170502-OPTIMA-33 10K/20K/30K (ENGLISH) - 17 

 

 

 

START UP FOR PARALLEL UPS SYSTEM 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING: Make sure all requirements and previous inspection have been revised and complied before initiating start up procedure. If 

not please do not try to continue with start-up procedure. 

 

1.- Make sure all equipments to be protected and connected to UPS output are in OFF condition. 

2.- Check AC input breaker located in UPS rear panels is in OFF position in all UPS of the system. 

3.- Power on external main AC input in electrical panel. Set to ON position all external AC input    breakers. 

4.- If UPS are using external battery packs, set to ON all DC breakers to connect external DC packs to UPS. 

5.- For UPS No. 1: Set to "ON" AC input breaker located in rear panel of UPS No. 1. Wait until UPS No.1 completes auto-checking and Bypass 

LED lights continuously. 

6.- For UPS No. 2: Set to "ON" AC input breaker located in rear panel of UPS No. 2. Wait until UPS No.2 completes auto-checking and Bypass 

LED lights continuously. 

7.-In case of having 3 UPS in the system, proceed in similar manner with UPS No. 3. 

 IMPORTANT: AC input breakers activation must be done in one by one and not at same time. First for UPS No. 1, then for UPS No. 2 and 

finally for UPS No. 3 (if you have a parallel system with 3 UPS). If AC input breakers are activated all at same time, warning message "3F" 

could be activated. If it occurs, reinitiate procedure sequentially. Warning 3F message must be previously reset according to warning and 

error section in this manual 

8.- When rear panel AC breaker is set to "ON", This UPS recognizes all other UPS previously powered ON in the parallel system and will get 

its own parallel identification as PAR 00X, where X is the position according to power on sequence. PAR 001 for 1st UPS powered on, PAR 

002 for 2nd and PAR 003 for 3rd UPS.   

 This message is only indicated in UPS manufactured after Dec-2011. 

 

 

9.- At this moment all UPS LCDs must turn on to indicate internal circuitry in UPS is been powered. 

  

** If bypass mode is allowed, all UPS will go to bypass mode. 

  

** If bypass mode is not allowed by configuration, all UPS will go to a kind of stand-by mode with outputs open and powered off 

waiting until ON command is selected in UPS front panel. 

10.- At this moment configuration menu in each UPS LCD must be revised to select desired configuration. It is mandatory to use same 

configuration in all configuration parameters for all UPS of the system. 

11.- Once configuration has been selected and verified, all UPS can be started up by selecting "ON" push button in front panel. Please press 

"ON" push button for each UPS. One long "beep" will be generated. "ON" message will be displayed on top side of LCD. 

12.- All UPS will go to NORMAL Online mode at same time. 

13.- Before setting to "ON" external output breakers please revise AC voltage output on each UPS.   

 ** Please measure AC output voltage using a digital multi-meter and confirm all output voltages are similar. Maximum acceptable deviation 

should be 3Vac or lower. Typically 1.5Vac. 

**  If  difference  between  output  voltage  values  is  higher  than  3Vac,  we  suggest  to  adjust  them  by  function  15  (for  inverter  output  L1),   

function 16 (for inverter output L2) and function 17 (for inverter output L3). You can reduce (Sub) or increase (Add) voltage output voltage 

for any of 3 inverters in each UPS as required. 

 

 

 

14.- If AC output voltages are similar (lower than 3Vac), please set to "ON" external output breakers for all UPS progressively. Start with UPS 

Nº 1, then UPS Nº 2, etc. After that, all UPS outputs are connected in parallel.   

15. Check to confirm there are no error or alarm messages on LCDs. At this moment all UPS are working in NORMAL Online mode and 

connected in parallel. 

16.- It is time to power on equipments connected to UPS output. Power on progressively one by one. Check on UPS LCDs how power output 

rises meanwhile equipments are powered on. 

  

** Once all output load is connected check power output is below 100%. 

  

** At this moment, UPS parallel system is powering your system in NORMAL Online mode. 

Summary of Contents for Xmart OPTIMA-33 10K

Page 1: ...on this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products o...

Page 2: ...UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION 6 START UP SINGLE UPS INSPECTION BEFORE START UP SINGLE UPS START UP PROCEDURE...

Page 3: ...ect sun light dust and extreme temperature WARNING Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation WARNING This UPS must be connected to appropriate elect...

Page 4: ...2 2 Class 2 3 WARNING Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party responsible for compliance could void the use...

Page 5: ...nal working values UPS cabinet includes all electronic and I O transformers Batteries are located in dedicated external battery cabinet EXBATT BATTERY CABINETS If external batteries are required for 2...

Page 6: ...Bater as Externas 3 EPO Emergency Stop Parada Emergencia 9 AC Input Breaker Breaker de Entrada AC 4 Share Current for parallel UPS para UPS paralelas 10 Terminal block cover Tapa Regleta Conexiones 5...

Page 7: ...that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must be protected by protection devices against over c...

Page 8: ...C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru the ventilation system Fan Do not block UPS vent...

Page 9: ...must be protected by magneto thermal protection devices against over current breakers with capacity and technology appropriate to effectively accomplish its function as indicated in this manual Moreov...

Page 10: ...8 AWG 10 mm2 Neutral 6 AWG 16 mm2 Ground 6 AWG 16 mm2 Breaker 50 Amps AC Curve D Max Nominal Current Ph N 30A in normal mode 220V Wiring min recommended size Phase 8 AWG 10 mm2 Neutral 6 AWG 16 mm2 G...

Page 11: ...nd 4 AWG 25 mm2 Breaker 100Amps DC Curve C Wiring min recommended size 6 AWG 16mm2 30KVA 208 120VAC Breaker 125 Amps AC Curve D Max Nominal Current Ph N 111A in normal mode 100V Wiring min recommended...

Page 12: ...panel UPS Input wires must come from electric panel board and they must be protected by a circuit breaker protection device Connect input and output ground wires to the UPS chassis or terminal block G...

Page 13: ...s 240Vdc Measure and verify DC voltage supplied by battery pack before making connections 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Usin...

Page 14: ...AL BLOCK PREPARATION Remove cover of terminal block at the UPS rear panel identified as 10 in rear panel section of this manual UPS INPUT AND OUTPUT CONNECTIONS Connect input and output ground wires t...

Page 15: ...USER MANUAL OPTIMA 33 10K 20K 30K www xmart ups com 170502 OPTIMA 33 10K 20K 30K ENGLISH 13 PARALLEL TERMINAL BLOCK WIRING...

Page 16: ...USER MANUAL OPTIMA 33 10K 20K 30K www xmart ups com 170502 OPTIMA 33 10K 20K 30K ENGLISH 14 PARALLEL CONTROL CABLES...

Page 17: ...Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON 3 Put Battery Bank breaker to ON Only for Ex Models If using external battery pack 4 Put AC INPUT Breaker to ON...

Page 18: ...le capacity in Watts of all UPS to be connected in parallel is higher than load to be connected to UPS system It is recommendable total UPS power is at least 25 higher to total load If UPS system will...

Page 19: ...2011 9 At this moment all UPS LCDs must turn on to indicate internal circuitry in UPS is been powered If bypass mode is allowed all UPS will go to bypass mode If bypass mode is not allowed by configur...

Page 20: ...d to turn UPS OFF ESCAPE It Works as ESCAPE key when LCD is in configuration menu mode TEST UP BATTERY TEST When UPS is in normal mode by selecting TEST key UPS enters into battery test mode during 10...

Page 21: ...NDICATOR LIGHTS There are 4 LED indication lights in front panel located below LCD These 4 LEDs describe UPS condition as follow MODE Bypass Line Battery Fault UPS is in Auto check mode during start u...

Page 22: ...es to battery mode elapsed time during battery mode is displayed in Hours Minutes Seconds 3 ERROR ALARM CODE In case of alarm or error 2 digits code is displayed in this section to describe the kind o...

Page 23: ...s AC input is out of acceptable range it enters into Normal Online mode If an AC failure occurs under ECO mode the UPS s inverter starts working draining energy from batteries There is a transfer time...

Page 24: ...ting mode status UPS Power On Description When UPS is powered on it will enter into this mode for a few seconds as initializing the CPU and system LCD display No output mode Description When bypass vo...

Page 25: ...en the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode LCD display ECO mode Description When the input volt...

Page 26: ...set to CF the inverter will output constant frequency 50 Hz or 60 Hz At this mode the UPS will have no bypass output but still charge battery LCD display Battery mode Description When the input voltag...

Page 27: ...s enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test Description When UPS is in AC mode or CVCF mode press Test key for more than 0 5s Then t...

Page 28: ...nt the warning situation In the warning screen the icon will be flashing and it can show up to 3 error codes and each code indicates one error You can find the code meaning in the warning code table L...

Page 29: ...electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the above requirements cannot be complied below procedure must not be per...

Page 30: ...mode Code Description Bypass No Output mode AC mode ECO mode CVCF mode Battery mode Battery Test 01 Output voltage 02 Output frequency 03 Voltage range for bypass 04 Frequency range for bypass 05 ECO...

Page 31: ...Disable AtO Auto bAT Battery NCF Normal mode not CVCF mode CF CVCF mode SUb Subtract Add Add ON On OFF Off Fbd Not allowed OPN Allow RES Reserved N L Neutral line loss CHE Check OP V Output voltage P...

Page 32: ...utput frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not CVCF mode If selected the output fre...

Page 33: ...e The setting range is from 5 to 10 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface...

Page 34: ...neutral loss is detected an alarm will be generated If the UPS is turned on it will transfer to battery mode When neutral is restored and detected the alarm will be muted automatically and the UPS wi...

Page 35: ...arger voltage Any modification should be suitable to battery specifications 15 Inverter A voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter A voltage Parame...

Page 36: ...urement value of the output B voltage and you can calibrate it by pressing Up or Down according to the measurement from an external voltage meter The calibration result will be effective by pressing E...

Page 37: ...eutral short circuit SHORT 16 Inverter C L3 output line to neutral short circuit SHORT 17 Inverter A B L1 L2 output line to line short circuit detected SHORT 18 Inverter B C L2 L3 output line to line...

Page 38: ...different 22 In parallel systems bypass situation different 33 Locked in bypass after overload 3 times in 30min 34 Converter current unbalance 35 Battery fuse broken 36 Inverter inter current unbalanc...

Page 39: ...ble Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping every second I P fuse broken Beeping every second Overload 3 times in 30min Beeping every second ALAR...

Page 40: ...t 2 beeps per second UPS overloaded Disconnect devices from UPS outlets until solving overload Intermittent 2 beeps per second By Pass activated UPS overloaded UPS has changed to BYPASS mode to avoid...

Page 41: ...ter as UPS 33 400 230Vac with internal batt internal 1 set x 20pcs internal 2 sets x 20pcs internal 3 sets x 20pcs UPS 33 208 120Vac no internal batt External batt cabinet Bater as Externas 1 set x 20...

Page 42: ...ones pueden cambiar sin previo aviso N1 Output voltage is selectable by LCD El Voltaje de salida es configurable entre 4 alternativas seleccionables en el LCD N2 Backup time for programable outlets is...

Page 43: ...tribution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product i...

Page 44: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Zona Ind San Vicente II C F A11 Maracay Venezuela...

Reviews: