27
440 01 1051 02
Specifications are subject to change without notice.
IN
ON
OFF
VE
NT
AIR FLOW
Coupling & Clamps
(Optional)
Drain Tube Corrugated,
5
/
8
ID & Clamps
Cut at straight section
Figure 19
Horizontal Right
−
Side Vent
25
−
24
−
84c
Single Pressure Switch Detail
Dual Pressure Switch
Tee Trap
White PVC
(loose parts bag)
EXHAUS
T
Alternate
Orientation
Field
Supplied Tee
Cut Here
Leave room for clamp
Plastic Cap
Yellow or black
Vent Drain
& Clamps
Level or Sloped
towards Tee
INLET
On Some Models
ONLY
Elbow Tube
Black Rubber
1
/
2
(12.7mm) ID & Clamps
(Loose Parts Bag)
Representative drawing only, some models may vary in appearance.
Flexible Tubing Connector
3
/
16
(4.8mm) OD (Loose
Parts Bag)
Relief Tube Black Rub
ber
3
/
16
(4.8mm) ID
Relief Tube Extension
Black Rubber
3
/
16
(4.8mm) ID
Cut to Fit (Loose Parts Bag)
Drain Tube Black
Rubber
1
/
2
(12.7mm) ID &
Clamps
Barbed Coupling
1
/
2
(12.7mm)
OD (Loose Parts Bag)
Horizontal Right Side Vent
(See Figure 19)
Disconnect drain tee if installed
Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using
cover plate and gasket provided in the loose parts bag, cover the
hole from the burner compartment to the blower compartment and
secure with screws.
Remove knockout from the side of the furnace casing where drain
tube will exit.
Mount the trap externally to the bottom side of the unit using the
two screws provided in the location shown.
Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap.
Secure connections with clamps.
Connect the black
1
/
2
″
(12.7mm) ID drain tube from the Vent Drain
to the trap. If an extension is required, use the
1
/
2
″
(12.7mm) OD
barbed coupling and the black
1
/
2
″
(12.7mm) ID drain tube in the
loose parts bag. Cut tube to length. Secure connections with
clamps.
Connect the
3
/
16
″
(4.8mm) ID relief tube to the middle port on the
trap. If an extension is required, use the clear
3
/
16
″
(4.8mm) OD
splice connector and the black
3
/
16
″
(4.8mm) ID relief tube in the
loose parts bag. Cut tube to length.
Cut an appropriate length of 2
″
(50.8mm) PVC pipe, fittings and
extension pipe long enough to exit the cabinet and connect the
vent drain to either:
•
A standard field supplied 2
″
(50.8mm) PVC tee, or
•
A 2
″
(50.8mm) PVC coupling fastened onto the drain tee.
Install tee trap into bottom section of tee.
Important: The pipe to the tee trap must be level or sloping towards
the tee trap.
Connect the tee trap and the main drain line exiting the casing as
shown in
Figure 20
.
Note:
It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing.
Both
the external trap and the external tee trap must be primed
before operation.
Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may
be installed as shown for future servicing of the vent system.