11. ALARMS ON LCD
ALARM Description
ICON on LCD
Beep Alarm
Low battery
1 / s
Overload: high power consumption detected at
UPS output.
2 / s
Battery disconnected
1 / s
Batteries overcharged
1 / s
Input Cable failure
1 / s
EPO enable
1 / s
FAN failure
1 / s
Over Temperature
1 / s
Battery charger problem
1 / s
Input out of range in bypass mode
1 / s
12. TROUBLESHOOTING TABLE
Problem Description
Probable Root Cause
Suggested Action
* LCD does not show input voltage value
* AC input failure alarm active
(1 beep / 4s) however AC input source is
OK
Input power cord is not
connected
Check input power cord
connection.
Input power cord is connected
into UPS outlet.
Check input power cord
connection.
UPS cannot be powered on even AC
input is OK.
Beep alarm is active (1 beep/s) & LCD
shows:
EPO function is active.
Re-establish emergency power
off switch and set UPS in normal
mode.