24
441 01 1411 04
Specifications are subject to change without notice.
Figure 33
−
HP with ECM Single
−
Stage Furnace, Humidi-
fier and Dehumidification
NOTES FOR Figure 27
−
Figure 33
1. Refer to outdoor equipment Installation Instructions for
additional information and setup procedure.
2. Outdoor Air Temperature Sensor must be attached in
all dual fuel application.
3. Refer to ICP thermostat Installation Instructions for ad-
ditional information and setup procedure.
4. When using a Humidity Sensing Thermostat, set DE-
HUMIDIFY OPTIONS to H DE
−
ENRGZD FOR DEHUM
5. HUM 24VAC terminal is 24 VAC and is energized when
the low pressure switch closes during a call for heat.
6. When connecting 115 VAC to humidifier use a separate
115 VAC supply.
7. When using a humidifier on a HP installation, connect
humidifier to hot water.
VENTING
The furnace shall be connected to a listed factory built
chimney or vent, or a clay
−
tile lined masonry or concrete
chimney. Venting into an unlined masonry chimney or
concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced,
the original venting system may no longer be sized to
properly vent the attached appliances. An improperly sized
Category I venting system could cause the formation of
condensate in the furnace and vent, leakage of condensate
and combustion products, and spillage of combustion
products into the living space.
Vent system or vent connectors may need to be resized. Vent
systems or vent connectors, must be sized to approach
minimum size as determined using appropriate table found in
the NFGC.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death. The following steps shall be followed for each
appliance connected to the venting system being placed
into operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54. Determine that
there is no blockage or restriction, leakage,
corrosion and other deficiencies, which could
cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system
are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they are operating at maximum
speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the
thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped
appliances at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of
a match or candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54.
9. After it has been determined that each appliance
connected to the venting system properly vents
when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any
other gas
−
fired burning appliance to their previous
conditions of use.
!
WARNING
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National
Fuel Gas Code ANSI Z223.1
−
2012/NFPA 54
−
2012 (NFGC),
Parts 12 and 13, the local building codes, and furnace and
vent manufacturers’ instructions.
These furnaces are design
−
certified as Category I furnaces in
accordance with ANSI Z21.47
−
2012/CSA 2.3
−
2012 and
operate with a non
−
positive vent static pressure to minimize
the potential for vent gas leakage. Category I furnaces
operate with a flue loss not less than 17 percent to minimize
the potential for condensation in the venting system. These
furnaces are approved for common venting and multistory
venting with other fan assisted or draft hood equipped
appliances in accordance with the NFGC, the local building
codes, and furnace and vent manufacturers’ instructions. The