OPERATING MANUAL and INSTALLATION INSTRUCTIONS for

 

 

 

           

          CHS for b262 

IntelliCon

®

-

CHS 

(4 - 25 PSI Operating Pressure and 25 - 145 PSI Operating Pressure versions)

 

COMMERCIAL STEAM HEATING SYSTEM ECONOMIZER 

 

 

Intellidyne, 

LLC

  • 303 Sunnyside Blvd., Suite 75  •  Plainview, NY 11803 USA  •  Phone (516) 676-0777  •  Fax (516) 676-2640

 

select the desired setting and then press the enter pushbutton twice to 
accept the change.  This setting will alter the displayed value of the Steam 
Pressure LOLIM programmable parameter, and how the steam pressure is 
displayed when the controller is in normal operation. 
  

P RANGE = 0-25 PSI (0–172 KPa) OR 0-145 PSI (0–1000 KPa)

 –  

The controller will indicate whatever value is currently selected (default 
value = 0- 25 PSI).  Using the pushbuttons, select the desired setting and 
then press the enter pushbutton twice to accept the change.  Changing 
this setting will erase any changes that may have been made to the Steam 
Pressure LOLIM, and will reset the Steam Pressure LOLIM to the default 
values for that range. 
 

S/W SWITCH = NORMAL or REVERSE

 – This parameter allows 

the direction of operation of S/W SW (summer/winter switch) to 
be reversed.  In NORMAL mode, a contact closure of the S/W SW 
terminals would put the unit in to Summer Mode.  In Summer 
Mode the Steam Pressure is ignored and the controller only 
responds to Domestic Water Temperature changes.  In the 
REVERSE mode a contact opening would have the same effect. 
 

ET DISPLAY = ON/OFF?

 -- This parameter controls whether or not the 

Economizer Time accumulator is displayed. Using the pushbuttons, select 
the desired setting and then press the enter pushbutton twice to accept 
the change.    Note – the accumulator is active even if not displayed.

 

 

 

R T   D I S P L AY   =   O N / O F F ?

  - -   This parameter controls whether or not 

the Burner Run-Time accumulator is displayed. Using the pushbuttons, 
select the desired setting and then press the enter pushbutton twice to 
accept the change.  Note – the accumulator is active even if not displayed. 
 

S T E AM   L O L I M   =   x x x   P S I   o r   K P a

  - -   This parameter is used by 

the controller to set the low limit below which the controller will no longer 
attempt to achieve any savings and will return control to the operating-
control.  The indicated value will be what is currently set in the controller.  
The default values are 2 PSI (14 KPa) for the low pressure unit,  and 22 
PSI (155 KPa) for the high pressure unit. The +/Menu and -/Menu 
pushbuttons will allow the setting to be changed between the minimum 1 
PSI (7 KPa) to a maximum of 10 PSI (70 KPa) for a low pressure unit and 
a minimum of 12 PSI (84 KPa) to a maximum of 32 PSI (224 KPa) for a 
high pressure unit. If the steam pressure goes below this value while the 
operating-control is calling for the burner to run, the controller will indicate 
“HEATING/LOLIM” on the display. 

 

 

D O M E S T I C  

LOLIM = xxx ˚F(C)

  - -   This parameter is used by the 

controller to set the low-limit temperature for the domestic hot water. When 
the domestic water temperature goes below this setting, the controller will 
no longer attempt to achieve any savings and will return control to the 
operating-control.  The indicated value will be what is currently set in the 
contro

ller (default = 115˚F / 46˚C). The +/Menu and -/Menu pushbuttons 

will allow the setting to be changed between the maximum (180

˚F/82˚C) 

and minimum 

(90˚F/32˚C) settings. If the ‘Domestic’ water temperature 

goes below this value while the operating-control is calling for the burner to 
run, , the controller will release the burner to run, and  will indicate 
“HEATING/LOLIM” on the display.

 

 

R E T U R N   L O L I M   =   x x x  

˚F(C)

  - -   This parameter is used by the 

controller to set the low-limit temperature for the condensate return. When 
the condensate temperature goes below this setting, the controller will no 
longer attempt to achieve any savings and will return control to the 
operating-control.  The indicated value will be what is currently set in the 
contro

ller (default = 90˚F / 32˚C). The +/Menu and -/Menu pushbuttons will 

allow the setting to be changed between the maximum (180

˚F/82˚C) and 

minimum (70

˚F/21˚C) settings.   If the ‘Condensate’ temperature goes 

below this value while in Winter Mode, and the operating-control is calling 
for the burner to run, the controller will release the burner to run, and 
indicate “HEATING/LOLIM” on the display. 
 

R E T U R N   D I F F   =  

xx ˚F(C)

  - -   This parameter is used by the 

controller to set the point at which the burner will be allowed to run when in 
Winter Mode. In Winter Mode, the burner will be inhibited from firing as 
long as there is energy in the condensate. When the condensate 
temperature goes below this setting, the controller will no longer attempt to 

achieve any savings and will return control to the operating-control.  The 
indicated value will be what is currently set in the controller (default = 10

˚F 

~ 6˚C). The +/Menu and -/Menu pushbuttons will allow the setting to be 
changed between the maximum (25

˚F/18˚C) and minimum (5˚F/3˚C) 

settings.   If the ‘Condensate’ temperature goes below this value while in 
Winter Mode, and the operating-control is calling for the burner to run, the 
controller will release the burner to run, and indicate “HEATING” on the 
display. 
 

PREPURGE = xxx SEC

 -- This parameter indicates the pre-purge time 

currently programmed into the controller (default value = 000 seconds).  
The +/Menu and -/Menu pushbuttons will allow the setting to be changed 
between the maximum (240 Secs.) and minimum (000 Secs.) settings.  
This setting is important for proper run-time hours accumulation. 
 

MAX ECON = xxx MIN

 -- This feature of the controller is to limit the 

maximum amount of time that the controller is allowed to remain in the 
Economizer Mode.  The indicated value will be what is currently set in the 
controller (default = 30 minutes). The +/Menu and -/Menu pushbuttons will 
allow the setting to be changed between “Disabled” or the maximum (120 
Mins.) and minimum (5 Mins.) settings. If the controller goes in to the 
“HEATING MODE” as a result of this feature, there will be a period (“.”) 
appended to the word “MODE” on the display. 
 
 

MAX STBY = xxx MIN

 -- This feature of the controller is to limit the 

maximum amount of time that the controller is allowed to remain in the 
Standby Mode as a means of monitoring the internal electronics against 
failure. If a heating call is not sensed within the prescribed time period, the 
timer will expire and the control will take itself out of the circuit (fail-safe).  
A period (“.”) will be appended to the “

STANDBY MODE.

” message to 

indicate that this timer has expired for service personnel.  It will only reset 
upon sensing a call from the aquastat. Cycling power to the control will 
NOT reset the timer.  
 
The indicated value will be what is currently set in the controller (default = 
180 mins). The +/Menu and -/Menu pushbuttons will allow the setting to be 
changed between “Disabled” or the maximum (180 Mins.) and minimum 
(45 Mins.) settings.  

DISABLING THIS FUNCTION IS NOT RECOMMENDED!

 

 
This condition is not necessarily a fault and will occur naturally if the 
heating system has been “off” or there are long periods of time between 
aquastat heating calls.  The only time that this should be considered a 
problem is if the controller is in “STANDBY MODE.” and the burner is 
running.  This would indicate a failure of the on-board electronics and that 
the IntelliCon has taken itself out of the circuit.  

 

 
 
FOLLOW THE SCREEN INSTRUCTIONS TO EXIT THE 
CONFIGURATION MODE AND REBOOT THE CONTROL. 