(091214_Sp) Integra EPRO 1K-3K

 

 - 

17

 

 
 

UPS  cannot  be  powered  on  even  AC 

input is OK. 

ON  push  button  is  not  been 

selected properly 

Push  ON  button  during  2 

seconds or longer 

1  beep  /  s  alarm  is  active  and  LCD 
shows: 

   

 

 

Input  Line  and  Neutral  are 
swapped 

Rotate UPS plug at wall socket 
to  allow  correct  line-neutral 

connection.  This  suggestion  is 
only valid for Schuko power plug 

type. 

1  beep  /  s  alarm  is  active  and  LCD 
shows: 

  

 

Internal or external batteries are 
not properly connected 

Check battery connection. 

* Code 

27

 

*  Active: 

 

* Continuous beep 

Very high voltage at batteries or 

charger failure 

Batteries  and  charger  must  be 

inspected by qualified personnel 

* Code 

28

 

*  Active: 

 

* Continuous beep 

Very low voltage at batteries or 
charger failure 

Batteries  and  charger  must  be 
inspected by qualified personnel 

* Intermittent: 

 +

 

* 2 beeps per second. 

UPS overloaded  

Disconnect  devices  from  UPS 
outlets until solving overload 

* Intermittent: 

 +

 

* 2 beeps per second. 

* By-Pass activated 

UPS  overloaded.  UPS  has 

changed  to  BYPASS  mode  to 
avoid internal damage.  

Disconnect  devices  from  UPS 

outlets until solving overload 

After repetitive small overloads, 

UPS  has  changed  to  BYPASS 
mode. 

Disconnect  devices  from  UPS 

outlets  until  solving  overload. 
Then power off UPS and re-star 

again. 

* Code 

43

 

* Active:

 

* Continuous beep 

UPS  has  been  automatically 

powered off because overload. 

Disconnect  devices  from  UPS 

outlets  until  solving  overload. 
Then power ON. 

* Active: 

 on LCD. 

* Continuous beep 

UPS  has  been  automatically 

powered  off  because  short 
circuit detected at output. 

Check  short  circuit  problem  in 

devices connected to UPS 

Summary of Contents for EPRO-Rack1K-3K

Page 1: ...________________________________________________________________________________ 091214_Sp Integra EPRO 1K 3K 1 USER MANUAL ONLINE DOUBLE CONVERSION UPS User Manual 220V Europe Schuko Zone 110V Americ...

Page 2: ...onnect this UPS to any of its own power outlets WARNING UPS must be installed following instruction from this manual The manufacturer is not liable for any damage that might rise from misusing this un...

Page 3: ...patibility levels for low frequency conducted disturbances and signaling in public low voltage power supply systems EN 61000 4 6 2006 EN 61000 4 8 2001 EN 61000 4 11 2004 EPRO EPRO RACK 2 0KVA 3 0KVA...

Page 4: ...EUROPE Zone 1 1 Programmable Outlets 2 Standard Outlets 3 AC Input 4 Input Breaker 5 Protected LAN network jacks 6 EPO Emergency Power Off 7 USB port 8 RS 232 port 9 Intelligent Slot for SNMP LAN car...

Page 5: ...ANEL 120V AMERICA 1 Programmable Outlets 2 Standard Outlets 3 AC Input 4 Input Breaker 5 Protected LAN network jacks 6 EPO Emergency Power Off 7 USB port 8 RS 232 port 9 Intelligent Slot for SNMP LAN...

Page 6: ...Auto Test function OFF ENTER a POWER OFF UPS Keep pushed for 2 seconds to power off UPS b ENTER Enter function works under configuration mode only It works as confirmation or selection key for accepti...

Page 7: ...operation If this kind of products will be connected to the UPS operation power rating must be considering to size total power consumption to be connected to UPS 4 EPO Function Emergency Power Off fun...

Page 8: ...208Vac 220Vac 230Vac 240Vac d Output Frequency It can be selected to 50Hz or 60Hz Default configuration allows auto selection to match with frequency of input AC source NOTE When conversion frequency...

Page 9: ...om AC input and UPS only switch to battery mode when input is out of range or in black out status Transition time from ECO mode to Battery mode is not zero Typically is about 4ms that is why ECO Mode...

Page 10: ...ammable Outputs Indicates programmable function is activated Operation Mode Indicates UPS is connected to input AC source under normal range Indicates UPS is in battery mode Indicates UPS is in BYPASS...

Page 11: ...s Battery Low 1 Beep per second Output Overload 2 Beeps per second UPS Failure Continuous Beep By Pass Mode 1 Beep every 10 seconds 7 LCD TEXT MESSAGES TEXT LCD TEXT Meaning ENA Enable DIS Disable ESC...

Page 12: ...ion key Enter ON Mute is used to select upper option in menu SELECT is used to select bottom option in menu Configuration Menu 00 Initial Menu Quit option 01 Output Voltage 02 CF Frequency Conversion...

Page 13: ...battery mode BAT 50 50Hz BAT 60 60Hz If CF function is enable output frequency can be set in normal mode CF 50 50Hz CF 60 60Hz 04 ECO Enable or Disable ENA ECO enable ON DIS ECO disable OFF 05 ECO In...

Page 14: ...e outlets 9 LCD screens depending of Operation Mode Operation Mode Description LCD ONLINE UPS ON Input AC source OK UPS output generated by inverter ECO UPS in ON ECO mode activated Input AC source is...

Page 15: ...MUTE SELECT at same time STAND BY UPS is OFF No power in UPS outlets Input AC source is OK Batteries are been charged 10 ERROR FAILURE CODES ON LCD FAILURE ERROR CODE ICON Bus failure 01 Hi BUS Volta...

Page 16: ...s Battery charger problem 1 s Input out of range in bypass mode 1 s 12 TROUBLESHOOTING TABLE Problem Description Probable Root Cause Suggested Action LCD does not show input voltage value AC input fa...

Page 17: ...onnel Code 28 Active Continuous beep Very low voltage at batteries or charger failure Batteries and charger must be inspected by qualified personnel Intermittent 2 beeps per second UPS overloaded Disc...

Page 18: ...again Battery can be degraded because long lifetime Batteries must be replaced by new batteries Intermittent 1 beep per second FANs blocked or damaged Check FANs and call service support if problem c...

Page 19: ...E PRODUCT Conditions Warranty Plus 1 If during the warranty period this product fails to operate under normal use and service due to defects in materials or workmanship authorized distributor or servi...

Page 20: ...9AH x 6 pcs 12V 9Ah x 12 pcs 3 Sealed Lead Acid VRLA AGM 29 PHYSICAL 580 x 438 x 133 mm 3U Power Outlets Total Progr N2 LCD Panel UPS status Load level Battery Input Output voltage Discharge timer an...

Page 21: ...ed to comply with special project requirements N1 Output voltage is selectable from LCD N2 Backup time for programmable outlets is configurable in minutes from LCD to offer longer time to critical loa...

Reviews: