background image

443 06 4003 00

15

Specifications  subject to change without notice.

When correct input is obtained, make sure cap that conceals

gas valve regulator adjustment screw is oriented properly for

natural (NAT) gas. The NAT arrow should be pointing toward

gas valve. (See 

Figure 23

)

10. Remove jumper across R and W thermostat connections

to terminate call for heat.

11. Turn furnace gas valve control knob or switch to OFF

position.

12. Turn gas supply manual shutoff valve to OFF position.
13. Turn off furnace power supply.
14. Remove manometer and replace manifold pressure tab

plug. (See 

Figure 25

)

15. Turn furnace gas

valve switch to ON position.

16. Turn on furnace power supply.
17. Set room thermostat to call for heat.
18. Check pressure tap plug for gas leaks when main

burners ignite.

19. Check for correct burner flame. (See 

Figure 22

)

20. Observe unit operation through two complete heating

cycles.

21. See Sequence of Operation in furnace Installation,

Start

Up, and Operating Instructions.

22. Set room thermostat to desired temperature.
23. After making the required manifold pressure

adjustments, check and adjust the furnace temperature

rise per the furnace installation instructions.

24. Verify Natural Gas Input Rate By Clocking Gas Meter.

NOTE

:  Be sure all pressure tubing, combustion-air and vent

pipes, and burner enclosure front are in place when checking

input by clocking gas meter.

a. Calculate high-altitude adjustment (if required).

UNITED STATES
At altitudes above 2000 ft, this furnace has been approved for a

2 percent derate for each 1000 ft above sea level. See 

Table 2

for derate multiplier factor.
CANADA
At installation altitudes from 2000 to 4500 ft, this furnace must

be derated 5 percent by an authorized Gas Conversion Station

or Dealer.
To determine correct input rate for altitude, see example above

and use 0.95 as derate multiplier factor.

b. Turn off all other gas appliances and pilots.

c. Start furnace and let operate for 3 minutes.

d. Measure time (in sec) for gas meter test dial to

complete one revolution.

e. Refer to 

Table 4

 for cu ft of gas per hr.

f. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)

using natural gas heating value from local gas

utility/supplier.

g. Fill in Conversion Responsibility Label (321102-101)

located on inside of main furnace door. Date, name,

and address of organization making the conversion is

required.

h. Check for gas leaks.

Table 2

Altitude Derate Multiplier for U.S.A.

ALTITUDE

PERCENT

OF

DERATE

 DERATE

MULTIPLIER

FACTOR*

FT.

 M

0–2000

 0

610

0

1.00

2001–3000

 610

914

4

6

0.95

3001–4000

 914

1219

6

8

0.93

4001–5000

 1219

1524

8

10

0.91

5001–6000

 1524

1829

10

12

0.89

6001–7000

 1829

2134

12

14

0.87

7001–8000

2134

2438

14

16

0.85

8001–9000

2438

2743

16

18

0.83

9001–10,000

2743

3048

18

20

0.81

*Derate multiplier factors are based on midpoint altitude for altitude range.

!

WARNING

FIRE AND EXPLOSION HAZARD

Failure to follow this warning could result in personal injury

and/or death.
NEVER test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections. A fire or

explosion may result causing property damage, personal

injury or loss of life.

!

AVERTISSEMENT

RISQUE D’EXPLOSION ET D’INCENDIE

Le fait de ne pas suivre cet avertissement pourrait entraîner

des dommages corporels et / ou la mort.
Ne jamais examiner pour les fuites de gaz avec une flamme

vive. Utilisez plutôt un savon fait specifiquement pour la

détection des fuites de gaz pour verifier tous les connections.

Un incendie ou une explosion peut entrainer des dommages

matériels, des blessures ou la mort.

LABEL MODIFICATION

NOTE

:  See 

Figure 6, Figure 7

 and 

Figure 8

 for label location.

1. Fill in Conversion Responsibility Label (334973

101)

previously applied to inside of main furnace door by

installer. Date, name, and address of organization

making this conversion are required. Specify that unit is

now converted for use with natural gas.

2. Place ALL unused parts, adjusting key, and these

Installation Instructions in adhesive pouch attached to

outside of main furnace door or accessible side of

furnace.

3. Reinstall main furnace door.

Summary of Contents for NAHB00101MH

Page 1: ...hat may apply Follow all safety codes In the United States follow all safety codes including the current edition of the National Fuel Gas Code NFGC NFPA No 54 ANSI Z223 1 In Canada refer to the curren...

Page 2: ...Gas to Propane SECTION III Conversion from Propane to Natural Gas SECTION I INITIAL KIT INSTALLATION Procedure 1 General A downflow furnace application is where furnace blower is located above combust...

Page 3: ...SING IS NOT INSTALLED NOT SHOWN 1 Accessory floor base MUST be used Review floor base Installation Instructions before installation 2 Secure accessory floor base to structure using 5 16 in 8 mm lag sc...

Page 4: ...tor harness from gas valve Disconnect wires from Hot Surface Igniter HSI and Flame Sensor See Figure 9 8 Support the manifold and remove the four 4 screws that secure the manifold assembly to the burn...

Page 5: ...igure 8 for label location 1 Attach Conversion Responsibility Label 340323 101 inside of main furnace door See Figure 7 Date name and address of organization making this conversion are required See Fi...

Page 6: ...n furnace rating plate is for installations at altitudes up to 2000 ft 610 M In the U S A the input rating for altitudes above 2000 ft 610 M must be reduced by 2 percent for each 1000 ft 305 M above s...

Page 7: ...Figure 14 Igniter Position Back View 2 1 2 in 64 4 1 1 4 in 31 8 A11405 Figure 15 Igniter Position Side View A12392 2 in 2 5 mm 3 8 in 3 16 in 0 8 1 5 50 mm 9 6 mm 4 6 mm 3 32 in 1 32 3 64 in Figure 1...

Page 8: ...iels des blessures ou la mort 2 Apply pipe dope sparingly to the male threads of the 1 8 in black iron street elbow Install the street elbow into the gas valve inlet pressure tap Point the open end of...

Page 9: ...re 9 2 Align the orifices in the manifold assembly with the support rings on the end of the burner 3 Insert the orifices in the support rings of the burners Manifold mounting tabs should fit flush aga...

Page 10: ...osition CHECK FURNACE AND MAKE ADJUSTMENTS 1 Be sure main gas and electric supplies to furnace are off 2 Remove 1 8 in 3 mm pipe plug from manifold pressure tap on downstream side of gas valve 3 Attac...

Page 11: ...lamme vive Utilisez plut t un savon fait specifiquement pour la d tection des fuites de gaz pour verifier tous les connections Un incendie ou une explosion peut entrainer des dommages mat riels des bl...

Page 12: ...by manifold pressure and orifice size Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft 610 M In the U S A the input rating for altitudes above 2000 ft 610M must...

Page 13: ...e 1 8 in NPT pipe plug from the tee fitting on the Low Gas Pressure Switch 5 Remove the Low Gas Pressure Switch from fittings on gas valve and discard 6 Remove remaining fittings from gas valve and di...

Page 14: ...with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal inj...

Page 15: ...for gas meter test dial to complete one revolution e Refer to Table 4 for cu ft of gas per hr f Multiply gas rate cu ft hr X heating value Btu cu ft using natural gas heating value from local gas uti...

Page 16: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 17: ...3 3 42 3 4 2134 700 43 3 5 43 3 7 43 3 8 42 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44...

Page 18: ...313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120...

Reviews: