© Intatec Ltd 2021
7
Outlet Temperature Adjustment Range
30˚C to 50˚C
Temperature Stability
±2˚C
Maximum Hot Inlet Temperature
85˚C
DO8 Working Pressure Range
1.0 to 5.0 bar : High Pressure
Min Temp Differential (Mix to Hot) for Fail-Safe
10˚C
Max. Pressure Inlet Differential
5 : 1
Intatherm Thermostatic Basin Tap
Introduction
The Intatherm safe touch thermostatic basin tap has been specifically designed and manufactured
to meet the requirements of BS 7942:2011 and NHS D08.
Technical Specification
Fail Safe Function
The Intatherm thermostatic basin tap is designed to stop the mixed water flow in the event of
either the hot or cold water supply failing when installed in accordance with these instructions.
To ensure thermal shut off the minimum temperature differential between the hot water inlet to the
tap and the mixed water outlet
MUST be at least 10˚C.
Operating Pressure Range
High Pressure
Maximum Static Pressure
10 bar
Flow Pressure, Hot and Cold
1 to 5 bar
Hot Supply Temperature
55˚C to 65˚C
Cold Supply Temperature
5˚C to 20˚C
Summary of Contents for IT1007CP
Page 14: ...Intatec Ltd 2022 13 Notes...
Page 15: ...Intatec Ltd 2022 14 Notes...