3.1.3 System Errors
Following System Error Message are recorded.
SP XX > 22 mA
Current signal at analog Input XX > 22 mA.
Cause:
Short-circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution:
Check cable to Transmitter, Make Calibration, Change the Transmitter.
SP XX < 3 mA
Current signal to analog Input XX < 3 mA.
Cause:
Wire break at analog Input or Transmitter not calibrated, Transmitter defective.
Solution:
Check cable to Transmitter, Make Calibration, Change the Transmitter.
GC Error:
Internal Communication Error I/O Board to LCD Board.
Cause:
Internal Error.
Solution:
Change the Controller.
Maintenance:
System maintenance is necessary.
Cause:
Maintenance date exceeded.
Solution:
Perform maintenance.
3.2 Stage Status
Display the actual stages exceeded in the sequence they happen. The sensor points are over laid where a stage
has been exceeded. Changes are not possible in this menu.
Symbol Description Function
SP 01
Sensor Point
(SP) Point No.
SX
Stage Status
S1 = Stage 1 ON
S2 = Stage 2 ON
S3 = Stage 3 ON
S4 = Stage 4 ON
S5 = Stage 5 ON
3.3 Relay Status
Display the actual status of each relay. Manual operation of the relays.
Symbol Description Setting
Status
Function
R 01
Relay No. 01
Select Relay No.
OFF
Status Relay
OFF
OFF
ON
Manual OFF
Manual ON
= Relay Off (Not Activated by Stage Setpoint)
= Relay On (Activated by Stage Setpoint)
= Relay manual Off
= Relay manual On
Specifications subject to change without notice. | USA 131119 | Page 9 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
Polygard® is a registered trademark of MSR | LGC/LG2-04
Specifications subject to change without notice. | USA 160104 | Page 9 of 30
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
LGC-LG2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | LGC/LG2-04
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 200211 | Page 9 of 30
LGC-LG2 – UserManual