INSTALLATION INSTRUCTIONS
Gas Furnace: N9MSE
10
440 01 4103 03
Specifications subject to change without notice.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (25.4 square mm)of free area per 3,000 Btuh
(734 mm
2
/kW) for combined input of all gas
appliances in the space per
Table 3
and
b. Not less than the sum of the areas of all vent
connectors in the space.
The opening shall commence within 12-in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at
least 1-in. (25 mm) from the sides and back and 6-in. (150 mm)
from the front. The opening shall directly communicate with the
outdoors or shall communicate through a vertical or horizontal
duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
Indoor Combustion Air
NFPA & AGA
Standard and Known-Air-Infiltration Rate
Methods
Indoor combustion air
is permitted for combustion, ventilation,
and dilution, if the
Standard
or
Known-Air-Infiltration Rate
Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Many homes require air to be supplied from outdoors
for furnace combustion, ventilation, and dilution of flue
gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
Figure 6
Air for Combustion, Ventilation,
and Dilution for Outdoors
*Minimum dimensions of 3‐in. (76mm)
NOTE
: Use any of the following combinations of openings:
A & B, C & D, D & E, F & G
L12F012
The
Standard
Method:
1. The space has no less volume than 50 cubic feet per
1,000 Btuh (4.8 cubic meters per kW) of the maximum
input ratings for all gas appliances installed in the space
and
2. The air infiltration rate is not known to be less than 0.40
air changes per hour (ACH).
The
Known Air Infiltration Rate
Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number
of ACH and shall be determined per
Table 4
or Equations 1
and 2. Determine the minimum required volume for each
appliance in the space and add the volumes together to get the
total minimum required volume for the space.
Table 4
−
Minimum Space Volumes
were determined by
using the following equations from the National Fuel Gas Code
ANSI Z223.1/NFPA 54
−
2012, 9.3.2.2:
1. For
other than fan-assisted appliances
, such as a
draft hood-equipped water heater
A04002
2. For
fan-assisted appliances
such as this furnace:
A04003
If:
I
other
=combined input of all
other than fan-assisted
appliances
in Btuh/hr
I
fan
=combined input of all
fan-assisted appliances
in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the
Standard
Method and
to the
Known Air Infiltration Rate
Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1-in.
2
/1,000 Btuh
(2,000 mm
2
/kW) of the total input rating of all gas
appliances in the space, but not less than 100-in.
2
(0.06 m
2
). One opening shall commence within 12
−
in.
(300 mm) of the ceiling and the second opening shall
commence within 12-in. (300 mm) of the floor. The
minimum dimension of air openings shall be at least
3-in. (80 mm). (See
Figure 7
)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be
considered as communicating spaces if connected by
one or more permanent openings in doors or floors
having free area of at least 2
−
in.
2
/1,000 Btuh
(4,400 mm
2
/kW) of total input rating of all
gas appliances.
2. An attic or crawlspace may be considered a space that
freely communicates with the outdoors provided there
are adequate permanent ventilation openings directly to
outdoors having free area of at least 1-in.
2
/4,000 Btuh of
total input rating for all gas appliances in the space.