Appendix A Parameter Table
- 94 -
Para.
No.
Para. Name
Setting Range
Default
Property
F0-07
Final frequency
reference setting
selection
Ones: Final frequency reference
selection
0: Main frequency reference
1: Main and auxiliary calculation
result (determined by the tens
position)
2: Switchover between main
frequency reference and auxiliary
frequency reference
3: Switchover between main
frequency reference and main and
auxiliary calculation result
4: Switchover between auxiliary
frequency reference and main and
auxiliary calculation result
Tens: Main and auxiliary calculation
relationship
0: Main + Auxiliary
1: Main - Auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
4: Main x Auxiliary
0
☆
F0-08 Preset frequency
0.00 Hz to maximum frequency (F0-
10)
50.00 Hz
☆
F0-09 Running direction
0: Run in the default direction
1: Run in the direction reverse to the
default direction
0
☆
F0-10 Maximum frequency
50.00 to 600.00 Hz
50.00 Hz
★
F0-11
Setting channel of
frequency reference
upper limit
0: Set by F0-12
1: AI1
2: AI2
4: Pulse reference (DIO1)
5: Communication setting
6: Multi-reference
0
★
F0-12 Frequency reference
upper limit
Frequency reference lower limit (F0-
14) to maximum frequency (F0-10)
50.00 Hz
☆
F0-13
Frequency reference
upper limit offset
0.00 Hz to maximum frequency (F0-
10)
0.00 Hz
☆
F0-14 Frequency reference
lower limit
0.00 Hz to frequency reference upper
limit (F0-12)
0.00 Hz
☆
F0-15 Carrier frequency
0.8–12.0 kHz
Model
dependent
☆
F0-16
Carrier frequency
adjusted with
temperature
0: No
1: Yes
1
☆