Summary of Contents for IVA 3070 X

Page 1: ...User manual IVA 3070 X IVA 3110 X ...

Page 2: ...A 3110 X sensors have Automatic Signal Gain Control AGC and a Fresnel lens which guarantee a strong and stable signal They offer efficient detection via dual pulsed infrared beams and can be powered with either a DC or AC source Read the introductory product information presented in this manual carefully for the correct use of the sensors ...

Page 3: ...of the sensor use a cloth moistened with water never use chemicals The sensor must be attached well so that the beams do not misalign over time In outdoor environments with a high rate of fog or rain install the sensors at a maximum of 50 of the distance specified for each model in order to avoid false alarms It must be kept in mind that the distance between the sensors will depend on the density ...

Page 4: ... Product 6 3 Installing the sensors 6 3 1 Wall installation 7 3 2 Pole installation 8 4 Beam alignment 9 4 1 Beam alignment display 10 5 Tests 11 5 1 Response time adjustment receiver only 11 6 Frequently asked Questions 12 Warranty term 13 ...

Page 5: ...over is removed Adjusting the optical axis 12 vertical 90 horizontal Dimensions B W D 82 175 85 mm Weight 300 g Protection rating IP54 Color Black LED indicators Receiver Level orange the brightness of the LED varies according to the incident signal level on the receiver When only the orange LED is lit the receiver will be misaligned When in addition to the orange LED the green Good LED is lit the...

Page 6: ...teristics of the panel area Longitudinal protection distance and lateral protection distance No fog With fog Model Longitudinal protection distance Side protection distance Longitudinal protection distance Side protection distance IVA 3070 X 70 m 5 m 35 m 2 5 m IVA 3110 X 110 m 8 m 55 m 4 m Note this sensor has high immunity to false triggering with fog however triggering can occur depending on th...

Page 7: ...remove the front cover 2 Mark the installation holes and drill the guide holes Side or top bottom holes can be used for wall mounting as shown in the figure below If you are going to use the top and bottom hole do not remove the rubber film it is a guarantee of sealing against water and insects use the screw itself to tear it Note M4 25 perforating screw ...

Page 8: ...s 4 Mount the sensor on the wall 5 Connect the wires to the terminal according to the figure on the terminal block 3 2 Pole installation 1 Pass the wires through the hole and then pull them out 2 Remove the cover 3 Attach the base to the support as shown in the figure below The base of this sensor has a suitable design for connection to a pole Note M4 25 perforating screw ...

Page 9: ...he jumper JP1 open the receiver with the help of a screwdriver and unlock the rear cover Hangs Hangs Back cover Wiring power ratio Note variations in the sensor power input may occur due to the internal resistance in the cable being used Always check at the sensor input if the supply voltage is between 12 24 Vdc or 11 18 Vac 4 Beam alignment 1 Position the transmitter and receiver so that they are...

Page 10: ...e alignment display Opposite sensor seen through the sight Visor de alinhamento olho direito Visor de alinhamento olho esquerdo Sensor oposto visto pela mira Mira Sight 1 Adjust the vertical angle adjustment screw figure A and the horizontal angle adjustment bracket by holding it at the top as shown in figure B In this way it will be possible to obtain greater precision in the adjustment Do this a...

Page 11: ...n 3 and 4 Vdc 5 Tests After installation confirm correct operation by testing the beam cut Block the beams with your hand or some screen and check if the receiver triggers by observing the alarm signal by the LEDs as shown in the following table Condition Indication Transmitter Broadcasting Green LED on Receiver Alignment OK Good green and Level orange LEDs on Alarm Alarm LED red on 5 1 Response t...

Page 12: ...the alarm does not go off Shorted wiring Check wiring and connection to the control panel The connection is not adequate Check wiring and connection to the control panel The alarm LED on the receiver is always on The beams are not properly aligned Adjust the beams There are barriers between the transmitter and the receiver Remove barriers The cover or optical parts are dirty Clean the optical part...

Page 13: ...by the Consumer or by third parties foreign to the manufacturer b if the damage to the product arises from accidents disasters agents of nature lightning floods landslides etc humidity voltage in the electrical network excess voltage caused by accidents or excessive fluctuations in the network installation use in disagreement with the user s manual or arising from natural wear of the parts pieces ...

Page 14: ...te tecnico Support via e mail suporte intelbras com br Customer Service 0800 7042767 Where to buy Who installs it 0800 7245115 Imported to Brazil by Intelbras S A Indústria de Telecomunicação Eletrônica Brasileira Rodovia SC 281 km 4 5 Sertão do Maruim São José SC 88122 001 CNPJ 82 901 000 0014 41 www intelbras com br ...