System Overview 

 

 

Installation Procedures 

 

 
 

 

COMPONENT DESCRIPTION

 

The 950P Portable DFS Air Cleaning System integrates the system components into a single, portable unit: 
the Prefilter, V-Bank Main Filter and the High Energy Grid are accessible from the back service door. The unit 
is also remotely controllable by using a remote control. The fan inlet screen is located on the bottom side of 
the unit and provides protection from loose items being drawn into the fan and thus damaging the unit    and 
the internal  components.

 

Electrical controls are located on the front of the unit. It consists of the Main Power ON-OFF switch with a 
Blue LED to indicate HVPS power status, Blower Speed Status and Blower Speed Control Switch.

 

 
 

 

Replacement Filters

 

Efficiency

 

Replacement Period*

 

Prefilter

 

MERV-8 (30% Efficiency)

 

1-2 times per year

 

 

VOC Post Filter

 

Formaldehyde > 99%

 

Benzine > 99%

 

Toluene > 99%

 

1/2” Filter: 2 times per year

 

Optional V-Bank: once a year

 

DFS V-Bank 

Main Filter

 

99.99% Efficient 

(down to .007 microns)

 

once a year

 

 

*Replacement period depends on the level of pollution in the environment

 

 

POWER  REQUIREMENT

 

The power requirements are as follows:

 

*Electrical disconnects may also be required - check local electrical codes

 

 

Model

 

Power

 

FLA

 

Power Usage 

Max Start-up

 

V

 

Hz

 

Phase

 

AMPS

 

WATTS

 

950P

 

120

 

50/60

 

1

 

       4.44

 

590

 

950P

 

220

 

50/60

 

1

 

2.21

 

560

 

 
 
 

 

LOCATION DETERMINATION

 

The 950P is designed as a portable floor model. Place the air purifier anywhere in the room; being careful 
not to block air from “entering” the intake grill, or “exiting” the top grill cover.

 

Do not place the air purifier where drapes or other objects block airflow.

 

For best performance, it is recommended to place the air purifier at least two (2) feet from walls and 
other obstructions.

 

Place the unit on a flat and level surface to allow continuous airflow to the bottom intake and out the top 
outlet grill.

 

Do not run power cord under carpeting or near heaters, registers, radiators, stoves or fireplaces. To avoid a 
tripping hazard, keep the power cord away from traffic areas.

 

Never operate the air purifier in areas where combustible gases or vapors are present or any other 
flammable materials.

 

 
 

 

                                                                                                                                                                                                                                                  

 

 
 

 

 

 

 

Do not operate unit using an extension cord.

 

 

 

The filter unit will not turn on without the Prefilter installed and firmly seated.

 

Summary of Contents for 950P

Page 1: ...Installation Manual 950P PORTABLE AIR CLEANING SYSTEM 2015 10065 ...

Page 2: ...4 2 2amp FEATURES High Air Flow Capacity delivers high CFM with low energy consumption Wattage MobileDesign builtin3 5 safetylockswivelcasters fullwidth handle for easy movement Multiple Fan Speeds four fan speeds for ease of control 99 99 DFSFiltration Efficiency downtoasizeof0 007microns IndependentAirflow DistributionControl tofacilitate placement anywhere in the space Patented V Bank Filter in...

Page 3: ... or disassembly by unauthorized personnel 5 defacing the serial number or 6 modifying the original factory assembled unit in any way B THIS LIMITED WARRANTY DOES NOT APPLY TO SHIPPING CHARGES FOR PRODUCT SHIPPED TO OR FROMTHEFACTORYORDESIGNATEDSERVICECENTERINCONNECTIONWITHWARRANTYCLAIMSNOR DOES IT APPLY TO ANY DAMAGES OCCURRING DURING SUCH SHIPMENT C This Limited Warranty does not apply to labor f...

Page 4: ...the filtration system This manual contains general recommendations but specific requirements may apply to individual installations Such requirements are outlined in federal state and local codes Compliance with applicable codes and strict adherence to these installation instructions are the sole responsibility of the user This symbol will be used throughout this manual to indicate safety checkpoin...

Page 5: ... Unit Description 11 Component Description 12 Installation Procedures 13 Power Requirements 13 Location Determination 13 System Operation 15 Electrical Connection 15 To Turn On the Unit 15 To Turn Off the Unit 15 Maintenance 17 Prefilter Replacement 17 VOC Post Filter Replacement 17 V Bank Main Filter Replacement 18 Cleaning the Unit 19 Parts List 20 Troubleshooting 21 DFS Troubleshooting Guide 22...

Page 6: ...ier accepts the responsibility for any subsequent shortages or damage evident or concealed Inspection by the carrier of damage evident or concealed must be requested Evident shortage or damage should be noted on the carrier s delivery document before signature of acceptance Claims must be made against the carrier by the purchaser Filtration systems are shipped as fully assembled filter units STORA...

Page 7: ...efilter is not installed correctly fig G Return the Filter Access Door Lift the latch wings 4 and turn clockwise to close fig H UNIT DESCRIPTION The 950PAir Cleaning System is a high performance system that utilizes patented award winning Disinfecting Filtration System technology DFS technology electrically enhances a low efficiency high flow low pressure drop filter to high efficiency while retai...

Page 8: ...own to 007 microns once a year Replacement period depends on the level of pollution in the environment POWER REQUIREMENT The power requirements are as follows Electrical disconnects may also be required check local electrical codes Model Power FLA Power Usage Max Start up V Hz Phase AMPS WATTS 950P 120 50 60 1 4 44 590 950P 220 50 60 1 2 21 560 LOCATION DETERMINATION The 950P is designed as a port...

Page 9: ...unction should also come on fig I TO TURN OFF THE UNIT To turn off the unit simply turn off the main switch located on the front of the unit Do not connect power to the unit until the High Energy Grid wires have been checked for proper connection Refer to page 10 fig I LO TURBO 950P REMOTE Each unit is also equipped with a Remote Control fig J The Remote has 3 buttons fig J ON SPEED Turns the unit...

Page 10: ...lter is not installed correctly Return the Filter Access Door Lift the latch wings 4 and turn clockwise to close fig 2 VOC POST FILTER REPLACEMENT Lock the 2 front wheels to secure the unit fig 1 Remove the Filter Access Door located in the back of the unit using the four butterfly latches located on the sides of the unit Lift the latch wings 4 and turn counter clockwise to open fig 2 Filter Acces...

Page 11: ...ending on contamination level this procedure should be conducted about once a year or during each filter change or if an electrical problem occurs Remove the V Bank Main Filter and High Energy Grid Assembly Refer to page 18 for proper instructions To clean the wires use a fiber free swab either dry or moistened with distilled or deionized water clean along the length of each wire spring clip and c...

Page 12: ...the status of the fuses 2 If problem persists then check for disconnected wires or connectors inside the unit including all low voltage control connections 3 If the problem persists then call for assistance Blue LED FS is OFF Fan is not running 1 Check whether the unit is running on the required supply voltage and confirm the status of the fuses 2 If the problem persists check the prefilter and pr...

Page 13: ...Bank Main Filter and ensure that it is free of metal debris excess dirt or hair etc G Secure the V Bank Main Filter to the High Energy Grid by using the six screws 4 corners and 2 in the center in the V Bank Main Filter H Stand the V Bank Main Filter and High Energy Grid Assembly up and inspect the gasket on the seal side of the Assembly Replace the gasket if it is damaged DFS TROUBLESHOOTING GUID...