2.
SAFETY & QUALITY STANDARDS
SAFETY - LOW VOLTAGE DIRECTIVE (2014/35/EU)
UPS Part 1-1: General & Safety UPS in accessible areas
IEC/EN 62040-1
ELECTROMAGNETIC COMPATIBILITY - EMC DIRECTIVE (2014/30/EU)
UPS, Part 2, Electromagnetic Compatibility:
IEC/EN 62040-2
Low Freq. Conducted Disturbances & Signals:
IEC/EN 61000-2-2
Electrostatic discharge immunity Test:
IEC/EN 61000-4-2
(Air: Level 3, Contact: Level 2)
Radiated radio Frequency immunity:
IEC/EN 61000-4-3 (Level 3)
Electrical Fast Transient / burst immunity:
IEC/EN 61000-4-4 (Level 3)
Surge immunity:
IEC/EN 61000-4-5
(L-L: Level 2, L-G: Level 3)
UPS Part 3: Methods of operation, specifications, and test requirement
IEC/EN 62040-3
IT Equipments. SAFETY. Part 1: General Requirements
IEC/EN 60950-1
IP PROTECTION
IP20 (static)
QUALITY MANAGEMENT: ISO 9001 : 2000
Manufactured under:
ISO 9001
ENVIRONMENTAL MANAGEMENT: ISO 14001 : 2004
Manufactured under:
ISO 14001
Any modification made by user or operator may affect compliance of the safety and performance certifications listed above.
UPS manufacturer is not responsible of any modification made on the product or its accessories after it is manufactured.
This product is designed to operate in domestic and commercial environment. CE standards apply for 230V models.
This is a C2 category product. In residential environment, this product may cause radio interference, in this case the user may
require taking additional measures.
3.
BATTERY MAINTENANCE
▪
Batteries capacity, in general (of all kinds), decreases with time and use.
▪
Our products contain high quality batteries only.
▪
Batteries useful life in our UPS is between 3 and 5 years, considering environment temperature under
25ºC and optimal operational conditions. This time can be dramatically reduced by high temperature and
other adverse operation condition.
▪
Batteries life expectancy may be also affected by other operation conditions such as electrical service
quality as well as number and kind of equipments connected to UPS
▪
Batteries should be periodically tested to check capacity and assure and appropriate back up.
* To enlarge batteries life expectancy, it is recommendable to fully discharge UPS once every 3 months
* During long UPS storage recharge batteries according to following table:
STORAGE TEMPERATURE
FREQUENCY
RECHARGING TIME
-25°C a +30°C
Every 4 months
4 h
+30°C a +45°C
Every 2 months
4
h