User Manual
- ONLINE 6K/10K RACK-TOWER ISOTX UPS
ENGLISH
__________________________________________________________________________________________________________________________
www.integra-ups.com
130717 RT9- 6K-10K (ENG)
- 36
SETTING / ECO
ECO:
-->
Status: Disable
High Loss: 232V
Low Loss: 184V
High Loss: 52Hz
Low Loss: 48Hz
STATUS ENABLE:
ECO function enable
STATUS DISABLE:
ECO function disable
HIGH LOSS V:
Acceptable high limit for input voltage for UPS in ECO
mode.
LOWLOSS V:
Acceptable min. limit for input voltage for UPS in ECO
mode.
HIGH LOSS F:
Acceptable high limit for input frequency for UPS in
ECO mode.
LOWLOSS F:
Acceptable min. limit for input frequency for UPS in ECO
mode.
SETTING / OUTPUT
Output:
-->
Volt: 220.0V
Freq: Auto
CVCF: Disable
VOLT:
208:
set output voltage to 208Vac
220:
set output voltage to 2220Vac
230:
set output voltage to 230Vac
240:
set output voltage to 240Vac
FREQ:
50Hz:
Set output to 50Hz
60Hz
: Set output to 60Hz
ATO:
Set output according to input frequency.
From 46-54Hz set to 50Hz. From 56 to 64Hz set to 60Hz.
CVCF:
Set if frequency conversion is activated.
Enable:
Output frequency is fixed in 50Hz or 60Hz according to
previous FREQ setting
Disable:
Converter function disables. Output frequency will be
synchronized with input frequency.