SITE INSPECTION AND INSTALLATION CONDITIONS
REGULATIONS AND LEGAL DIRECTIVES
It is necessary to check that installation site, wiring and power protection in the installation supplied by end user, fulfill technical parameters
required by UPS.
A particular installation might accomplish with UPS requirements but not with local directives and regulations.
The end user and/or electrical contractor will be responsible of watching for complying with electrical regulations and normative during
electrical installation managed by end user.
Inspection performed by installation technician is not intended to confirm regulations and directives accomplishing but only with technical
needs for optimal UPS operation.
SITE INSPECTION
•
During transport of this UPS from a cold place to a warmer and more humid one, some condensation could be generated. Leave
the UPS for at least 2 hours to climate to new installation site.
•
Do not install the UPS outdoors or near water sources nor in wet environment
•
Do not install the UPS in sites exposed to sun light or heat sources. Temperature at operation site should never rise over 35 ºC.
Batteries
’ life shortens over 25 ºC.
•
Installation site must be dry, fresh, free of dust, fibers and any other objects (conductors or not) suspended in the air that could
get into the UPS thru the ventilation system (Fan).
•
Do not block UPS ventilations
UPS INPUT AND OUTPUT POWER LINES PROTECTION
AC LINES PROTECTIONS DEVICES:
All UPS Inputs and outputs must be protected by circuit breakers and current leak protections. Protection capacity and type must fulfill
local regulations as well as directives from this manual. Grounding must be according to local directives as well. Please check wiring and
protections selection table in this section of the manual. A wrong selection of breakers and current leak protections could generate false
trips.
LEAK CURRENT PROTECTION:
In many countries, now a day, it is legally required to install protections against current leakage to protect human beings in cases of leaks
o discharges to ground. It is responsibility of the end user and/or electrical contractor selecting and including these protection devices in
the electrical circuit of the UPS.
DC PROTECTIONS DEVICES:
For Ex models (with external batteries) there must be also DC Circuit Breakers between UPS and battery bank.
Some Models include a DC breaker on the rear panel for external battery pack protection; otherwise an external DC Circuit breaker must
be installed.