Operating Instructions CP BLOCKTHERM D.A HI

HOM160086923Ien-1

Page 4 / 7

INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany · 

 +49 9445 9532-0 ·   info@intertec.info

 CAUTION

Risk of burns from a hot surface

Attainable highest temperatures:

- Max. 160°C with T3 heating systems

- Max. 100°C with T4 heating systems

- Max. 70°C with T5 heating systems

- Max. 50°C with T6 heating systems

Do not touch device during operation! Before working on
the device, allow it to cool down first.

5

Technical Data

Protection class

IP66/IP68 1bar/30min

Rated voltage

max. 250 V AC

Permitted operating voltage

max. 275 V AC

Rated current (in compli-

ance with VDE 0298)

max. 10 A

Ambient temperature

- 60 to + 60 °C

Max. permitted operating

temperature

- 60 to + 180 °C

Switching capacity of fault

alarm (AM)

10 A / 275 V AC

Connecting cable

Silicone hose cable, notch-

and oil resistant, 3 x 1,5

mm² Ø8,8 mm

Connecting cable AM

Silicone hose cable, notch-

and oil resistant, 5 x 1,0

mm² Ø8,5 mm

Material

Seawater-proof aluminium,

black anodized

Special  voltages  with  corresponding  power  adjustment
and component selection are possible.

Profile type "K" Length x

Width x Height

90 x 40 x 30

mm

Profile type "L" Length x

Width x Height

105 x 40 x 30

mm

Profile type "P" Length x

Width x Height

225 x 50 x 45

mm

 INFO

You will find the precise technical data for your in-
strument on the label.

Temperature class

Rated voltage / Operating voltage

High temperature version

Rated output

Illustration 1: 

Example: CP BLOCKTHERM DPA 500 T4 HI la-

bel

6

Installation

NOTICE

Carefully remove

When removing from the packaging and during trans-
port, the connection line must not be stressed or bent.

If  an  additional  TAE  thermostat  is  switched  in  series,
then  it  can  be  attached  to  the  surface  of  the  heater
(thermal coupling). The minimum distance also needs to
be adhered to here. Refer to the following drawing.

To  ensure  operational  safety,  the  heater  must  operate
under temperature conditions which will NOT exceed the
trigger temperature of the limiter.

The operating temperatures must be adhered to.

The  connection  cable  must  be  permanently  installed  up
to  the  inlet  into  the  on-site  junction  box,  taking  the  per-
missible bending radius = 5 x outer diameter into consid-
eration.

In  the  dust  Ex  area,  the  applicable  requirements  of  EN
60079-14 must be complied with.