17

Commissioning

   5.  If the mixed water temperature exceeds the recommended temperature of 41˚C by 2˚C or 
        does not reach 41˚C the shower valve can be adjusted as follows:

        5.1 With stable supply conditions remove the temperature control knob.

        5.2 Rotate the temperature control knob by one spline clockwise to increase the temperature
        and one spline anticlockwise to reduce it.

        5.3 Measure the water discharging from the shower.

        5.4 Repeat 5.2 until the desired temperature is stabilised and record the temperature. 

        5.5 Repeat 4.4 and 4.5

        5.6 Secure the temperature control knob with the retaining screw and re-fit the cover.

   6.  The above information must be recorded and updated on every occasion when any work is 
        carried out on the valve.

In Service Testing

    It is a requirement that all TMV2 approved valves shall be verified against the original set 
    temperature results once a year. When commissioning / testing is due the following 
    performance checks shall be carried out.

   1. Measure the mixed water temperature at the outlet.

   2. Carry out the cold water supply isolation test by isolating the cold water supply, wait for five

     seconds if water is still flowing check that the temperature is below 43

˚

C.

   3. If there is no significant change to the set outlet temperature (±2˚C or less from the original 

     settings) and the fail-safe shut off is functioning, then the valve is working correctly and no 
     further service work is required.

Notes:

   •   If there is a residual flow during the commissioning or the annual verification (cold water 

        supply isolation test), then this is acceptable providing the temperature of the water seeping 
        from the valve  is no more than 2˚C above the designated maximum mixed water outlet 
        temperature setting of the valve.

   •   Temperature readings should be taken at the normal flow rate after allowing for the system 

        to stabilise.

   •   The sensing part of the thermometer probe must be fully submerged in the water to be 

        tested.

   •   Any thermostatic shower that has been adjusted or serviced must be re-commissioned and 

        re-tested in accordance with the manufacturers’ instructions

Summary of Contents for Nulo CB10031CP

Page 1: ...tion as accurate as possible We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or...

Page 2: ...pplied at a safe temperature to suit the users The shower is pre set using ideal conditions to 38 C at the stop with a manual push button override to 46 C can be re set to suit site conditions or user...

Page 3: ...et Temperature 85 C Max Inlet Pressure Dynamic 5 bar Pre Set Factory Temp Setting 38 C Min Operating Pressure Dynamic 0 2 bar Temperature Stability 2 C Max Unbalanced Pressure Ratio 5 1 Min Temp Diffe...

Page 4: ...her than the hot supply we recommend that a separate pressure reducing valve is fitted to the cold supply as close as possible to the shower valve and with no draw off points between it and the shower...

Page 5: ...lt the pump manufacturer s installation requirements Gravity System The drawing shows a typical installation of a shower valve on a gravity supplied system Please note the minimum head pressure requir...

Page 6: ...ter or plaster board should all be considered when routing the hot and cold supply pipes The valve requires the supply pipes and wall brackets to have 150mm centres and sufficient copper pipe must pro...

Page 7: ...inside edge of the concealing plates position over the compression faces and press firmly to the wall Installing the Shower Valve The connector 10 check valve 9 filter 8 union nut 11 and sealing wash...

Page 8: ...ow control 1 and allow the outlet temperature to stabilise from the bottom outlet Temporarily refit the control knob bush 8 and control knob 6 and using a digital thermometer it is possible to increas...

Page 9: ...have a high quality finish and should be treated with care An occasional wipe with a mild washing up liquid on a soft damp cloth followed by a thorough rinsing is all that is required The nozzles in t...

Page 10: ...t at cold the showering temperature is too hot The hot and cold supply connections have been made in reverse Thermostatic cartridge movement limited due to lime scale build up The maximum showering te...

Page 11: ...ble Riser Rail Dimensions 42 5 652 Ctr 684 1 2 3 4 6 7 8 5 Wall Bracket End Cap Details 15 Item Qty Component 1 2 Wall Bracket 2 2 End Cap 3 1 Riser Rail 4 1 Handset Holder 5 2 Retaining Screw Plug 6...

Page 12: ...ail Dimensions 42 5 652 Ctr 684 1 2 3 4 7 8 5 6 Wall Bracket End Cap Details 30 15 Item Qty Component 1 2 Wall Bracket 2 2 End Cap 3 1 Riser Rail 4 1 Handset Holder 5 2 Retaining Screw Plug 6 1 Push B...

Page 13: ...all the way behind the ceramic tile Using the screw provided secure the wall bracket 1 to the wall ensuring the correct orientation for the bracket Assemble the handset holder onto the riser rail as...

Page 14: ...ure the conditions of use are appropriate for the valve Introduction The thermostatic shower valve has been specifically designed and manufactured to meet the requirements of BS EN1111 1999 and TMV2 T...

Page 15: ...99 and also be aware of their responsibility and duty of care to ensure that all aspects of the installation comply with the regulations It has been brought to our attention that flushing water system...

Page 16: ...e s to within the limits as quoted previously 8 Any thermostatic shower valve must be fitted with a back flow prevention device such as check valves to prevent the cross contamination of supplies The...

Page 17: ...eratures are established before any attempt to commission 4 Once the supply temperatures are stable and the normal operating conditions are established the shower valve can be commissioned The followi...

Page 18: ...g performance checks shall be carried out 1 Measure the mixed water temperature at the outlet 2 Carry out the cold water supply isolation test by isolating the cold water supply wait for five seconds...

Page 19: ...Intatec Ltd 2017 18 Notes...

Page 20: ...n Staffordshire ST18 0PF Tel 01889 272 180 Fax 01889 272 181 email sales intatec co uk web www intatec co uk E O E 10 08 17 To activate your product warranty please visit www intatec co uk and click o...

Reviews: