background image

 

© 2018 UTC Fire & Security Americas Corporation, Inc. All rights reserved.                         1 / 10                  P/N 466-1452 • REV E • ISS 16OCT18 

 

Quik Bridge International Loop Receiver 
Installation Sheet 

Introduction 

The Quik Bridge International Loop Receiver (see Figure 1) 
allows you to use up to 16 learn mode wireless sensors (two 
per zone) with any standard hardwire control panel. In 
addition, you can use up to 45 keychain touchpads and panic 
button transmitters, for a total of 61 wireless transmitters. 

Figure 1: Quik Bridge International Loop Receiver 

The receiver monitors the alarm, battery, tamper, and 

supervisory status of transmitters learned into the receiver’s 
eight zones. 

The receiver features the following: 

• 

Spatial-diversity receiver enhances reception. 

• 

Eight programmable zone outputs (N/C or N/O). 

• 

Selectable zone supervision (programmable). 

• 

RF (radio signal) jam detection on zone 7 (optional). 

• 

Sensor tamper output summary and receiver 
cover/antenna tamper on zone 8 (optional). 

• 

Two yellow trouble LEDs indicate sensor low battery and 
supervisory conditions. 

• 

Support for a piezo (used for RF testing only) that 
sounds the number of transmissions received from 
learned transmitters. 

• 

On-board EPROM stores sensor IDs and programming 
information in nonvolatile memory, if power is removed. 

• 

Selectable 1- or 4-hour RF supervisory. 

Transmitter compatibility 

The receiver is compatible with all current Learn Mode 
sensors (433.92 MHz), panic button transmitters, two- and 
four-button keychain touchpads, with the exception of smoke 
detectors. 

Control panel compatibility 

The receiver is compatible with control panels designed with 
hardwire loops where the loop negative is ground (common-
loop ground).

 

The receiver is not directly compatible with powered loops 
(two-wire smoke detector loops and glassbreak detector 
loops). If the loop on the control panel can power a device, it 
must not be connected directly to the loop receiver. Instead, 
a relay is required when connecting to powered loops. 

Compatibility testing 

Typically, hardwire loops have the negative (-) side of the 
loop common with ground. If this is true, and the loop is 
nonpowered, the loop should be compatible with the 
receiver.

 

Although most control panels are compatible with the 
receiver open collector outputs, each loop should be tested 
for compatibility before connecting receiver outputs to the 
control panel loop outputs. If the receiver is not directly 
compatible with a control panel loop, you can use a relay to 
establish compatibility. 

To check if the negative side of the loop is common to control 
panel ground, do the following: 

1.  Turn off or remove control panel power and disconnect 

the back-up battery. 

2.  Use an ohmmeter and measure the resistance between 

the negative side of the loop and panel ground. If the 
resistance is zero or close to zero, this loop should be 
compatible with the loop receiver. If the resistance is not 
zero, a relay is required for this loop. 

Test the compatibility for all loops that you are going to 
connect to the receiver. 

 

Summary of Contents for 60-660-43

Page 1: ...2 MHz panic button transmitters two and four button keychain touchpads with the exception of smoke detectors Control panel compatibility The receiver is compatible with control panels designed with hardwire loops where the loop negative is ground common loop ground The receiver is not directly compatible with powered loops two wire smoke detector loops and glassbreak detector loops If the loop on ...

Page 2: ...nsistors for the zone and trouble outputs see Figure 2 The outputs can be open high impedance or closed shorted to ground which can be configured to be normally closed N C or normally open N O Each output can be wired to the control panel Zone outputs There are eight zone outputs labeled 1 through 8 When a learned transmitter is activated the corresponding zone output switches to the alarm state a...

Page 3: ...Receiver failed power up test Blinks off momentarily Receiver received an RF signal whether learned or not Run mode LED indications In run mode the LEDs indicate three conditions alarm low battery and supervisory failure Alarm status conditions When the trouble LEDs are both off the zone LEDs indicate alarm information The zone LEDs turn on for zones that are open in alarm Zone LEDs remain off for...

Page 4: ... receiver do the following 1 To remove the receiver cover press down on the top center of the cover see Figure 6 and pull the cover away from the base Figure 6 Remove the cover Caution You must be free of static electricity before handling circuit boards Touch a bare metal surface or wear a grounding strap before handling circuit boards 2 Press the lower right corner of the base until the lower ri...

Page 5: ... When learned into zone 2 both of these key presses work together to provide a maintained toggle output response only one of these buttons needs to be learned for both to work Typically this output would be used for a maintained keyswitch on the control panel for arming disarming refer to your control panel documentation for this application Zone 3 lights You can only learn this keypress into zone...

Page 6: ...de the DIP switch up The low battery and supervisory LEDs blink back and forth 2 Press and release the ADV switch until the desired zone LED turn on If you press and hold the ADV switch you will advance to the next zone and cause the zone LED to flicker 3 Press and release the SEL switch once to select this zone for learning transmitters The zone LED remains on and the low battery and supervisory ...

Page 7: ...sion on a zone do the following 1 To enter program mode slide the DIP switch up 2 Press the tamper switch twice to gain access to configuring zone supervision 3 Press and release the ADV switch until the desired zone LED turns on 4 Press and release the SEL switch to change the RF supervision configuration to the desired setting 5 Repeat the procedure for each zone configuration change 6 Slide the...

Page 8: ... responses Transmitter Should cause Sensors 7 to 8 beeps and LED flashes Keypad touchpads 1 button press 2 beeps and LED flashes 2 button press 8 beeps and LED flashes To test the system using a piezo beeper do the following 1 Connect a piezo beeper between the test output T and ground GND as shown in Figure 13 Piezo status beeper connections Figure 13 Piezo status beeper connections 2 Make sure t...

Page 9: ...nformation on warranty disclaimers and product safety information please check https firesecurityproducts com policy product warning or scan the QR code Certification TUV 0123 Test report reference CEQP 60 660 43 Applied standards EN50130 4 1995 A2 2003 Safety Test report reference CEQP 60 660 43 Applied standards EN 60950 1 2001 Radio TUV 0123 Test report reference CEQP 60 660 43 Applied standard...

Page 10: ...10 10 P N 466 1452 REV E ISS 16OCT18 ...

Reviews: