Customer Services (858) 578-7887 & (888) GO IN
TEC
IN
TEC
Controls, 12700 Stowe Dr., Suite 1
0
0, Poway, CA 92064
Fax (858) 578-4633 & (888) FX IN
TEC
www.inteccontrols.com
Specification subject to change without notice.
Printed in USA 131119
Polygard® is a registered trademark of MSR
MGC2-16
PolyGard
®
Multi-Point Controller
User Manual - MGC2-16
Page 22
3.7.6 Customer Password (Code 1)
Change the System Password for level 1
Symbol Description Default
Status
Function
1234
Customer-
password
1234
1234 = Define the Customer Password with 4 characters
Factory preprogrammed system password "9001".
3.7.7 Analog Output
The Controller has two analog outputs (AO) with 4 to 20 mA signal per control module. Each of the analog outputs
can be assigned the signal of one or more sensor points. The assignment occurs in the menu “SP Setup“ for
each SP. The sensor point sends the signal that is defined in the menu “C/A Mode“.
The Controller determines from the signal of all assigned sensor points the minimum, the maximum or the average
value and sends this value to the analog output. The determination of which value is sent is defined in this menu
“Analog Output X“. The analog output can be calibrated for 4 and 20 mA using an ampere meter attached (with
measuring range 25 mA) then respective AO factor can be changed to adjust the analog output 4 and/or 20 mA
During AO calibration no evaluation is made of the sensor point signals. This calibration is factory-set. The factors
should only be changed if you have an accurate amp meter.
Symbol Description Default
Status
Function
Max.
Select
Output mode Max.
Min. = Spends the minimum value of all assigned SP
Max. = Spends the maximum value of all assigned SP
Average = Spends the average value of all assigned SP
4.0
20.0
Calibration
4.0
20.0
4.0 = Calibration factor at 4 mA
20.0 = Calibration factor at 20 mA
3.7.8 Define the Failure Relay
Define the Failure Relay. See also malfunction management (3.1)
Symbol Description Default
Status
Function
19
Failure Relay R19
R19 = Define the failure relay
3.7.9 Power On Time
Sensors need a warm up period until the chemical process of the sensor reaches a stable condition. During this
warm up period the current signal can cause unwanted false alarms. Therefore, the Controller starts reporting
alarms after the Power ON Time delay once power is applied. While this time runs off, the Controller does not
report alarms. The Power On status is displayed.
Symbol Description
Default
Status
Function
30 s
Power On Time 30 s
XX = Define the Power On Time (sec.)