background image

OPERATING MANUAL and INSTALLATION INSTRUCTIONS for

 

 

 

           

          CHS for b262 

IntelliCon

®

-

CHS 

(4 - 25 PSI Operating Pressure and 25 - 145 PSI Operating Pressure versions)

 

COMMERCIAL STEAM HEATING SYSTEM ECONOMIZER 

 

 

Intellidyne, 

LLC

  • 303 Sunnyside Blvd., Suite 75  •  Plainview, NY 11803 USA  •  Phone (516) 676-0777  •  Fax (516) 676-2640

 

“RETURN” (Condensate Return Sensor) *** 

If a Heat-Timer is present or condensate return temperature indication and 
sensing is desired, plug this temperature sensor in to the ‘Return' jack 
(J3), and attach the sensor to the condensate return pipe as close to the 
boiler as possible or upstream of condensate pump (if present).  Mount the 
sensor  (as shown in fig. 2).    While this sensor is not required for proper 
operation, it does enhance the operation of the IntelliCon

®

-CHS and 

should be used if a Heat-Timer is present. 
 

***This temperature sensor is not included and must be ordered 
separately.  

 

Heat-Timer / Summer-Winter Switch 

A Dry (No Voltage) contact should be connected to the S/W SW. 
terminals. The contact should be closed for summer  operation or when 
there is a domestic water call when used with a Heat-Timer. 

 

Checkout 

Recheck the wiring one last time and make sure that all of the installed sensors 
are plugged into the proper jacks. The sensors are only detected 

during 

power-up.  Set the IntelliCon

®

 power switch to ‘OFF/BYPASS’ and restore 

power to the boiler.  Next set the switch to ‘ON’.  The display will illuminate 
and will then indicate the results of a sequence of status checks of the 
unit’s electronics.  Next, it will check to see which sensors are attached 
and indicate which; on the display.  The installer should verify that each 
sensor attached is detected by the unit.  If an installed sensor is not 
detected,  power the unit down and remove and reattach the sensor’s 
connector.  Restore power.  If the sensor is still not detected; replace the 
sensor with another.  After these tests are successfully completed, the unit 
will display one of the operating mode messages depending upon the 
pressure/temperature of the boiler at power-up.  If the IntelliCon

®

  comes 

on and goes into the ‘Standby Mode’; note the pressure-control setting 
and force a burner call by temporarily setting the control higher and 
verifying the change of mode of the IntelliCon

®

.  Make sure to return the 

pressure-control to its’ previous setting.  If the IntelliCon

®

  does not come 

out of ‘STANDBY MODE’ when the boiler’s pressure control is calling for 
the burner to run, the unit is probably miswired; see  the WIRING NOTE.  
After completion of the above checkout procedure and observation of a full 
boiler cycle, the installation is complete.

 

 

Service and Troubleshooting 

The IntelliCon

®

-CHS does not require any maintenance and will provide 

years of trouble free operation.  The unit may be disconnected at any time 
by putting the power switch to the ‘OFF/BYPASS’ position.  In this position, 
the unit has no effect on the system and the boiler is wired as it was prior 
to the IntelliCon

®

  installation.  This allows  service personnel to diagnose 

boiler problems without the IntelliCon

®

 intervening. 

 
If at any time the power indicator on the front panel blinks, a sensor fault 
has been detected.  A "FAIL" messages will be displayed, for the faulty 
sensor, on the LCD display.  If this occurs, the unit automatically 
disconnects itself and returns full control to the boiler. If a sensor fault 
message appears; call your installer for service. 

 

IMPORTANT - READ CAREFULLY 

 

1. 

Failure to follow these instructions may result in damage to the 
system or cause a hazardous condition.  

2. 

Installer must be experienced, qualified, and in certain locations, 
licensed to work on the system that this control is being installed 
on.   

3. 

After installation is complete, follow the check-out procedure as 
provided in these instructions to confirm proper system 
operation. 

4. 

Intellidyne is not responsible for improper installation or any 
damages that may result from improper installation.  

5. 

Actual wiring may differ from that shown in the diagrams. 

6. 

Equipment may have controls not shown. 

7. 

Because the IntelliCon  can operate with different voltages for the 
power and control circuits, it has separate common wires for these 
circuits.  It is necessary that these wires are connected to the proper 
commons or the unit will not function properly.  See the wiring 
diagrams on the reverse side of this sheet for details.
 

8. 

For CE compliance, all wiring and sensor leads must be installed in 
grounded metallic conduit. 

 
IMPROPER VOLTAGE SELECTION MAY DAMAGE THE UNIT AND VOID 
THE WARRANTY. 

PROGRAMMING 

The following parameters may be changed in the field by following these 
instructions. 

Pre-Purge time, Temperature indication in either degrees F or C, 
Steam Intedation in either PSI or KPa, Steam Pressure Low-Limit, 
Domestic Water Low-Limit, Return Water Low-Limit, Return Water 
Differential, Maximum Economizer Hold-Off Time, Standby-Timer 
Override, and whether or not the Economizer Time and/or Burner 
Run-Time Hour accumulators are Displayed. 

 The system may also be 

returned to factory default values and the Economizer Time, and Run-
Time accumulators may be cleared. 
 

All of the default values have been carefully selected to result in the 
greatest savings for the broadest scope of heating system 
applications.  Individual system requirements may require changes.  
Please note that all of these programmable parameters will affect the 
amount of savings.  Prudent changes are strongly advised. 
 
It is very important that if there is any kind of a delay  (more than 
fifteen (15) seconds), from the time that the Operating-control calls 
for the burner to start and the burner actually starts, that this time 
delay value be entered into the controller as a Pre-Purge time (e.g. 
actual pre-purge timer, Flue Damper interlock, etc.). If there is a delay 
and the correct value is not programmed into the controller, the 
savings calculations will be incorrect. 
 
ALL PROGRAMMING IS ACHIEVED BY USING THE FOUR (4) 
SWITCHES LOCATED IN THE WIRING COMPARTMENT ABOVE THE 
SENSOR CONNECTOR JACKS 
 
PROGRAMMING MAY BE STOPPED OR ABORTED AT ANY TIME BY 
BACKING OUT OF THE MENU STRUCTURE OR BY TURNING THE 
CONTROLLER OFF.  ANY PARAMETERS THAT WERE CHANGED 
WILL REMAIN CHANGED. 

 

Entering Configuration Mode: 

To enter configuration mode, both the +/menu and -/menu pushbuttons 
must be depressed simultaneously when the “Line Frequency = ??Hz” 
screen is displayed.  Pressing the buttons before or after this screen will 
result in the unit NOT going into the configuration mode.  Navigating the 
menus, changing parameters, and confirmations are all done using the 
appropriate pushbutton.  Follow the on-screen instructions for switch 
usage. 

 

Changes made will be confirmed by indicating “**DATA SAVED**”. 
 
After making a change and the “**DATA SAVED**” message is 
displayed, you can move forward or backward in the menu structure 
to make any additional changes before exiting Configuration Mode. 

 

RESET TO DEFAULTS?

 -- This parameter will reset all of the 

programmable parameters to factory defaults. It will not clear any of the 
accumulators. 

 

RESET RUN-TIME?

 -- This parameter will clear the Run-Time 

accumulator.  

(Note: This value is accumulated even if not being displayed.) 

 

RESET ECONO-TIME?

 -- This parameter will clear the Economizer Time 

accumulator.  

(Note: This value is accumulated even if not being displayed.) 
 

TEMP READING IN ˚F or ˚C

 -- The controller will indicate whatever value 

is currently selected (default value = F).  Using the pushbuttons, select the 
desired setting and then press the enter pushbutton twice to accept the 
change.  This setting will alter the displayed values of the LOLIM 
programmable parameters, and how the temperatures are displayed when 
the controller is in normal operation. 
 

STEAM READING IN PSI or KPa

 -- The controller will indicate whatever 

value is  currently selected (default value = PSI).  Using the pushbuttons, 

Reviews: