© Intatec Ltd 2021

10

Commissioning

 

   2   Commissioning the temperatures must be carried out using a suitably calibrated 

        thermometer preferably a digital thermometer. 

   3   In the absence of other temperatures being specified, we recommend the outlet temperature 

        quoted in Table 1 are used. 

Table 1

   4   Each basin tap must be commissioned taking into consideration any fluctuations, which 

        may occur within the system due to simultaneous demands. It is advisable that any outlets 
        which are connected to the same supply as the basin tap are opened during the setting of 
        the mixed water temperature. During commissioning it is advisable to ensure that the water 
        temperatures are established before any attempt to commission. 

   5   Once the supply temperatures are stable and the normal operating conditions are 

        established, the tap can be commissioned. The temperature setting can be adjusted 
        following the procedure described earlier in the Temperature Setting section.  

        We suggest that the following sequence is followed when commissioning the valve: 

        5.1 Set the mixed water temperature to the required temperature. 

        5.2 Measure and record the temperature of the hot and cold water supplies at the 
        

connection to the tap. 

        5.3  Measure and record the temperature of the water discharging from the basin tap. 

        5.4  Isolate the cold water supply to the tap and monitor the mixed water temperature. 

        5.5 Measure and record the maximum mixed water temperature and the final temperature. 
        

The final temperature found during the test should not exceed the value quoted in    

        

Table 2. 

        5.6  Record all the equipment used during the commissioning.

Table 2

Application

Maximum Set Mixed Water Temp.

Wash Hand Basin

43˚C

6  Ensure that the application, in which the basin tap will be used, is appropriate for the 

   approved designation. The above information must be recorded and updated on every 
   occasion when any work is carried out on the basin tap.

Application

Recommended Set Mixed Water Temp.

Wash Hand Basin

41˚C

Summary of Contents for IT1007CP

Page 1: ...as possible We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or otherwise Intat...

Page 2: ...hat a water conditioner such as the ActivFlo be fitted to reduce the risk of calcium deposits forming Safety The Intatherm safe touch basin mixer tap contains an integral thermostatic cartridge to pre...

Page 3: ...Retaining screw 4 1 Handle 5 1 Thermostatic cartridge 6 1 Nozzle 7 1 Sealing ring 8 1 Horse shoe plate 9 1 Threaded rod 10 1 Retaining nut 11 2 350mm copper tail integral with body 12 2 Connector wit...

Page 4: ...g combination boilers Max Inlet Pressure Static 10 bar Max Unbalanced Pressure Ratio 15 1 Max Inlet Pressure Dynamic 5 bar with flow regulator Max Inlet Temperature 85 C Max Unbalanced Pressure Ratio...

Page 5: ...left hand side of the mixer when viewed from the front Ensure that the O ring seal 7 is located in the base of the tap prior to fitting the mixer to the basin Once in place using the horse shoe retai...

Page 6: ...3 handle 4 and the temperature stop rings A and B Temporarily refit the handle 4 and move to the position for the hottest water and allow the outlet temperature to stabilise Using a digital thermomete...

Page 7: ...h a new cartridge Re assemble in the reverse order and turn on the water supplies Aftercare The nozzle should be cleaned periodically to remove any build up of debris or deposits which may affect the...

Page 8: ...o meet the requirements of BS 7942 2011 and NHS D08 Technical Specification Fail Safe Function The Intatherm thermostatic basin tap is designed to stop the mixed water flow in the event of either the...

Page 9: ...nstallation IMPORTANT The following instructions must be read prior to the installation of any Inta basin tap The installer should also be aware of their responsibility and duty of care to ensure that...

Page 10: ...ontamination of supplies 9 The taps are supplied with integral filters and check valves in the compression connections on the hot and cold supplies Independent isolation valves must be fitted in conju...

Page 11: ...the procedure described earlier in the Temperature Setting section We suggest that the following sequence is followed when commissioning the valve 5 1 Set the mixed water temperature to the required t...

Page 12: ...e the final temperature should not exceed the values quoted in table 2 3 6 Record the equipment used during these tests 4 If the mixed water temperature is greater than the values quoted in table 2 or...

Page 13: ...erved after the first 2 or 3 in service tests is that the intervals for future tests should be set to those which previous tests have shown can be achieved with no more than a small change in mixed wa...

Page 14: ...Intatec Ltd 2022 13 Notes...

Page 15: ...Intatec Ltd 2022 14 Notes...

Page 16: ...on Staffordshire ST18 0PF Tel 01889 272 180 Fax 01889 272 181 email sales intatec co uk web www intatec co uk E O E 12 05 22 To active your product warranty please visit www intatec co uk and click on...

Reviews: