Setting Up
CI-3K50601 Project 2191 DMR2731 Rev.1 18-08-11
14
15.
Press
to confirm your selection. SET will be displayed.
16.
Press
to exit parity setting routine. SET will go off and
the
and
keys can be used to select a different
Comms parameter.
Stop Bits(not applicable for JC N2)
Note that, if Parity is set to Odd or Even, Stop Bits will be set to 1 and cannot be changed.
17.
Use the
and
keys to select the Stop Bits option.
18.
Press
to enter the Stop Bits setting routine. The
parameter value will flash.
19.
Use the
and
keys to select the desired number of
Stop Bits – 1 or 2.
20.
Press
to confirm your selection. SET will be displayed.
21.
Press
to exit Stop Bits setting routine. SET will go off and
the
and
keys can be used to select a different
Comms parameter.
RS485 Address
An RS485 network can accommodate up to 255 different devices, each identified by an
address between 1 and 247 (Modbus™) or 1 and 255 (JC N2).
22.
Use the
and
keys to select the Address option.
23.
Press
to enter the Address setting routine. The first digit
will flash.
24.
Use the method described in Section 4.2.2 to set the 3-digit
address to the required number between 1 and 247 for
Modbus™ or 1 and 255 for JC N2.