VOLTAGE OUTPUT ADJUSTMENT

The output is factory set to 24 VDC, but can be adjusted from 1.5 to 26

 

VDC. The voltage output can be changed by 

adjusting the P1 turn pot with a flat-head screwdriver.  Rotate the turn pot screw clockwise to increase the voltage output, 
or rotate the turn pot screw counter-clockwise to decrease the voltage output.

OUTPUT CURRENT

The maximum output current (mA) will be dependent on multiple factors, including ambient room temperature, voltage, 
etc. The graph below shows the minimum (bottom line) and maximum (top line) current output.  

PRODUCT SPECIFICATIONS

W.E.E.E. DIRECTIVE

At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not 
dispose of with household waste. Do not burn.

22 VAC to 26 VAC, 50/60Hz; or 30 VDC to 36 VDC
24 VDC
1.5 VDC to 26 VDC
Jumper Selectable
Built-in current limiting thermal protection
Fuse, 3.15A/250 VAC, 5x20 mm, fast acting (Littelfuse 02173.15MXP or equivalent)
32ºF to 158ºF (0ºC to 70ºC)
5% to 95% RH non-condensing
Screw Terminal Blocks | 14 AWG (2.1 mm

2

) to 22 AWG (0.33 mm

2

)

4 lb-in (0.5 Nm) maximum 

Supply Power
Output Voltage – Factory Set
Output Adjustment Range
Half-Wave/Full-Wave Selection
Overload Protection
Ground-Loop Protection
Operating Temperature Range:
Operating Humidity Range:
Connections | Wire Size:
Terminal Block Torque Rating:

AMBIENT AIR TEMPERATURE  |  77ºF (25ºC)

Volts (DC)

5

0.0

0.2

0.4

0.6

0.8

1.0

10

12

15

18

20

24

27

MAX

0.605

MIN

0.325

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | I0000824, Version 3 | USA 200211 | Page 3 of 3