background image

14

START

UP

System Checks

1. Conceal the tubing where possible.
2. Make sure that the drainage tube slopes downward along

its entire length.

3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall.
5. Seal the hole through which the cables and tubing pass.
6. Connect the air conditioner to the power source and turn it

on.

7. Check all air conditioner operating modes. Refer to Own-

er’s Manual for operating details.

INDOOR UNIT

1. Do all the remote controller buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drainage work?

OUTDOOR UNIT

1. Are there unusual noises or vibrations during operation?
2. Is noise, drain water or airflow from the unit likely to dis-

turb the neighbors?

3. Are there any gas leaks?

EXPLAIN THE FOLLOWING ITEMS TO THE CUSTOMER,
WITH THE AID OF THE OWNER’S MANUAL:

1. How to turn the air conditioner on and off; selecting cool-

ing, heating and other operating modes; setting a desired

temperature; setting the timer to automatically start and

stop air conditioner operation; and the other features of the

remote controller and display panel.

2. How to remove and clean the air filter.
3. How to set the air deflection louver.
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions

to the customer.

CARE AND MAINTENANCE

The following may be performed by the equipment owner.

Outdoor Units

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before performing recommended maintenance, be sure unit

main power switch is turned off.

!

WARNING

CLEANING COILS — Coil should be washed out with
water or blown out with compressed air. Clean coil annu-

ally or as required by location and outdoor air condi-

tions. Inspect coil monthly and clean as required. Fins

are not continuous through coil sections. Dirt and debris

may pass through first section, become trapped between

the row of fins and restrict outdoor unit airflow. Use a
flashlight to determine if dirt or debris has collected be-

tween coil sections. Clean coil as follows:

1. Turn off unit power and install lockout tag.
2. Using a garden hose or other suitable equipment, flush

coil from the outside to remove dirt. Be sure to flush all

dirt and debris from drain holes in base of unit. Fan mo-

tors are waterproof.

Indoor Units

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
To avoid the possibility of electric shock, before performing

any cleaning and maintenance operations, always turn off

power to the system by pressing the ON/OFF button on the

remote control and turn off the separate disconnect switch

located near the unit.
If the indoor unit is on a separate switch, be sure to turn this

disconnect off as well.

WARNING

!

COMPONENT DAMAGE HAZARD

Failure to follow this may result in unit component damage.
Do not wash filter in water over 120

_

F (to avoid

shrinkage). Do not expose filter to fire (to avoid fire

damage). Do not expose filter to direct sunlight. Clean filter

more frequently when air is extremely dirty.

CAUTION

!

ELECTRICAL SHOCK, FIRE COMPONENT DAMAGE

HAZARD

Failure to follow this warning could result in personal

injury, death and or property damage.
Do not attempt to clean or service components in control

box.

WARNING

!

To Clean the Indoor Unit Front Panel

 — if the front panel of

the unit becomes dirty or smudged, wipe the out

side of the panel

with a soft dry cloth. Use a mild liquid deter

gent and wipe off

carefully with a dry cloth.

To Clean Indoor Coil

 — To clean the coil, remove indoor unit

front panel and vacuum the coil fins, using care not to bend or

damage fins.

LUBRICATION — The indoor

fan, automatic air sweep, and the

outdoor

fan motors are factory lubricated and require no oiling.

Air Filters for Indoor Units

COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in unit component

damage.
Operating your system with dirty air filters may damage the

indoor unit and, in addition, can cause reduced

performance, intermittent system operation, frost build up

on the indoor coil, and blown fuses. Inspect and clean or

replace the air filters monthly.

CAUTION

!

TO REMOVE AIR FILTERS — Open the unit’s front panel by

lifting the lower part and pulling it gently outward and upward.

Pull out the filters.

TO CLEAN OR REPLACE FILTERS — Filters can be

vacuumed or washed in warm water. Shake filter to remove any

excess water, and replace it back. If the filter has begun to break

Summary of Contents for DFS2A/H 2X09

Page 1: ...and NOTE The signal words DANGER WARNING CAUTION and NOTE are used to identify levels of hazard serious ness The signal word DANGER is only used on product labels to signify an immediate hazard The signal words WARNING CAUTION and NOTE will be used on product labels and throughout this manu al and other manuals that may apply to the product DANGER Immediate hazards which will result in se vere per...

Page 2: ...nd 2 for minimum required distances between unit and walls or ceilings S Indoor and outdoor units should be installed at a Mini mum length of 10 ft apart Maximum line length of 50 ft and vertical separation of 30 ft S Do not install indoor units near a direct source of heat such as direct sunlight steam or flame UNIT COMPONENT DAMAGE Failure to follow this caution may result in damage to unit comp...

Page 3: ...Cushions Electric Terminals Remote Controller Mounting Bracket Remote Controller and Batteries Insulation for Indoor Fittings Owner s Manual Wall mounted Receiver RTX 2 X 1 2 X 8 2 X 1 2 X 1 2 X 1 2 X 1 2 X 1 Mounting Bracket with 2 screws 2 X 8 4 1 OPTIONAL Not Included DFF2A DFF2H 09 12 Available for HEAT PUMP ONLY NADA001TW ...

Page 4: ... refrigerant lines Table 3 Physical Data Heat Pump INDOOR UNIT 2 X DFF2AH09J1A 2 X DFF2AH12J1A COOLING CAPACITY Btuh SEER 2 X 9 000 13 0 2 X 11 400 13 0 HEATING CAPACITY Btuh HSPF 17 200 7 7 23 600 7 7 SYSTEM CHARGE Ib 2 X 2 4 2 X 3 1 MOISTURE REMOVAL pt hr 2 X 2 6 2 X 4 5 AIRFLOW 3 Speeds High Med Low Cfm 2 X 350 2 X 280 2 X 220 2 X 350 2 X 280 2 X 220 DIMENSIONS LxHxW in 32 3 32x10 15 64x7 9 32 ...

Page 5: ... D I S T F E L W E I V P O T A C B 20 06 2006 GAD L EITANC NEW 5 8 1 0 6 2 5 1 8 0 3 2 5 3 6 5 3 6 7 2 1 0 4 0 5 7 2 8 0 2 3 6 9 1 6 0 1 4 1 2 1 7 5 1 6 0 9 5 2 8 2 7 3 2 0 1 0 6 2 5 1 8 0 3 2 5 3 6 5 8 1 7 2 1 0 4 0 5 7 2 5 3 6 4 1 2 1 5 2 b l 7 8 1 6 9 1 6 0 1 7 5 1 6 0 9 8 2 7 3 2 0 1 8 0 2 3 A 1 J 9 0 H A 2 F F D A 1 J 9 0 H H 2 F F D A 1 J 2 1 H A 2 F F D A 1 J 2 1 H H 2 F F D P C I ...

Page 6: ...TANC SUPERSEDES NEW REV W E I V P O T E G R A H C S I D R I A N I R I A VIEW S E C N A R A E L C M U M I N I M 1 E T O N E E S G N I T U O M T O L S N O I T C E N N O C R E W O P D L E I F N O I T C E N N O C L O R T N O C R E V O C S I H T R E D N U 3 E T O N E E S P Y T º 0 3 E N I L R O P A V A I D P N O I T C E N N O C E R A L F T R O P E C I V R E S N O I T C E N N O C E R A L F 5 2 T R O P E...

Page 7: ...en the indoor and outdoor units drill a 2 5 in hole through the wall for the refrigerant lines drainage hose and control cable passage as shown in Fig 5 1 Mark the center of the hole to be drilled according to the re frigerant line routing used and dimensions shown in Fig 4 2 Make sure to drill outwards and downwards so that the opening in the outside wall is at least 1 2 lower than the opening on...

Page 8: ...nect the outdoor sensor TH3 to its mating black terminal See Fig 9 FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Make sure that all wires and screws are firmly fastened WARNING REASSEMBLE 1 Connect the display connector to the display panel printed circuit board 2 Put the control box cover and grille frame back on using the appropriate scre...

Page 9: ...pper refrigerant tubing No other type of tubing may be used Use of other types of tubing will void the manufacturer s warranty Do not open service valves or remove protective caps from tubing ends until all the connections are made Bend tubing with special bending tools to avoid the formation of sharp bends Take care to avoid kinks or flattening of the tubing Keep the tubing free of dirt sand mois...

Page 10: ... expelled then refrigerant charge must be checked and adjusted Follow the steps below 1 Open the service port cap on the suction line valve large valve of unit No 1 2 Connect the vacuum pump to the service port of unit No 1 via the pressure gage and evacuate to 500 microns to eliminate contamination and moisture 3 Disconnect the vacuum pump Unit should maintain 500 microns for 5 minutes 4 Remove t...

Page 11: ...oth sections NOTE Specifications and performance data are subject to change with out notice 3095897 Table 5 Electrical Data Outdoor Units 115 1 60 UNIT VOLTAGE MCA MOCP FULL LOAD AMPS FAN MO TOR AMPS COM PRESSOR AMPS COMPRESSOR LOCKED ROTOR AMPS DFC2A 318J2A 115VAC 19 8 25 18 1 00 7 2 42 DFC2H 324J2A 115VAC 24 6 30 22 2 1 00 9 3 58 LEGEND MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protectio...

Page 12: ...6 J 7 J 8 J N A F S V R P M O C 8 1 J 6 K 5 K 1 K 2 K STEPPER R O T O M 8 K 9 K 7 K 1 1 J 4 1 J K L B D E R 1 3 V 2 1 V 2 1 K L B H W D E R N E E R G C D L B R O T O M 1 J 5 J 1 3 3 J 4 J 1 H T l o r t n o c 0 7 6 C A T n i a M 1 7 6 C A T d r a o B B 2 7 6 C A T l o r t n o C r o t o M M 1 2 3 L E Y L E Y R G 2 3 4 6 5 B T V T L H 1 R O R O D N G 3 H T K L B 1 2 3 4 5 6 BLK W H T BRN R ED BLK YEL...

Page 13: ... 5 B T V T L H 1 R O D N G K L B T I N U R O O D N I 2 H T H W N E E R G D E R 2 1 J 6 J 7 J 8 J N A F S V R P M O C 8 1 J 6 K 5 K 1 K 2 K STEPPER R O T O M 8 K 9 K 7 K 1 1 J 4 1 J K L B D E R 1 3 V 2 1 V 2 1 K L B H W D E R N E E R G C D L B R O T O M 1 J 5 J 1 3 3 J 4 J 1 H T l o r t n o c 0 7 6 C A T n i a M 1 7 6 C A T d r a o B B 2 7 6 C A T l o r t n o C r o t o M M 1 2 3 L E Y L E Y R G 2 3...

Page 14: ...nd install lockout tag 2 Using a garden hose or other suitable equipment flush coil from the outside to remove dirt Be sure to flush all dirt and debris from drain holes in base of unit Fan mo tors are waterproof Indoor Units ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death To avoid the possibility of electric shock before performing any cleaning and ...

Page 15: ...he start of each cooling season Check the flow by pouring water into the drain Clean or Replace Drain Pan The drain pan should only be cleaned or replaced by a qualified service technician 1 Place a plastic sheet on the floor to catch any water that may spill from the drain pan 2 Remove the intake grille and distribution assembly 3 Remove the condensate water in the drain pan by letting water drai...

Page 16: ...ect resistance Check for proper connection Replace thermistor if necessary 3 Flashes Low Pressure Check system pressures Check refrigerant charges Check thermistors TH1 and TH2 for correct resistance 4 Flashes High Pressure Check system pressures Check refrigerant charges Check thermistors TH1 and TH2 for correct resistance 5 Flashes Low Voltage Check operating voltage Check electrical connections...

Page 17: ...74 13 25 35 6 2 1 8 1 0 11 75 12 22 12 70 37 4 3 1 8 1 0 11 28 11 73 12 18 39 2 4 1 8 1 0 10 83 11 25 11 68 41 0 5 1 8 1 0 10 40 10 80 11 21 42 8 6 1 8 1 0 9 986 10 370 10 76 44 6 7 1 8 1 0 9 595 9 960 10 33 46 4 8 1 8 1 0 9 222 9 569 9 921 48 2 9 1 8 1 0 8 866 9 196 9 530 50 0 10 1 8 1 0 8 526 8 840 9 157 51 8 11 1 8 1 0 8 197 8 496 8 797 53 6 12 1 8 1 0 7 883 8 167 8 453 55 4 13 1 6 0 9 7 583 7 ...

Page 18: ...7 2 2 1 2 2 264 2 352 2 441 118 4 48 2 3 1 3 2 192 2 227 2 364 120 2 49 2 3 1 3 2 122 2 206 2 291 122 0 50 2 3 1 3 2 055 2 137 2 220 123 8 51 2 3 1 3 1 990 2 070 2 151 125 6 52 2 3 1 3 1 928 2 006 2 085 127 4 53 2 3 1 3 1 867 1 943 2 021 129 2 54 2 3 1 3 1 809 1 883 1 959 131 0 55 2 5 1 4 1 753 1 826 1 900 132 8 56 2 5 1 4 1 699 1 770 1 842 134 6 57 2 5 1 4 1 647 1 717 1 787 136 4 58 2 5 1 4 1 597...

Page 19: ... fan motor In Heat mode Delayed start for indoor fan motor Normal software delay maximum of 20 sec Clogged air filters Clean filters Low Capacity Lack of refrigerant Ice formation on the evapora tor coil Unit must be charged according to the nameplate after local izing the gas leak Clogged air filters Clean filters In Heat Mode Only Compressor Runs Out door and Indoor Fan Motors are Stopped A C op...

Reviews: