
0
If an analog
output is used
Setting range same as FMR
Set AO function
F5-07 AO function selection
0
0: Running frequency
1: Set frequency
2: Output current
3: Output torque (100.0% corresponds to 2 times of rated motor
torque)
4: Output power
5: Output voltage (100.0% corresponds to 1.2 times of rated motor
voltage)
6: Pulse input (100.0% corresponds to 50.0 kHz)
7: AI1
8: AI2
9: Reserved
10: Length
11: Count value
12: Communication setting
13: Motor speed
14: Output current (100.0% corresponds to 1000.0 A)
15: Output voltage (100.0% corresponds to 1000.0 V)
16: Output torque (directional, 100.0% corresponds to 2 times of
rated motor torque)
Set accel/decel
time
F0-17
Acceleration time 1
20.0s
0.00s to 65000s
F0-18 Deceleration time 1
20.0s
If smooth
acceleration/
deceleration is
requested
0.00s to 65000s
Set S-curve
F6-07
Acceleration/Deceleration mode
0
0: Linear acceleration/deceleration
1: S-curve acceleration/deceleration
F6-08 Time proportion of S-curve start
segment
30.0%
0.0% to (100.0% - F6-09)
F6-09 Time proportion of S-curve end
segment
30.0%
0.0% to (100.0% - F6-08)
If it is V/F control