background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: (F/G)9MXT

Specifications  subject to change without notice.

10

440 04 4321 02

Adjust Continuous Fan Airflow

The Continuous Fan airflow can be set from the remaining
blower speed taps. Refer to the Air Delivery Tables in these
instructions.

FIRE HAZARD

Failure to follow this warning could result in personal injury,
death, and/or property damage.

Reinstall manifold pressure tap plug in gas valve to
prevent gas leak.

!

WARNING

FURNACE OVERHEATING HAZARD

Failure to follow this caution may result in reduced furnace
life.

Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
midpoint of rise range or slightly above.

CAUTION

!

Adjust Thermostat Heat Anticipator

When using a nonelectronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of the electrical
components in RW circuit.  Accurate amp draw readings can
be obtained at the thermostat subbase terminals R and W.

Figure 5

 illustrates the easy method of obtaining actual amp

draw.  The amp reading should be taken after blower motor has
started and furnace is heating.  Connect ammeter wires as
shown in 

Figure 5

.  The thermostat anticipator should not be in

the circuit while measuring current.  If thermostat has no
subbase, the thermostat must be disconnected from R and W
wires during current measurement.  See thermostat
manufacturer’s instructions for adjusting heat anticipator and for
varying heating cycle length.  For an electronic thermostat, set
cycle rate for 3 cycles per hour.

Figure 5

Amp. Draw Check with Ammeter

A96316

R Y W G

10 TURNS

THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)

HOOKAROUND
AMMETER

EXAMPLE:

5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS

 

=

FROM UNIT 24V
CONTROL TERMINALS

Check Safety Controls

The flame sensor, gas valve, and pressure switch were all
checked in the Startup procedure section as part of normal
operation.

1. Check Main Limit Switch 

This control shuts off combustion system and energizes
aircirculating blower motor, if furnace overheats. By
using this method to check limit control, it can be
established that limit is functioning properly and will
operate if there is a restricted returnair supply or motor
failure. If limit control does not function during this test,
cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of

cardboard or sheet metal until the limit trips.

c. Unblock return air to permit normal circulation.

d. Burners will relight when furnace cools down.

2. Check Pressure Switch(es) 

This control proves operation of the draft inducer blower.
a. Turn off 115V power to furnace.
b. Disconnect inducer motor lead wires from wire

harness.

c. Turn on 115V power to furnace.

d. Set thermostat to “call for heat” and wait 1 minute.

When pressure switch is functioning properly, hot
surface igniter should 

NOT 

glow and control

diagnostic light flashes a status code 3. If hot surface
igniter glows when inducer motor is disconnected,
shut down furnace immediately.

e. Determine reason pressure switch did not function

properly and correct condition.

f. Turn off 115V power to furnace.

g. Reconnect inducer motor wires, replace outer door,

and turn on 115V power.

h. Blower will run for 90 seconds before beginning the

call for heat again.

i. Furnace should ignite normally.

Checklist

1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/TWIN

terminal. Verify that there is nothing plugged into the PLT
connector.

NOTE

:  Note: If there is a jumper connector plugged into PLT,

remove it and discard. (See 

Figure 4

)

3. Verify that (TT) switch SW-1 is set properly.  (See

Figure 4)

4. Verify that the Heat OffDelay SW2 and SW3 switches

are set as desired. (See 

Figure 4)

5. Verify that the blower and control (“Main”) doors are

properly installed.

6. Verify that the Status LED glows. If not, check that the

power supply is energized and that the blower door is
secure. (See 

Figure 14

) to interpret diagnostic codes.

7. Cycle test furnace with room thermostat to be sure that it

operates properly with the room thermostat. Check all
modes including Heat, Cool and Fan.

8. Check operation of accessories per manufacturer’s

instructions.

9. Review Home Owner’s Information with owner.

10. Attach entire literature packet to furnace.

Summary of Contents for F9MXT0401410A

Page 1: ...bination with colors and or pictures or product labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury TABLE OF CONTENTS START UP ADJUSTMENT AND SAFETY CHECK 4 THERMOSTAT SETUP SWITCH 4 PRIME CONDENSATE TRAP WITH WATER 4 PURGE GAS LINE...

Page 2: ...death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this w...

Page 3: ...Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Shade in Heating Fan Time OFF Setting and Thermostat Type setting ON OFF 1 2 3 TT OFF DLY Calculated Input BTU Rate See Checks and Adjustments Section Heating Check Measured Line Pressure During High Heat Measured Manifold Pressure High Heat Low Heat Temperature of Supply Air High Heat Low Heat Temperature of Ret...

Page 4: ... thermostat W to W W1 at furnace control terminal block See Figure 7 For single stage thermostats the control will operate for 12 minutes on low heat then switch to high heat if heat call remains Setup switch TT must be in the factory shipped OFF position See Figure 7 and Figure 15 for setup switch information If a two stage heating thermostat is to be used move setup switch TT to ON position befo...

Page 5: ... heat value and specific gravity lines to point of intersection to find orifice size and low and high heat manifold pressure settings for proper operation f Check and verify burner orifice size in furnace NEVER ASSUME ORIFICE SIZE ALWAYS CHECK AND VERIFY Table 1 Altitude Derate Multiplier for U S A ALTITUDE FT M PERCENT OF DERATE DERATE MULTIPLIER FACTOR 0 2000 0 610 0 1 00 2001 3000 610 914 4 6 0...

Page 6: ...o increase input rate NOTE DO NOT set high heat manifold pressure less than 3 2 in w c or more than 3 8 in w c for natural gas If manifold pressure is outside this range change main burner orifices to obtain manifold pressure in this range c When correct input is obtained replace caps that conceal gas valve regulator adjustment screws Main burner flame should be clear blue almost transparent See F...

Page 7: ...3 8 1 6 42 3 2 1 4 850 44 3 8 1 6 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 875 44 3 6 1 5 44 3 7 1 6 43 3 4 1 4 43 3 5 1 5 4000 900 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 1219 925 44 3 2 1 4 44 3 4 1 4 44 3 5 1 5 44 3 6 1 5 950 45 3 7 1 6 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 750 42 3 3 1 4 42 3 4 1 4 42 3 5 1 5 42 3 6 1 5 4001 775 43 3 7 1 6 43 3 8 1 6 42 3 3 1 4 42 3 4 1 4 1220 800 43 3 5 1 5 43 3 6 1 5...

Page 8: ... 1 6 9000 750 44 3 3 1 4 44 3 4 1 4 44 3 5 1 5 44 3 6 1 5 2743 775 45 3 7 1 6 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 9001 600 42 3 3 1 4 42 3 4 1 5 42 3 6 1 5 42 3 7 1 6 2744 625 43 3 7 1 6 42 3 2 1 3 42 3 3 1 4 42 3 4 1 4 650 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 43 3 8 1 6 675 44 3 7 1 6 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 10000 700 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 3048 725 44 3 2 1 3 44 3 3 1 4 44...

Page 9: ...pply ducts for excessive restrictions causing static pressures greater than 0 50 in w c d Adjust temperature rise by adjusting blower speed e Increase blower speed to reduce temperature rise f Decrease blower speed to increase temperature rise ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Disconnect 115V electrical power before changing speed t...

Page 10: ...otor if furnace overheats By using this method to check limit control it can be established that limit is functioning properly and will operate if there is a restricted return air supply or motor failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sheet ...

Page 11: ... 375 120 30 60 150 49 73 147 367 Table 6 AIR DELIVERY CFM with filter INPUT BTUH RETURN AIR SUPPLY SPEED EXTERNAL STATIC PRESSURE in w c 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 40 000 SIDE BOTTOM 5 Gry 1120 1080 1030 980 925 875 820 760 690 630 4 Yel 880 845 810 780 740 710 680 640 615 570 3 Blu 695 665 620 575 535 495 455 420 370 280 2 Org 640 595 540 495 460 420 370 310 260 230 1 Red 570 525 475 4...

Page 12: ...n to component location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the furnace Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing Lock out and tag swi...

Page 13: ...urnace control component test allows all components to run for a short time except the gas valve and humidifier terminal HUM are not energized The EAC 1 terminal is energized when the blower is energized The HUM terminal is energized when the inducer is energized This feature helps diagnose a system problem in case of a component failure The component test feature will not operate if any thermosta...

Page 14: ... necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency 5 Inspect the vent pipe vent system before each heating season for water leakage sagging pipes or broken fittings Have vent pipes vent system serviced by a qualified service agency 6 Inspect any accessories attached...

Page 15: ... balance will be affected 7 If greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b Loosen setscrew holding blower wheel on motor shaft NOTE Mark blower mounting arms and blower housing so each arm is positioned at the same hole ...

Page 16: ...mage Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service Follow the operating instructions on the label attached to the furnace WARNING Refer to Figure 9 1 Disconnect power at external disconnect fuse or circuit breaker 2 Turn off gas at external shut off or gas meter 3 Remove control door and set aside 4 Turn electric switch...

Page 17: ...e Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Figure 10 and Figure 11 1 Turn off gas and electrical supplies to furnace 2 Remove control door 3 Disconnect igniter wire connection 4 Check igniter resistance Igniter resistance is affected by temperature Only check resistance when the igniter is at room tempera...

Page 18: ...ach the relief hose to the relief port on the condensate trap and collector box 5 Secure tubing to prevent any sags or traps in the tubing 6 Connect condensate drain elbow or drain extension elbow to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or drain extension pipe 9 Turn gas on at electric switch on gas...

Page 19: ...amage If the furnace is installed in an unconditioned space where the ambient temperatures may be 32_ F 0_ C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result of the heat transfer process Therefore once it has been operated it cannot be turned off and ...

Page 20: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MXT Specifications subject to change without notice 440 04 4321 02 20 Figure 14 Service Label 338313 2E ...

Page 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MXT Specifications subject to change without notice 21 440 04 4321 02 Figure 15 Wiring Diagram 338313 2 Rev E ...

Page 22: ...be turned on Inducer motor will start in HIGH speed and remain on HIGH until the end of the blower test then shift to LOW speed for 7 to 15 seconds the following components are on for 10 15 seconds each individually hot surface igniter blower speeds LO HEAT HI HEAT COOL Was there a previous status code Go to section below for the flashed status code Does the control respond to W W1 W2 Y1 Y Y2 and ...

Page 23: ...K check burner carryover and flame sensor location Clean flame sensor with fine steel wool and recheck current Nominal current is 4 0 to 6 0 A DC Is current near typical value Replace electrode Will main burners ignite and stay on Replace furnace control Fixed YES YES NO NO Replace furnace control Check for continuity in the harness and igniter Replace defective component Reconnect the R thermosta...

Page 24: ...utes after ignition If HPS doesn t close after 2 minutes from LPS closing GV is turned off and heat off delay is completed Then a new cycle will begin if a call for heat remains b Igniter Warm Up At the end of the prepurge period the Hot Surface Igniter HSI is energized for a 17 second igniter warm up period c Trial for Ignition Sequence When the igniter warm up period is completed the main gas va...

Page 25: ... and Y1 or R to G and Y1 and Y2circuits are opened The outdoor unit stops and the furnace blower BLWM and electronic air cleaner terminal EAC 1 AMP will remain energized for an additional 90 seconds Jumper Y1 to DHUM to reduce the cooling off delay to 5 seconds See Figure 4 17 Dehumidify Mode See Figure 17 Figure 22 for humidity sensing thermostat connections The dehumidification output H on the h...

Page 26: ...and Y Y2 and G circuits are energized the furnace control CPU will switch to or turn on the blower motor BLWM at COOL speed and begin a high heat cycle The blower motor BLWM will remain on until the end of the prepurge period then shut off for 24 seconds then come back on at HI HEAT speed When the W W1 input signal disappears the furnace control begins a normal inducer post purge period and the bl...

Page 27: ...re 2 Outdoor Air Temperature Sensor must be attached in all dual fuel application 3 Refer to ICP thermostat Installation Instructions for additional information and setup procedure 4 When using a Humidity Sensing Thermostat set DEHUMIDIFY OPTIONS to H DE ENRGZD FOR DEHUM 5 Optional connection for Two Stage If wire is connected SW1 1 TT on furnace control should be set to ON position to allow ICP T...

Page 28: ...e when used Inducer motor capacitor when used Collector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation personal injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning ex...

Page 29: ...T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 040 40 000 BTU hr 060 60 000 BTU hr 080 80 000 BTU hr 100 100 000 BTU hr 120 120 000 BTU hr INPUT HEAT 14 14 3 16 17 17 1 2 21 21 24 24 1 2 CABINET WIDTH 10 1000 CFM max 14 1400 CFM max 16 1600 CFM max 20 2000 CFM...

Reviews: