SECTION 7
-
The HIU Controller first power up and set up
Page 23
SECTION 12
-
Technical Specification
DH maximum pressure
16 bar
DH maximum temperature
85° C
DH maximum pressure differential.
4 bar
HTG maximum working pressure
2.5 bar
HTG safety valve setting
3 bar
HTG maximum temperature
75° C
HTG
-
radiators temperature adjustment
30°C to 75°C
UFH
-
underfloor heating temperature adjustment
20°C to 50°C
HTG maximum output (85C at 1330 ltrs/hr)
29kW
HTG minimum output
1kW
Heating pump nominal head capacity
70 kPa
DHW temperature adjustment
45°C to 65°C
DHW maximum output at 1300 ltrs/hr with 80C DH and
∆
T 40°C
Max 80kW
DHW minimum output at 400 ltrs/hr with 55C DH and
∆
T 40°C
Min 15 kW
DHW maximum flow at 1300 ltrs/hr with 80C DH and
∆
T 40°
28.5 Ltrs/min
DHW maximum flow at 1300 ltrs/hr with 55C DH and
∆
T 40°
5.8 Ltrs/min
DHW side maximum pressure
10 bar
Minimum suggested inlet pressure for cold water supply
1.5 bar
Electrical supply
1 ph 50Hz 230v
Average flow measured by BESA for 8 hour period of keep warm
4.5 Ltrs / hr
HIU installation weight, no cover.
25.4 kg
HIU weight
-
Gross, inc packaging
32.5 kg
Indirect interface for
instantaneous DHW and space heating
Hiper II
Part code without heat meter
HIPER2TP1580
Part code with fitted Zenner heat meter
HIPER2TP1580ZE
Control method
Electronic PID controller with fast acting stepper / PICV.
Plate Heat Exchangers
Stainless steel—insulated Wras approved
Expansion Vessel
8 Ltr
Casing
Fully insulated steel backplate and cover
Dimensions
585mm H x 465mm W x 265mm D
Heat meter options
Zenner C5 MID compliant 1.5 qp M
3
/hr 110mm
Filters 1) Primary 2) Htg 3) CW inlet
800 micron
Wras approved shock arrester
Inta
-
mechanical spring loaded
Internal pipework
copper
General
Technical