USER MANUAL - OPTIMA RT10 1K/1.5K/2K/3K (UL)
VER.2010.22-One (ENG)
12
7.
UPS CONFIGURATION
Configuration menu allows setting of functions and parameters of the UPS.
Menu is activated by pressing
< SELECT >
during 3 seconds with UPS in STAND-BY or BYPASS mode (powered but without
activation of ON button).
To come back to normal state, ESC (00) screen can be selected to confirm with ENTER or simply user can wait 10 seconds to allow
UPS to come back automatically.
In configuration mode, LCD displays ID of the menu and values of 2 adjustable parameters:
( 1 )
: MENU ID
( 2 )
: Function name
( 3 )
: Configurable value
KEYBOARD IN CONFIGURATION MODE:
<ON / MUTE>
Used as
key to navigate or changing parameters value
<OFF / ENTER>
Used as <
ENTER
> key to confirm modifications
<SELECT>
Used as
key to navigate or changing parameters value
CONFIGURATION MENU:
For this model, configuration menu has below options and functions:
00
ESC:
To quit from configuration mode.
01
OUTPUT VOLTAGE:
- For 220V/230V models: Operator can select between 200/208/ 220/230/240Vac.
Factory set to: 230V
- For 120V models: Operator can select between 100/110/115/120/127V.
Factory set: 120V
02
CF: ENABLE / DISABLE FREQUENCY CONVERTER FUNCTION:
CF can be enabled or disabled according to the value selected in this parameter:
ENA = Enabled
DIS = Disabled
If CF is enabled Function 03 must be set to preferred frequency value: 50Hz or 60Hz
This function allows UPS to generate output at selected frequency no matter value of
input frequency