© Intatec Ltd 2022
5
Calibration
The Intatherm safe touch mixer tap has a factory set outlet temperature of 43˚C via the security
setting. This is based on a balanced supply pressure and a stable hot water inlet temperature of
65˚C.
However, the calibration point
MUST
be checked and re-set as necessary to suit site
conditions.
Care must be taken when re-calibrating the tap as
INCORRECT CALIBRATION CAN CAUSE
INJURY.
• Remove the indice (2), retaining screw (3), handle (4) and the temperature stop rings (A and
B).
• Temporarily refit the handle (4) and move to the position for the hottest water and allow the
outlet temperature to stabilise.
• Using a digital thermometer it is possible to increase or reduce the mixed water outlet
temperature until 43˚C is re-established, by slowly rotating the handle.
• Remove the control knob (4) and refit the temperature stop rings (A and B) onto the splined
section of the cartridge as shown.
• Refit the handle in the reverse order.
PLEASE NOTE THAT ONCE CALIBRATED, THE SECURITY SETTING WILL ONLY BE 43
˚
C
UNDER THE SUPPLY CONDITIONS USED FOR CALIBRATION.
A - Hot
B - Cold
A
B
Figure 1
Figure 2