Figure 32
5/32” GAP
ELECTRODE
NOZZLE
0-1/16”
5/16” ABOVE CL
1 1/8”
Figure 32. oil Gun electrode Position
Gas Gun (M1B Models)
Combustion air box adjustment is made to the main burner
by loosening the two lock nuts on the plastic air shutter,
located on the left side of the burner blower housing. Air
shutter adjustment line is located on the same side of
the blower housing. Turn the plastic shutter to a smaller
number (counter clockwise) for less air to a larger number
(clockwise) for more air. Gently tighten the lock nuts after
completing the adjustment. For best results, use instrument
to measure between 8 - 9% CO
2
, after the combustion air
has been adjusted.
notE:
Do not over-tighten the lock
nuts. This may damage the plastic air shutter.
Oil Gun Only (M5S Models)
It is recommended that the CO
2
and Smoke levels be
measured for maximum performance. CO
2
readings should
be 10 - 11% for 66,000 BTUH furnaces and 12 - 13% for
86,000 BTUH furnaces. The Smoke should be N0. 0 on
the Bacharach Scale, and 0 to 0.02 negative draft over fire.
Electrode setting (oil Gun only)
Poor ignition of the oil spray may result if the electrodes
are not adjusted as shown in
any electrodes to be grounded to any surface.
switching Ignition control between
Interrupted and Intermittent Duty
(oil Gun only)
Honeywell and Beckett oil primary controls can be switched
between interrupted and intermittent ignition control. To
switch from interrupted duty (Factory set) to intermittent
duty, remove the blue wire from the quick-connect terminal.
Attach the burner motor and igniter wire to the burner
motor (orange) control terminal by splicing or adding tab
adapters. Seal and isolate any bare wires.
oPERatInG sEQuEncE
Direct Ignition Furnaces (M1M Models)
1. On a call for heat, the thermostat contacts close,
supplying 24 VAC between terminals
C
and
W
of the
control module.
2. When the inducer starts, the air pressure switch closes
at -0.20 W.C. differential pressure and energizes the
gas valve.
3. After a 45 second purge, the ignitor is energized for a 30
second warm-up period. After warm up, the gas valve
opens.
notE:
The time for ignition is approximately 6
seconds, after which the gas valve either remains open
if flame is sensed, or closes if flame is not sensed.
5. If flame is not sensed, the sequence repeats four more
times before a lockout occurs. To reset, wait 30 seconds
and then interrupt the 24 VAC power by turning the room
thermostat below room temperature, then returning it
to the original set point.
6. If flame does not establish on the 5th attempt (initial
fire + 4 re-tries), the control de-energizes the gas valve,
the
red LED flashes 4 times, and the furnace locks out
heat operation for 1 hour. See
7. If a flame is present, the control energizes the main
blower on heat speed 30 seconds after the gas valve
opens.
8. When call for heat is satisfied the thermostat contacts
open, the gas valve shuts off gas flow and the combustion
blower remains on for a 30 second post-purge period.
9. The main blower is de-energized after a 120 second
blower off delay.
Oil Gun Furnaces (M5S Models)
With Honeywell R7184 / Beckett 7505 Control
1. When a call for heat is initiated, there is a 2 to 6 second
delay while the control performs a safe start check.
2. The ignition and motor are turned on and a flame
should establish within a 15-second lockout time.
notE:
Burner will prepurge for 15 seconds if equipped
with Honeywell R7184B or Beckett 7505B Control.
3. If flame is not sensed within the 15-second lockout
time, the control shuts down on safety lockout and must
be manually reset by pushing the reset button on the
control. If control locks over three times in a row, the
control enters restricted lockout. To reset Honeywell
R7184: Hold down the reset button for 45 seconds until
the LED flashes once. Beckett 7505: Hold down reset
button for 15 seconds until the
red
LED turns off and
the
yellow
LED turns on.
WaRnInG:
If furnace still doesn’t light, turn the furnace off
as described above and call your technician. In
the event of flashback or explosion, immediately
shut off furnace and call your service technician.
4. After flame is established, the ignition remains on for
10 seconds to ensure flame stability. It then turns off.