Hiper HIU Indirect models
Indirect HIPER HIU Xi45
Indirect HIPER HIU Xi60
Indirect HIPER HIU Xi75
Technical Parameters
Xi45
Xi60
Xi70
PRIMARY (heat supply from communal heat source)
MAXIMUM PRESSURE
16 bar
16 bar
16 bar
PRIMARY (heat supply from communal heat source)
MAXIMUM TEMPERATURE
90° C
90° C
90° C
PRIMARY (heat supply from communal heat source)
MAXIMUM pressure differential.
4 bar
4 bar
4 bar
SECONDARY (central heating ) MAXIMUM PRESSURE
3 bar
3 bar
3 bar
SECONDARY (central heating ) MAXIMUM TEMPERATURE
85° C
85° C
85° C
SECONDARY (central heating) TEMPERATURE ADJUSTMENT
20°C to 85°C
20°C to 85°C
20°C to 85°C
SECONDARY (central heating ) HEATING OUTPUT
10 kW
Xi6010 = 10 kW
Xi6015 = 15kW
15 kW
DOMESTIC HOT WATER (including cold water supply main)
MAXIMUM PRESSURE
10 bar
10 bar
10 bar
DOMESTIC HOT WATER
MAXIMUM TEMPERATURE LIMITED by TMV
Temperature setting update 19.06.17
57° C
57° C
57° C
DOMESTIC HOT WATER
TEMPERATURE ADJUSTMENT
30°C to 65°C
30°C to 65°C
30°C to 65°C
DOMESTIC HOT WATER OUTPUT
45kW
60kW
70kW
COLD WATER MAINS SUPPLY
RECOMMENDED PRESSURE AT INLET TO THE HIU
2 Bar
2 Bar
2 Bar
SECTION 11
-
Technical specifications
Controller factory settings
Xi45
Xi60
Xi75
Domestic Hot Water Services
55°C
55°C
55°C
For Heating to radiators
60°C
60°C
60°C