background image

484 01 3700 01

3

S

Place liquid filter dryer near ID unit to reduce the risk of
debris clogging the valve.

S

Make sure TXV bulb is securely fastened and wrapped in
the indentation on vapor line tube.

ENH4X Models:
These coils have a factory--installed hard--shutoff TXV

designed only for use with R--410A refrigerant. Use only

with outdoor units designed for R--410A.

NOTE

: All TXV’S have preset superheat settings and are

not field--adjustable.

Cabinet Sweating

If this unit is installed in a garage, attic, or other

unconditioned space, special attention needs to be given to

the potential of cabinet sweating. A 6 inch (152 mm) wide

piece of insulation should be wrapped around the coil

casing and supply duct connection point.

Condensate Management

With proper installation, these coils will manage the

condensate without blow--off into the duct work. The 60 size

coil requires the addition of a pan extension for both horizontal

left and horizontal right position, which is supplied with the

coils. See detailed instructions for more info. Also, refer to

Connect Condensate Drain Line section of this instruction.

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.

When installing over a finished ceiling and/or living area,

install a field--fabricated secondary condensate pan

under the entire unit.

CAUTION

!

HORIZONTAL--RIGHT AND

HORIZONTAL--LEFT WITH PAN EXTENSION

(5 Ton Size Only)

1. There are two separate pan extensions shipped with

the unit. For horizontal left installations, use the pan

attached to the left shipping bracket. For horizontal

right installations, use the pan attached to the right

shipping bracket. Be sure to use the correct pan

extension for the application. There should not be any

gaps between the plastic condensate pan and the

pan extension. All condensate should flow from the

pan extension to the plastic condensate pan and not

leak into the coil cabinet or duct.

NOTE

: Discard the pan not used along with both shipping

brackets.

2. For horizontal--left installation, install pan extension

onto left end of horizontal--condensate pan. Pan

extension is slotted to fit onto condensate pan edge

and will extend into supply plenum. See Figure 4.

Supply

Plenum

Condensate Pan

Pan Extension

A06032

Figure 4 -- Horizontal--Left Installation of Pan Extension

3. For horizontal--right installation, install pan extension

onto right end of horizontal--condensate pan. Pan

extension is slotted to fit onto condensate pan edge

and will extend into supply plenum. See Figure 5.

 

 

A09084

Figure 5 -- Horizontal--Right Installation of Pan

Extension

Installation Configurations

These units can be installed on a work platform, secured to

roof trusses in the attic, suspended from hangers on floor

joists in the crawl space, or installed on blocks. See proper

section and figures for detailed installation instructions.

NOTE

: Pan extension is needed for both horizontal left and

right applications. DO NOT DISCARD.

FURNACE ATTACHMENT

Attach coil to furnace

The attachment plates (3) and filler plate (1) are packaged

together and placed in the coil carton. Remove these items,

verifying the number of pieces. Use the following procedure

to attach ENH4X horizontal coil to furnace.

NOTE

: Remove shipping brace from both ends of casing

prior to installation. Also remove corrugated shipping block
from inside the right end of casing prior to installation.

1. Three attachment plates are used to attach coil to

furnace. Application determines which end of the coil

will be attached to the furnace.

2. Use self--tapping screws to mount attachment plates

to coil casing. See Figure 6.

Summary of Contents for ENH4X

Page 1: ...itions of the Canadian Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe ...

Page 2: ...ler Plate A08065 Figure 2 Horizontal Left Installation with Filler Plate Coil Ductwork Airflow Furnace Furnace Coil Ductwork Airflow Filler Plate Coil Ductwork Airflow Furnace Filler Plate Filler Plate A08066 Figure 3 Horizontal Right Installation with Filler Plate Airflow Airflow amount and distribution are vital to adequate system performance In addition heat pump applications require airflow in...

Page 3: ...e application There should not be any gaps between the plastic condensate pan and the pan extension All condensate should flow from the pan extension to the plastic condensate pan and not leak into the coil cabinet or duct NOTE Discard the pan not used along with both shipping brackets 2 For horizontal left installation install pan extension onto left end of horizontal condensate pan Pan extension...

Page 4: ... to four corners of coil casing see Figure 8 3 Use a minimum of two screws per corner to attach plumbers strap to casing 4 Position and secure coil in front of furnace discharge end 5 Make sure coil is level for proper condensate drainage 6 Using appropriate fasteners for duct type connect supply air duct to coil HORIZONTAL CRAWL SPACE INSTALLATION As an alternate to horizontal attic installation ...

Page 5: ...D Failure to follow this caution may result in property damage When installing over a finished ceiling and or living area install a field fabricated secondary condensate pan under the entire unit CAUTION The coil is designed to dispose of accumulated water through built in condensate drain fittings It is recommended that PVC fittings be used on the condensate pan Do not over tighten Finger tighten...

Page 6: ...nged period of time condensation can form on the bottom of pan and drip WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases See Fig 10 A10216 Figure 10 Condensate Drain to Waste Line EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death Provid...

Page 7: ... P Piston X TXV METERING DEVICE 18 18 000 BTUH 1 tons 19 18 000 BTUH 1 tons 24 24 000 BTUH 2 tons 30 30 000 BTUH 2 tons 31 30 000 BTUH 2 tons 36 36 000 BTUH 3 tons 37 36 000 BTUH 3 tons 42 42 000 BTUH 3 tons 43 42 000 BTUH 3 tons 48 48 000 BTUH 4 tons 60 60 000 BTUH 5 tons 61 60 000 BTUH 5 tons NOMINAL CAPACITY C Plain Copper L Aluminum T Tin Coated Copper HAIRPIN MATERIAL 14 14 3 16 17 17 1 2 21 ...

Reviews: