User Manual

  - ONLINE 6K/10K RACK-TOWER ISOTX UPS

      

                    ENGLISH 

  __________________________________________________________________________________________________________________________ 

 

www.integra-ups.com 

 

130717 RT9- 6K-10K (ENG)

 

 - 3 

 

  1. GENERAL SAFETY INSTRUCTIONS                                   

 

          .                                          

WARNING

: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating 

this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults. 

WARNING

: This product operates with dangerous voltages. It must be installed, operated and maintained ONLY by qualified 

technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related to this 
product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent 
practices at the moment of install, starting up or maintain this product. 
UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation. 

WARNING

: If you are not qualified technician do not try to install, operate or repair this product. 

 

WARNING

: Do not try to install, operate or repair this product if you are not accompanied by another qualified person able to offer 

first aid support in case of emergency or accidents.

 

WARNING

:  Internal  area  of  this  product  is  locked  by  screws.  Do  not try to access inside the UPS unless you are a qualified 

technician. UPS must be checked, repaired and maintained by qualified personnel only. 

 

CAUTION!!: ELECTRIC SHOCK RISK    

CAUTION

: There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line. 

CAUTION:

 Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, thought the UPS is OFF and 

unplugged of power line. 

CAUTION:

 There are dangerous voltages in DC (Direct Current) Capacitors. Please Check Capacitor location in Figure 8.4.1. Wait at 

least 10 minutes after turning off UPS before opening it to access inside. 

DANGER:

 Power off UPS and unplugged it from AC Line before opening it to Access inside this unit. 

CAUTION:

 Before starting the opening procedure, remove all jewelry and metallic objects such as: Rings, Watches, Bracelets, etc., 

because they could contact conductive parts and components inside the UPS and this might cause discharges and/or short circuits. 
Make sure using tools properly isolated to avoid electrical risks. 

 
Transportation and Storage: Warnings and Recommendations 

WARNING:  

This UPS must be transported only in its original package to be properly protected 

WARNING:  

This equipment must be storage in dry and ventilated site, in upright position.

 

WARNING:  

Before storage this UPS, batteries must be recharged for 8 to 10 hours

 

WARNING: 

During long term storage UPS must be recharged periodically according to this manual.

 

 

WARNING: EQUIPMENT DISPOSAL 

 
Out of service units: 

It is strongly recommended to dispose this piece of equipment according to valid directives in your country. At 

the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials 
to be recycled. 

Batteries:

  Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside 

Summary of Contents for OPTIMA RT9 10KVA

Page 1: ...r distributed totally or partially without written approval of INTEGRA INTEGRA can introduce modifications in their products or manuals without further notice INTEGRA is not responsible of mistakes or...

Page 2: ...NAL BLOCK UPS AC LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION 5 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONN...

Page 3: ...d by qualified personnel only CAUTION ELECTRIC SHOCK RISK CAUTION There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line CAUTION Inside this equipmen...

Page 4: ...ondition Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipments connected to UPS Batteries should be p...

Page 5: ...module for offering an isolated dual output 120Vac x 2 for RT9 6K 10K UPS Input 1Ph 220Vac coming from UPS output Output 2 isolated 120Vac outputs Components 1 module 3U with ISOTX EXBATT RT10 EXTERNA...

Page 6: ...3 EPO Emergency Power Off Open Power Output OFF Close Function disable 4 Share Current Port for parallel function 5 Parallel Port for parallel function 6 SNMP Intelligent Slot 7 Cooling Fans 8 Extern...

Page 7: ...ements described by this manual In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must be protected by...

Page 8: ...site should never rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get...

Page 9: ...ts is provided with rack cabinets If not UPS distributor can provide original telescopic guides as optional accessory Small black handles included with the UPS are only for locking purposes UPS cannot...

Page 10: ...______________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 10 TOWER INSTALLATION This UPS can be also inst...

Page 11: ...OWER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 11 3 MODULES...

Page 12: ...d in this manual Moreover installation grounding must be correct This UPS must be connected to appropriate electrical service according to selected model Technical specs sticker in the UPS shows the U...

Page 13: ...Vac 50 Watts each 6KVA ISOTX Output 110 220V Unique Output Capacity 6 000VA 5 400W Output Voltage 120Vac AC Breaker 80A Curve D Max Nominal Current 70A Wiring min size 6AWG 16 mm2 VA W per Output 3 00...

Page 14: ...g external batteries UPS terminal block preparation Remove cover of terminal block at the UPS rear panel in rear panel section of this manual DO NOT use a wall power outlet to plug UPS to AC Line as u...

Page 15: ...__________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 15 UPS TO ISOTX WIRING ISOTX module is an optional accessory rack module th...

Page 16: ...10K RACK TOWER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 16...

Page 17: ...______________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 17 ISOTX OUTPUT CONFIGURATIONS ISOTX outputs ca...

Page 18: ...RNAL BATTERY CABINETS CONNECTION PROCEDURE 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Using appropriate cable supplied with the EXBATT co...

Page 19: ...t to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected directly to electric panel board UPS INPUT AND OUTPUT CONNECTIONS...

Page 20: ...ER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 20 PARALLEL UP...

Page 21: ...__________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 21 PARALLEL USING ISOTX AC LINES CONNECTION NOTE 1 WARNING In parallel systems with ISOTX modules to avoid...

Page 22: ...TOWER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 22 PARALLE...

Page 23: ...re all equipments connected to UPS are off 2 Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON 3 Put Battery Bank breaker to ON Only for Ex Models If using exter...

Page 24: ...r panels as indicated in section 5 of this manual 7 Make sure total available capacity in Watts of all UPS to be connected in parallel is higher than load to be connected to UPS system It is recommend...

Page 25: ...lly Error message must be previously reset according to warning and error section in this manual 8 When rear panel AC breaker is set to ON UPS recognize all other UPS previously powered ON in the para...

Page 26: ...Alarm Calibration Others 13 If AC output voltages are as expected please set to ON external output breakers for all UPS progressively Start with UPS N 1 then UPS N 2 etc After that all UPS outputs are...

Page 27: ...APE OFF Goes directly to TURN OFF menu ESCAPE It works as ESCAPE key for screens options UP UP It works as UP key when navigating through screens menu DOWN DOWN It works as DOWN key when moving throug...

Page 28: ...PS FRONT PANEL LCD This UPS has a sophisticated LCD able to display all important information related to input line UPS status and values operation mode and error and alarm messages It is a powerful i...

Page 29: ...nsfer time of 4 ms typical This mode is configured and activated from LCD panel There is specific input voltage range and input frequency range to configure for ECO mode BYPASS Mode Under BYPASS mode...

Page 30: ...5 Each UPS must have their own external protections to allow total electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the abo...

Page 31: ...buttons in front panel according to section 8 of this manual Configurable functions according to UPS mode Not all functions are available in all operation modes When functions is not available under...

Page 32: ...______________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 32 Configuration menu functions and screens Screens menu is divided in...

Page 33: ...50Hz Mute No Batt 273 0V 99 Para Unlock Load 50 Control Battery Test Mode Battery Test Turn On IP 208 0V 50Hz Batt Test Yes OP 220 0V 50Hz Mute No Batt 245 0V 50 Para Unlock Load 0 Control Battery Mod...

Page 34: ...r 10000VA 00 00 00 Active Power 9000W Load 100 Bypass 4 5 Charger 5 5 Volt 220 0V Volt 273 0V Freq 50 0Hz Status ON F3 INFORMATION FUNCTIONS Bypass 1 6 ECO 2 6 Output 3 6 Status Open Status Open Volt...

Page 35: ...igh Loss F 54Hz Low Loss F 46Hz Bypass Status Forbid High Loss V 264V Low Loss V 110V High Loss F 54Hz Low Loss F 46Hz STATUS OPEN Bypass allowed UPS will run at bypass depending on ENABLE DISABLE par...

Page 36: ...ode HIGH LOSS F Acceptable high limit for input frequency for UPS in ECO mode LOWLOSS F Acceptable min limit for input frequency for UPS in ECO mode SETTING OUTPUT Output Volt 220 0V Freq Auto CVCF Di...

Page 37: ...et below from 000 to 990 min Disable Batteries protection disable UPS will run until reach very low battery level 000 990 Set time in minutes for Discharge protection function BATTERY TEST TYPE Short...

Page 38: ...ailure even UPS has no batteries connected DISABLE It allows UPS to work as standard UPS It will only restart when AC recovery is detected if UPS has batteries connected BACKUP TIME PARAMETERS BATT GR...

Page 39: ...of the parallel system FAULT ON RED 41 Over Temperature Internal UPS temperature above normal limit Possible reasons Fan blocked or ventilation windows are blocked or environment temperature is too h...

Page 40: ...y Cantidad Internal Batt Pack Bat Internas External Batt Cab Gab Ext Typical Recharge T T de Recarga Internal Battery Pack Bat Internas External batt cabinet Gabinete Ext Charging Amps Corriente de Ca...

Page 41: ...0Vac Transformador de aislamiento con salida dual 2 x 110Vac UPS RT9 6K 10K 2 Cabs UPS Battery ISOTX module is optional UPS RT9 6K 10K 2 gabinetes UPS Bater as ISOTX esopcional 57 77 Carton 87x58x25 c...

Page 42: ...ibution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is...