____________________________________________________________________________________________
(091214_Sp) Integra EPRO 1K-3K
-
12
8. UPS CONFIGURATION
Configuration Menu (00, 01, 02, 03, 04 ó 05)
Screen A
Screen B
* Configuration menu is activated by selecting SELECT push button at front panel during 5 seconds or longer. UPS
must be connected to input AC source but in stand-by mode (powered off).
* “OFF/Enter” button is used as confirmation key (Enter)
* “ON/Mute” is used to select upper option in menu.
* “SELECT” is used to select bottom option in menu.
Configuration Menu:
00: Initial Menu, Quit option
01: Output Voltage
02: CF Frequency Conversion Mode (to able or disable)
03: CF for configuring frequency value in Hz
04: ECO: to Able or Disable ECO Mode
05: ECO: To configure acceptable input voltage range in ECO mode.
06: By Pass: To able or disable by-pass function
07: By Pass: To configure acceptable input voltage range.
08: Programmable Outlets: To able or disable programmable outlets function
09: Programmable: To configure timer value in minutes for programmable outlets.