INSTALLATION INSTRUCTIONS
Gas Furnace: N9MSE
8
440 01 4103 03
Specifications subject to change without notice.
Figure 3
Multipoise Orientations
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
L12F010
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least
18
−
in. (457 mm) above the floor. The furnace must be
located or protected to avoid damage by vehicles. When
the furnace is installed in a public garage, airplane
hangar, or other building having a hazardous
atmosphere, the furnace must be installed in accordance
with the NFPA 54/ANSI Z223.1
−
2012 or CAN/CSA
B149.1
−
2010. (See
Figure 4
)
Figure 4
Installation in a Garage
A93044
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect re-
turn
−
air ducts to the back of the furnace. (See
Figure 5
)
Figure 5
Prohibit Installations
BACK POSITIONED
DOWNWARD
AIR
RETURN
CUT IN
BACK
BACK POSITIONED
UPWARD
L12F011