USER MANUAL 

 OPTIMA-33 10K/20K/30K 

www.xmart-ups.com                                                                       

170502-OPTIMA-33 10K/20K/30K (ENGLISH) - 40 

 

 
    13.- TECHNICAL SPECIFICATIONS (2/2) 

 

 

 

 

 

 

 

 

 

 

 

     

 

ONLINE UPS   33 Series

33 10K

33 20K

33 30K

INDICATORS / INDICADORES

LCD / Pantalla de Cristal Liquido (LCD)

ALARM / ALARMAS

Acoustic Beep Alarm / Alarma sonora: 

PRODUCT SIZE & NET WEIGHT / TAMAÑO Y PESO NETO

SIZE: UPS-33 400/230Vac (with internal batt.)

DxWxH: 815*250*826mm 

DxWxH: 815*250*826mm 

DxWxH: 815*300*1000mm 

SIZE: UPS-33 208/120Vac (no internal batt.)

DxWxH: 815*250*826mm

DxWxH: 815*250*826mm

DxWxH: 815*300*1000mm 

SIZE: Ext. Batt Cab. / Baterías Externas

DxWxH: 592*250*576 mm

DxWxH: 592*250*576 mm

DxWxH: 830*250*576 mm

WEIGHT (Kg): UPS-33 400/230Vac (with int. batt.)

109

164

233

WEIGHT (Kg): UPS-33 208/120Vac (no int. batt.)

124

160

224

WEIGHT (Kg): Ext. batt Cab. / Baterías Ext.

67

119

189

PACKING: Individual Small Pallet per Unit / EMPAQUE: Equipo en Pallet Individual

SIZE:  UPS-33 400/230Vac (with internal batt.)

DxWxH: 920*385*1071mm

DxWxH: 920*385*1071mm

DxWxH: 920*430*1205mm

SIZE:  UPS-33 208/120Vac (no internal batt.)

DxWxH: 920*385*1071mm

DxWxH: 920*385*1071mm

DxWxH: 920*430*1205mm

SIZE:  Ext. Batt Cab. / Baterías Externas

DxWxH: 700*385*823mm

DxWxH: 700*385*823mm

DxWxH: 965*385*823mm

WEIGHT (Kg): UPS-33 400/230Vac (with int. batt.)

116

171

247

WEIGHT (Kg): UPS-33 208/120Vac (no int. batt.)

142

178

238

WEIGHT (Kg):  Ext. batt Cab. / Baterías Ext.

77

129

203

OPERATING / AMBIENTALES

Operating Conditions / Condiciones de Operación
Noise Level / Ruido Producido
Altitude / Altura

COMMUNICATION / COMUNICACION

Smart RS-232 & USB ports
Intelligent Port (SNMP)

Specifications can be modified to comply with special requirements. Technical specifications may change without further notice

Las especificaciones pueden bajo requerimiento adaptarse a proyectos especiales. Las especificaciones pueden cambiar sin previo aviso.
(*N1): 

Output voltage is selectable by LCD

 / El Voltaje de salida es configurable entre 4 alternativas seleccionables en el LCD

(*N2): 

Backup time for programable outlets is configurable (in minutes) by LCD to offer longer time to critical loads connected to normal outlets

           La autonomía de las salidas programables es configurable (en min.) en el LCD para dejar mayor autonomía para las salidas normales
(*N3): 

Converter Mode Function allows to set output frequency at constant value: 50Hz or 60Hz when input Frequency is within 40 - 70 Hz

           El modo de Conversión de Frecuencia permite fijar la salida a 50 o 60Hz siempre que la frecuencia de entrada se mantenga entre 40 y 70 Hz.
** 

Derate capacity to 60% of total capacity when Frequency converter mode is activated.

     La capacidad en VA/ Watts se degrada y baja hasta el 60% en modo "Convertidor de Frecuiencia".
** 

When output voltage is set to 208V, output capacity is derated to 90% of total capacity in Watts. For example 10KVA model derates to 9KVA

     Cuando el voltaje de salida se ajusta a 208Vac (L-N) se pierde un 10% de capacidad de salida. Por ejemplo el modelo 10KVA baja a 9KVA
** 

Maximum working altitud is 4.000m. Over 1.000m output derates 1% every 100m.

     Altura máxima de operación es 4.000m. Sobre los 1.000m la potencia de salida disminuye un 1% cada 100m.

Efficiency for 208/120V models are 5% to 10% lower than reported values for 400/230Vac models

La eficiencia de los modelos 208/120V son de 5% a 10% menores a los modelos 400/230V

Optional / Opcional: LAN, AS400 & RS485

 -5ºC  to  +40 ºC  /  <95 % (non-condensing / no condensante)

Full Status, Error Codes and Real Time Values  /  Estado, Códigos Error y Valores

Windows family, Linux, Unix and MAC

Battery Mode, Low Batt., Overload, UPS Failure  /  Modo Batería, Baja Bat., Sobrecargas, Falla

Max Altitude: 4.500m. (over 1.000m output capacity is de-rated 1% every 100m)   /  

 Altura máx 4.500msnm (sobre 1.000m la capaidad de salida disminuye 1% cada 100m)

< 63dB @ 1m

 

Summary of Contents for Xmart OPTIMA-33 10K

Page 1: ...on this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products o...

Page 2: ...UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION 6 START UP SINGLE UPS INSPECTION BEFORE START UP SINGLE UPS START UP PROCEDURE...

Page 3: ...ect sun light dust and extreme temperature WARNING Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation WARNING This UPS must be connected to appropriate elect...

Page 4: ...2 2 Class 2 3 WARNING Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party responsible for compliance could void the use...

Page 5: ...nal working values UPS cabinet includes all electronic and I O transformers Batteries are located in dedicated external battery cabinet EXBATT BATTERY CABINETS If external batteries are required for 2...

Page 6: ...Bater as Externas 3 EPO Emergency Stop Parada Emergencia 9 AC Input Breaker Breaker de Entrada AC 4 Share Current for parallel UPS para UPS paralelas 10 Terminal block cover Tapa Regleta Conexiones 5...

Page 7: ...that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must be protected by protection devices against over c...

Page 8: ...C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru the ventilation system Fan Do not block UPS vent...

Page 9: ...must be protected by magneto thermal protection devices against over current breakers with capacity and technology appropriate to effectively accomplish its function as indicated in this manual Moreov...

Page 10: ...8 AWG 10 mm2 Neutral 6 AWG 16 mm2 Ground 6 AWG 16 mm2 Breaker 50 Amps AC Curve D Max Nominal Current Ph N 30A in normal mode 220V Wiring min recommended size Phase 8 AWG 10 mm2 Neutral 6 AWG 16 mm2 G...

Page 11: ...nd 4 AWG 25 mm2 Breaker 100Amps DC Curve C Wiring min recommended size 6 AWG 16mm2 30KVA 208 120VAC Breaker 125 Amps AC Curve D Max Nominal Current Ph N 111A in normal mode 100V Wiring min recommended...

Page 12: ...panel UPS Input wires must come from electric panel board and they must be protected by a circuit breaker protection device Connect input and output ground wires to the UPS chassis or terminal block G...

Page 13: ...s 240Vdc Measure and verify DC voltage supplied by battery pack before making connections 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Usin...

Page 14: ...AL BLOCK PREPARATION Remove cover of terminal block at the UPS rear panel identified as 10 in rear panel section of this manual UPS INPUT AND OUTPUT CONNECTIONS Connect input and output ground wires t...

Page 15: ...USER MANUAL OPTIMA 33 10K 20K 30K www xmart ups com 170502 OPTIMA 33 10K 20K 30K ENGLISH 13 PARALLEL TERMINAL BLOCK WIRING...

Page 16: ...USER MANUAL OPTIMA 33 10K 20K 30K www xmart ups com 170502 OPTIMA 33 10K 20K 30K ENGLISH 14 PARALLEL CONTROL CABLES...

Page 17: ...Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON 3 Put Battery Bank breaker to ON Only for Ex Models If using external battery pack 4 Put AC INPUT Breaker to ON...

Page 18: ...le capacity in Watts of all UPS to be connected in parallel is higher than load to be connected to UPS system It is recommendable total UPS power is at least 25 higher to total load If UPS system will...

Page 19: ...2011 9 At this moment all UPS LCDs must turn on to indicate internal circuitry in UPS is been powered If bypass mode is allowed all UPS will go to bypass mode If bypass mode is not allowed by configur...

Page 20: ...d to turn UPS OFF ESCAPE It Works as ESCAPE key when LCD is in configuration menu mode TEST UP BATTERY TEST When UPS is in normal mode by selecting TEST key UPS enters into battery test mode during 10...

Page 21: ...NDICATOR LIGHTS There are 4 LED indication lights in front panel located below LCD These 4 LEDs describe UPS condition as follow MODE Bypass Line Battery Fault UPS is in Auto check mode during start u...

Page 22: ...es to battery mode elapsed time during battery mode is displayed in Hours Minutes Seconds 3 ERROR ALARM CODE In case of alarm or error 2 digits code is displayed in this section to describe the kind o...

Page 23: ...s AC input is out of acceptable range it enters into Normal Online mode If an AC failure occurs under ECO mode the UPS s inverter starts working draining energy from batteries There is a transfer time...

Page 24: ...ting mode status UPS Power On Description When UPS is powered on it will enter into this mode for a few seconds as initializing the CPU and system LCD display No output mode Description When bypass vo...

Page 25: ...en the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode LCD display ECO mode Description When the input volt...

Page 26: ...set to CF the inverter will output constant frequency 50 Hz or 60 Hz At this mode the UPS will have no bypass output but still charge battery LCD display Battery mode Description When the input voltag...

Page 27: ...s enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test Description When UPS is in AC mode or CVCF mode press Test key for more than 0 5s Then t...

Page 28: ...nt the warning situation In the warning screen the icon will be flashing and it can show up to 3 error codes and each code indicates one error You can find the code meaning in the warning code table L...

Page 29: ...electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the above requirements cannot be complied below procedure must not be per...

Page 30: ...mode Code Description Bypass No Output mode AC mode ECO mode CVCF mode Battery mode Battery Test 01 Output voltage 02 Output frequency 03 Voltage range for bypass 04 Frequency range for bypass 05 ECO...

Page 31: ...Disable AtO Auto bAT Battery NCF Normal mode not CVCF mode CF CVCF mode SUb Subtract Add Add ON On OFF Off Fbd Not allowed OPN Allow RES Reserved N L Neutral line loss CHE Check OP V Output voltage P...

Page 32: ...utput frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not CVCF mode If selected the output fre...

Page 33: ...e The setting range is from 5 to 10 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface...

Page 34: ...neutral loss is detected an alarm will be generated If the UPS is turned on it will transfer to battery mode When neutral is restored and detected the alarm will be muted automatically and the UPS wi...

Page 35: ...arger voltage Any modification should be suitable to battery specifications 15 Inverter A voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter A voltage Parame...

Page 36: ...urement value of the output B voltage and you can calibrate it by pressing Up or Down according to the measurement from an external voltage meter The calibration result will be effective by pressing E...

Page 37: ...eutral short circuit SHORT 16 Inverter C L3 output line to neutral short circuit SHORT 17 Inverter A B L1 L2 output line to line short circuit detected SHORT 18 Inverter B C L2 L3 output line to line...

Page 38: ...different 22 In parallel systems bypass situation different 33 Locked in bypass after overload 3 times in 30min 34 Converter current unbalance 35 Battery fuse broken 36 Inverter inter current unbalanc...

Page 39: ...ble Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping every second I P fuse broken Beeping every second Overload 3 times in 30min Beeping every second ALAR...

Page 40: ...t 2 beeps per second UPS overloaded Disconnect devices from UPS outlets until solving overload Intermittent 2 beeps per second By Pass activated UPS overloaded UPS has changed to BYPASS mode to avoid...

Page 41: ...ter as UPS 33 400 230Vac with internal batt internal 1 set x 20pcs internal 2 sets x 20pcs internal 3 sets x 20pcs UPS 33 208 120Vac no internal batt External batt cabinet Bater as Externas 1 set x 20...

Page 42: ...ones pueden cambiar sin previo aviso N1 Output voltage is selectable by LCD El Voltaje de salida es configurable entre 4 alternativas seleccionables en el LCD N2 Backup time for programable outlets is...

Page 43: ...tribution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product i...

Page 44: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Zona Ind San Vicente II C F A11 Maracay Venezuela...

Reviews: