HID Wall Pack - WL Series

INSTALLATION INSTRUCTIONS

Model: WL150MH, WL175MH, 

WL150MHT & WL175MHT

FOR OUTDOOR USE ONLY

NOT FOR USE IN HAZARDOUS 

ATMOSPHERES

IMPORTANT: Read instruction sheet 

carefully before installing fixture. Retain 

instructions for future reference.

7.283in.

(185mm)

14.173in.

(360mm)

9.055in.

(230mm)

ELECTRICAL REQUIREMENTS

A qualified electrician should complete all required wiring. Models WL150MH & WL175MH will accept 120, 208, 240 or 277 
Volts AC. Models WL150MHT & WL175MHT will accept 120, 277 or 347 Volts AC. Fixtures must be properly grounded for 
safety. A mounting suitable for outdoor use and rated for wet locations is required. Follow all applicable electrical codes 
and regulations.

Please see below for list of warnings.

 

 

WARNING 

  Electric shock hazard

Disconnect power at circuit breaker or fuse box before 
installing or servicing light. 

 

 

WARNING 

  Fire hazard

USE MIN 90°C SUPPLY CONDUCTORS. CONNECT TO 
SUPPLY IN EXTERNAL JUNCTION BOX ONLY. 
Lamp and housing become very hot during use. Ensure 
free air circulation around unit to dissipate heat. Avoid 
enclosed locations and locations where flammable debris 
(leaves, cut grass, etc.) might collect. Avoid locations 
where humans or animals might accidentally touch fixture.

 

 

WARNING 

  Fire hazard

CONNECTIONS MADE INSIDE FIXTURE MUST USE 
WIRING RATED MINIMUM 125°

 

 

WARNING 

  Explosion hazard

Never operate light without securing the lens door. When 
light is operating, the gas in the lamp inner arc tube is at 
high pressure. Never operate light if the fixture lens or 
outer glass envelope of the lamp is broken or missing.

 

 

WARNING 

  Explosion hazard

Wear safety glasses and gloves when handling lamp.
Metal Halide outer envelope is pressurized and could 
explode if broken.

 

 

WARNING 

   UV hazard 

(Metal Halide Lamps Only)

The type of lamp used in this fixture can cause serious 
skin burn and eye inflammation from short wave ultra 
violet radiation if outer envelope of the lamp is broken or 
punctured, and the arc tube continues to operate. Do not 
use where people will remain for more than a few minutes. 
Certain types of lamps that will automatically extinguish 
when the outer envelope is broken or punctured are 
commercially available.

 

 

WARNING

Lamp Types: 

Metal Halide 150 Watt & 175 Watt
Metal Halide 150 Watt & 175 Watt with Tri-Tap

MOUNTING & WIRING

Loosen (2) screws, open, and remove fixture lens cover. Set 
lens  cover  aside  to  prevent  damage  while  installing.  (See 
Figure 2)
Loosen (4) screws and remove reflector.
Identify supply voltage.
Select  appropriate  fixture  wire  to  match  incoming  voltage. 
Models WL150MH & WL175MH are shipped with 277 V wire 
ready  for  connection.  Models  WL150MHT  &  WL175MHT 
are shipped with 347 V wire ready for connection. If supply 
voltage is lower, cap wire marked 277 V (or 347 V for tri-tap 
models)  with  appropriate  twist  on  wire  connector  and  strip 
fixture  wire  marked  with  matching  voltage.  (See  Figure  3 
through Figure 6)

1.

2.
3.
4.