DESCRIPTION:

The IOS-PP24 Power Pack supplies low voltage lighting control system. The power pack supplies low

voltage power to occupancy sensors and other control devices, switching line voltage in response to 

signals from control devices. 

INSTALLATION GUIDELINES

Follow these guidelines before beginning installation of the power pack:

•  Install power packs in accordance with state, local, and national electrical codes and requirements

•  Power packs attach to existing or new electrical enclosures with ½ inch knockouts.

•  Most applications require UL listed, 18-22 AWG, 3 conductor, Class 2 cable for low voltage wiring. 

  For plenum return ceilings, use UL listed plenum approved cables

•  The IOS-PP24 is a Class 2 Output Power Supply, suitable for parallel interconnection of up to 6 units 

 maximum. 

•  The power pack is UL listed for interconnection of power sources in accordance with National

  Electrical Code

MOUNTING THE POWER PACK

NOTE: After the wire connections are made, verify the wire installation was completed properly. 

Improper wiring can cause damage to the power pack, lighting system, occupancy sensor, and other 

control devices. 

NOTE: A customer-supplied junction box is needed to complete this procedure. 

1.  Make sure power is turned off at the circuit breaker. 

2.  Punch loose a knockout on the customer-supplied junction box. 

3.  Insert the power pack nipple into the opening in the junction box knockout. 

4.  Connect the power pack input wires as shown in Figure 2. 

  NOTE: The occupancy sensor contains four +12 to 24 VDC input wires to control the load relay. The

  inputs may be used in combination or individually depending on the needs of the application. See

  the table below for a description of the inputs. 

 

 

Input (wire) 

Description

 

Control ON (Blue wire) 

Occupancy sensor input. Applying 12 to 24 VDC

 

 

closes the relay.

 

Hold ON (Orange) 

Time or panel input. Applying 12 to 24 VDC closes

 

 

the relay.

 

 

Hold Off (Brown) 

Timer, panel, BAS, or load shed input. Applying

 

 

12-24 VEDIC opens the replay.

 

Manual ON/OFF (Gray) 

Low voltage momentary switch, if applicable.

5.  Refer to Figure 2 to verify the power pack is wired correctly.

OPERATION

The occupancy sensor enables the load to be automatically turned ON/OFF with an occupancy sensor

input, timer, panel, or BAS input. The load can also be manually turned off from an optional low voltage 

momentary switch.

OVERRIDING THE POWER PACK WITH MOMENTARY SWITCH (OPTIONAL)

The Power Pack can be overridden from the connected momentary switch. The momentary switch

can override the Power Pack when it is in the Control ON, Hold ON, and Hold OFF states.

OVER CURRENT PROTECTION

The IOS-PP24 Power Pack contains built-in short circuit and thermal protection circuitry that shuts

down the +24 VDC output (low voltage red wire) when the output exceeds 200MA to prevent permanent 

damage to the power pack. Removing the excess load from the output restores the occupancy sensor to 

proper operation.

12-24 Volt

Power Pack    

MODEL: IOS-PP24

Specifications:

Input Voltage: 120/230/240/277 VAC 50/60 Hz

Load Requirements

Ballast - 20 A @ 120/240/277 VAC

Electronic Ballast/LED: 500 W

Tungsten/Incandescent: 15 A, 120 VAC 50/60 Hz, 5 A, 250 VAC 50/60 Hz

Motor: 1 HP 120/240 VAC 50/60 Hz

Output - 150mA @ 24 VDC Class 2 Power Supply (with relay connected)

Low Voltage Input

Control ON - 12-24 VDC

Hold ON - 12-24 VDC

Hold OFF - 12-24 VDC

Manual ON (momentary switch required) - 12-24 VDC

Figure 3

Figure 2

Figure 4

IOS-PP24

+24VDC

Common

Control

Red

White

Neut.

Power Pack

Blue

Black

Red

Lighting

Load

277VAC

120VAC Black

+12-24VDC In

Hold Off

+12-24VDC In

Hold On

Any 3-Wire

24VDC

Sensor 

Hot

Red

Orange

Brown

Dry Contact

Low Voltage Wires

Momentary Switch (optional)

Gray

Low Voltage

Momentary

Switch Option

Wiring

2-wire Push Button

Gray

Manual ON

Red

24VDC

3-wire Push Button

Gray

Manual ON

Red

24VDC

Gray

Manual ON

Red

24VDC

Install

Jumper

Wire

S(x)

Com

Multi-button Switch

Do not use pilot or locator

light connections

Risk of Fire, Electrical Shock or Personal Injury

 

•  Turn OFF power at circuit breaker or fuse and test that the power is OFF before wiring.

  •  To be installed and/or used in accordance with appropriate electrical codes and regulations.

  •  If you are not sure about any part of these instructions, consult a qualified electrician.

  •  Use this device only with copper or copper clad wire. 

 • 

INDOOR USE ONLY

WARNING

Low

 Voltage

High

 Voltage

Figure 1

Neutral

Hot

White/Neutral

Wht

Blk

IOS-PP24 

Power

Pack

Red
Red

RD BK BL OR GN GY

Occupancy

Sensor

IOS-CMP-LV

Occupancy

Sensor

IOS-CMP-LV

Occupancy

Sensor

IOS-CMP-LV

Cap

Cap

Notes:

1. Relay shall be assigned to 

a Schedule to keep Motion

Sensors from turning lights

off during "Occupied" hours.

Relay on "Holds" lights on.

Relay off allows full Sensor

control of the lights.

2. IOS-PP24 Power Packs  

have150ma 24VDC 

available for Motion Sensors.

Power Pack hold on with Relay

Located in

Relay Panel

RELAY 1

Red +24VDC

om ("Hold On" Power)

Control 

Output

Common

+24VDC

Only the wires used in

this application are shown.

Control

Output

Common

+24VDC

Control

Output

Common

+24VDC

( Lights are held on during day by Scheduled Relay )

Sensor as

Needed 2

To other motion

Load

2

INSTALLATION AND CONFIGURATION INSTRUCTIONS