  12.- ERROR CODES, ALARMS & TROUBLESHOOTING 

 

 

 

                

 

 

ERROR / FAILURE CODES ON LCD   

 

 

 

 

 

 

   

 

STATUS 

FAULT 

LED CODE 

DESCRIPTION 

SUGGESTION 

FAULT ON-RED 

01 

Bus Start Fail 

Internal converter fails. PSDR board need to be replaced. Contact service 

support 

FAULT ON-RED 

02 

Bus Over 

Main AC input or load transient make DC BUS voltage high or converter 
fails. Try to shutdown and restart UPS. If fails again contact service 
support. 

FAULT ON-RED 

03 

Bus Under 

Internal converter fails. PSDR board need to be replaced. Contact service 
support 

FAULT ON-RED 

04 

Bus Unbalance 

Load connected to UPS output is abnormal (too inductive or halfwave). 

Disconnect load and shutdown and restart UPS. If fail is solved the 
problem is related to kind of load connected to UPS.If fail continues 
contact service support.  

FAULT ON-RED 

11 

Inverter Start Fail 

Inverter Fails. Contact service support 

FAULT ON-RED 

12 

Inverter Voltage High 

Inverter Fails. Contact service support 

FAULT ON-RED 

13 

Inverter Voltage Low 

Inverter Fails. Contact service support 

FAULT ON-RED 

14 

Output Short 

A short circuit was detected at UPS output. Solve short circuit and restart 
UPS. 

FAULT ON-RED 

1A 

Negative Power 

UPS power output is negative. There is a power feedback from UPS 
outputs because a regenerative load or because a problem in current 
control in a parallel system. 

FAULT ON-RED 

21 

Battery SCR Short 

Contact service support. 

FAULT ON-RED 

24 

Inverter Relay Short 

Contact service support. 

FAULT ON-RED 

35 

Parallel Comm. Fail 

Revise all parallel cables of the system. 

FAULT ON-RED 

36 

Output Current Unbalance  Revise AC wiring of the parallel system. 

FAULT ON-RED 

41 

Over Temperature 

Internal UPS temperature above normal limit. Possible reasons: Fan 
blocked or ventilation windows are blocked or environment temperature is 
too hot combined with high load connected to UPS 

FAULT ON-RED 

42 

CPU Comm. Fail 

Contact service support. 

FAULT ON-RED 

43 

Overload 

Power consumption of equipments connected to UPS output is too high. 

Remove no critical equipment from UPS 

 
ALARM 

CODES 

ON 

LCD           

 

STATUS 

FAULT 

LED CODE 

DESCRIPTION 

SUGGESTION 

WARNING OFF 

01 

Battery Open 

Check Battery cables and battery fuse 

WARNING OFF 

07 

Over Charge 

Battery quantity is not OK or Charger Voltage is too high or Charger is 
damaged 

WARNING OFF 

08 

Battery Low 

Batteries under low voltage or Battery quantity is not OK or Battery 
exhausted 

WARNING OFF 

09 

UPS overload 

Connected load to UPS is above UPS max capacity. 

WARNING OFF 

0A 

Fan Error 

Fan blocked or fan damaged or fan detection circuit damaged 

WARNING OFF 

0B 

EPO activated 

EPO jumper has been removed or emergency switch connected to EPO 
port is activated 

WARNING OFF 

0D 

Over Temperature 

Internal UPS temperature above normal limit. Possible reasons: Fan 
blocked or ventilation windows are blocked or environment temperature is 
too hot combined with high load connected to UPS 

WARNING OFF 

0E 

Charger Fail 

Charger fail 

WARNING OFF 

10 

Input fuse open 

Input AC fuse in power stage of the UPS is burnt 

WARNING OFF 

33 

External and repetitive 
overload 

UPS has detected 3 repetitive overload at their output in less than 30 min. 

WARNING OFF 

3A 

External bypass switch 
cover is open 

Cover for external maintenance bypass switch has been removed or 
external bypass switch cable is disconnected. 

WARNING OFF 

3F 

Parallel Protection 
Activated 

When a problem is detected in regards to parallel communication between 
some UPS in parallel warning code 3F is activated. Please check all 

parallel cables and go to CONTROL screen menu to unlock PARA 
UNLOCK parameter before trying to restart UPS.  

 

Summary of Contents for OPTIMA RT9 10KVA

Page 1: ...r distributed totally or partially without written approval of INTEGRA INTEGRA can introduce modifications in their products or manuals without further notice INTEGRA is not responsible of mistakes or...

Page 2: ...NAL BLOCK UPS AC LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION 5 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONN...

Page 3: ...d by qualified personnel only CAUTION ELECTRIC SHOCK RISK CAUTION There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line CAUTION Inside this equipmen...

Page 4: ...ondition Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipments connected to UPS Batteries should be p...

Page 5: ...module for offering an isolated dual output 120Vac x 2 for RT9 6K 10K UPS Input 1Ph 220Vac coming from UPS output Output 2 isolated 120Vac outputs Components 1 module 3U with ISOTX EXBATT RT10 EXTERNA...

Page 6: ...3 EPO Emergency Power Off Open Power Output OFF Close Function disable 4 Share Current Port for parallel function 5 Parallel Port for parallel function 6 SNMP Intelligent Slot 7 Cooling Fans 8 Extern...

Page 7: ...ements described by this manual In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must be protected by...

Page 8: ...site should never rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get...

Page 9: ...ts is provided with rack cabinets If not UPS distributor can provide original telescopic guides as optional accessory Small black handles included with the UPS are only for locking purposes UPS cannot...

Page 10: ...______________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 10 TOWER INSTALLATION This UPS can be also inst...

Page 11: ...OWER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 11 3 MODULES...

Page 12: ...d in this manual Moreover installation grounding must be correct This UPS must be connected to appropriate electrical service according to selected model Technical specs sticker in the UPS shows the U...

Page 13: ...Vac 50 Watts each 6KVA ISOTX Output 110 220V Unique Output Capacity 6 000VA 5 400W Output Voltage 120Vac AC Breaker 80A Curve D Max Nominal Current 70A Wiring min size 6AWG 16 mm2 VA W per Output 3 00...

Page 14: ...g external batteries UPS terminal block preparation Remove cover of terminal block at the UPS rear panel in rear panel section of this manual DO NOT use a wall power outlet to plug UPS to AC Line as u...

Page 15: ...__________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 15 UPS TO ISOTX WIRING ISOTX module is an optional accessory rack module th...

Page 16: ...10K RACK TOWER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 16...

Page 17: ...______________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 17 ISOTX OUTPUT CONFIGURATIONS ISOTX outputs ca...

Page 18: ...RNAL BATTERY CABINETS CONNECTION PROCEDURE 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Using appropriate cable supplied with the EXBATT co...

Page 19: ...t to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected directly to electric panel board UPS INPUT AND OUTPUT CONNECTIONS...

Page 20: ...ER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 20 PARALLEL UP...

Page 21: ...__________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 21 PARALLEL USING ISOTX AC LINES CONNECTION NOTE 1 WARNING In parallel systems with ISOTX modules to avoid...

Page 22: ...TOWER ISOTX UPS ENGLISH __________________________________________________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 22 PARALLE...

Page 23: ...re all equipments connected to UPS are off 2 Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON 3 Put Battery Bank breaker to ON Only for Ex Models If using exter...

Page 24: ...r panels as indicated in section 5 of this manual 7 Make sure total available capacity in Watts of all UPS to be connected in parallel is higher than load to be connected to UPS system It is recommend...

Page 25: ...lly Error message must be previously reset according to warning and error section in this manual 8 When rear panel AC breaker is set to ON UPS recognize all other UPS previously powered ON in the para...

Page 26: ...Alarm Calibration Others 13 If AC output voltages are as expected please set to ON external output breakers for all UPS progressively Start with UPS N 1 then UPS N 2 etc After that all UPS outputs are...

Page 27: ...APE OFF Goes directly to TURN OFF menu ESCAPE It works as ESCAPE key for screens options UP UP It works as UP key when navigating through screens menu DOWN DOWN It works as DOWN key when moving throug...

Page 28: ...PS FRONT PANEL LCD This UPS has a sophisticated LCD able to display all important information related to input line UPS status and values operation mode and error and alarm messages It is a powerful i...

Page 29: ...nsfer time of 4 ms typical This mode is configured and activated from LCD panel There is specific input voltage range and input frequency range to configure for ECO mode BYPASS Mode Under BYPASS mode...

Page 30: ...5 Each UPS must have their own external protections to allow total electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the abo...

Page 31: ...buttons in front panel according to section 8 of this manual Configurable functions according to UPS mode Not all functions are available in all operation modes When functions is not available under...

Page 32: ...______________________________________________________________________________________ www integra ups com 130717 RT9 6K 10K ENG 32 Configuration menu functions and screens Screens menu is divided in...

Page 33: ...50Hz Mute No Batt 273 0V 99 Para Unlock Load 50 Control Battery Test Mode Battery Test Turn On IP 208 0V 50Hz Batt Test Yes OP 220 0V 50Hz Mute No Batt 245 0V 50 Para Unlock Load 0 Control Battery Mod...

Page 34: ...r 10000VA 00 00 00 Active Power 9000W Load 100 Bypass 4 5 Charger 5 5 Volt 220 0V Volt 273 0V Freq 50 0Hz Status ON F3 INFORMATION FUNCTIONS Bypass 1 6 ECO 2 6 Output 3 6 Status Open Status Open Volt...

Page 35: ...igh Loss F 54Hz Low Loss F 46Hz Bypass Status Forbid High Loss V 264V Low Loss V 110V High Loss F 54Hz Low Loss F 46Hz STATUS OPEN Bypass allowed UPS will run at bypass depending on ENABLE DISABLE par...

Page 36: ...ode HIGH LOSS F Acceptable high limit for input frequency for UPS in ECO mode LOWLOSS F Acceptable min limit for input frequency for UPS in ECO mode SETTING OUTPUT Output Volt 220 0V Freq Auto CVCF Di...

Page 37: ...et below from 000 to 990 min Disable Batteries protection disable UPS will run until reach very low battery level 000 990 Set time in minutes for Discharge protection function BATTERY TEST TYPE Short...

Page 38: ...ailure even UPS has no batteries connected DISABLE It allows UPS to work as standard UPS It will only restart when AC recovery is detected if UPS has batteries connected BACKUP TIME PARAMETERS BATT GR...

Page 39: ...of the parallel system FAULT ON RED 41 Over Temperature Internal UPS temperature above normal limit Possible reasons Fan blocked or ventilation windows are blocked or environment temperature is too h...

Page 40: ...y Cantidad Internal Batt Pack Bat Internas External Batt Cab Gab Ext Typical Recharge T T de Recarga Internal Battery Pack Bat Internas External batt cabinet Gabinete Ext Charging Amps Corriente de Ca...

Page 41: ...0Vac Transformador de aislamiento con salida dual 2 x 110Vac UPS RT9 6K 10K 2 Cabs UPS Battery ISOTX module is optional UPS RT9 6K 10K 2 gabinetes UPS Bater as ISOTX esopcional 57 77 Carton 87x58x25 c...

Page 42: ...ibution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is...

Reviews: