USER MANUAL - OPTIMA RT10 1K/1.5K/2K/3K (UL)
VER.2010.22-One (ENG)
17
ERROR CODES
Error states are produced when UPS detects a critical problem that avoids its normal operation in ONLINE mode. This condition is
described by steady symbol and code on LCD. A continuous beep is also generated by the UPS.
TIPO DE FALLA
CODIGO DE FALLA
SIMBOLO
BUS START FAIL
01
BUS OVER
02
BUS UNDER
03
INVERTER SOFT START FAIL
11
INVERTER VOLTAGE HIGH
12
INVERTER VOLTAGE LOW
13
INVERTER OUTPUT SHORT
14
BATT VOLTAGE TOO HIGH
27
BATT VOLTAGE TOO LOW
28
CHARGER OUTPUT SHORT
2A
OVER TEMPERATURE
41
OUTPUT OVERLOAD
43
CHARGER FAILURE
45
OVERCURRENT AT INPUT
49
AUDIBLE ALARM BEEPS
ERROR:
Continuous Beep
BATTERY MODE:
1 "Beep" / 5s
BYPASS MODE:
1 "Beep" / 10s. This alarm cannot be muted
LOW BATTERY:
1 "Beep" / 2s. This alarm cannot be muted